Iowa State University
Facilities Planning and Management
FP&M Home Campus Space Data Planning / Design / Construction Operation / Maintenance / Repair Utility Services

Request for Services Form

View a Service Request

Service Request #

SR264892 has been converted into Project PR015066.

Requestor COCHRAN, RONALD E
Location FORKER 
Description TAKE CORRECTIVE ACTION WITH GYM LIGHTING 
Details Cost range will be provided
ITEMS: LIGHTING
Per Travelers insurance report need to take corrective action with Gym lighting per attached:
Metal halide lights were noted throughout the gym area. Metal halide lights have been known to fail catastrophically, showering molten glass fragments onto surfaces and objects beneath the light. In order to contain these fragments, one of the following should be done:

* Replace the metal halide lights with UL-listed glass fixtures that have integral containment barriers, constructed of tempered or borosilicate glass. The fixtures should be designed to contain molten fragments of quartz or glass (up to 1100C).

* Modify existing fixtures by installing tempered or borosilicate glass containment barriers or enclosures. Consult the original fixture manufacturer when planning modifications. Use the manufacturer's listed components and retrofit kits, if available.

* Replace existing lamps (bulbs) with lamps that have an int
Status PROJECT REQUESTED - ASSIGNED TO REVIEW TEAM
Contact Lola Van Wyk
4-8313
Const Start  
Const Due  

Questions about this request should be directed to the FP&M Project Coordination Center.