Year Constructed:
1924 / 1941
89,563 Gross Square Feet
| # |
Exemptions |
Summer |
Winter |
| 1 |
Design Studio Space |
24/7 |
24/7 |
| 2 |
(FC1) Operate DPS Occupied Areas (rooms 55, 162, 166, & 168) |
24/7 |
24/7 |
| Unit |
Service Area |
Cool |
Heat |
System Type |
Summer Hours |
Winter Hours |
| AHU1 |
SW Floor and bleachers |
|
Yes |
Constant Volume
|
24/7 |
24/7 |
| AHU2 |
Room 163 - Old Rifle Range |
|
Yes |
Constant Volume
|
Unit not used 24/7 = off |
Unit not used 24/7 = off |
| AHU3 |
East Floor, NE bleachers |
|
Yes |
Constant Volume
|
24/7 |
24/7 |
| AHU4 |
Main Floor, NE Bleachers |
|
Yes |
Constant Volume
|
24/7 |
24/7 |
| AHU5 |
West side of Building |
Yes |
Yes |
Mixed Air HVAC System
|
Local Control |
Local Control |
| FC1 |
Rooms 100,104,141 Fan Coil Unit control - Group 1, 2, 3 |
Yes |
Yes |
Fan Coil Unit with Occupant Thermostat
|
Room Scheduling |
Room Scheduling |
| AHU6 |
Navy and Army rooms 1st and 2nd floor East side |
Yes |
Yes |
Mixed Air HVAC System
|
24/7 |
24/7 |
| Unit |
Service Area |
Control Strategies |
| AHU1 |
SW Floor and bleachers |
Fan cycles based on outdoor air temperature (@ 50 degrees) and inside space temperature (room 86 @ 68 degrees) |
| AHU2 |
Room 163 - Old Rifle Range |
Unit not used |
| AHU3 |
East Floor, NE bleachers |
Fan cycles based on outdoor air temperature @ 0 degrees |
| AHU4 |
Main Floor, NE Bleachers |
Fan cycles based on outdoor air temperature (@ 50 degrees) and inside space temperature (room 86 @ 68 degrees) |
| AHU5 |
West side of Building |
Local thermostats @ 70 degrees |
| FC1 |
Rooms 100,104,141 Fan Coil Unit control - Group 1, 2, 3 |
Local thermostats @ 70 degrees during heating season and 76 degrees during the cooling season |
| AHU6 |
Navy and Army rooms 1st and 2nd floor East side |
pending completion:
100% ODA mixed air unit supplies 23 rooms on east side with a minimum of fresh air. Independant damper control switches from 100%ODA to 100%Open area when unoccupied. Preheat to 52 Degrees, Cool to 55Degrees, Rehear to 70 Degrees. |
| Date |
Ex |
Energy Conservation Action(s) Taken |
| 3/17/2006 |
1 |
Design Center Space = complete |
| 3/20/2006 |
2 |
FC1 = complete |
| 7/7/2006 |
|
Completed MEA Holiday schedules and reviewed hours of operation |
| 10/30/2006 |
|
Reviewed for winter settings = Off-line = Metasys controls are being updated |
| 5/9/2007 |
|
Reviewed for summer settings. |
| 11/1/2007 |
|
Reviewed for winter schedule |
| 5/15/2008 |
|
Reviewed for summer schedule. |
| 9/8/2008 |
|
Reviewed for winter schedule. |
| 9/30/2009 |
|
Reviewed for winter schedule. |