Year Constructed:
1998
47,861 Gross Square Feet
| # |
Exemptions |
Summer |
Winter |
| 1 |
AH-1 & AH-2 |
Run AH-1 and AH-2 0600 to 1800 all days for summer |
|
| Unit |
Service Area |
Control Strategies |
| AH01 |
1st Floor |
Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 83-degree upper limit and a 63-degree lower limit. |
| AH02 |
2nd Floor |
Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 83-degree upper limit and a 63-degree lower limit. |
| Date |
Ex |
Energy Conservation Action(s) Taken |
| 4/24/2006 |
1 |
AHU1 and AHU2 = complete |
| 7/7/2006 |
|
Completed MEA Holiday schedules and reviewed hours of operation |
| 10/30/2006 |
|
Reviewed for winter schedule. |
| 5/9/2007 |
|
Reviewed for summer schedule. |
| 11/1/2007 |
|
Reviewed for winter schedule |
| 5/14/2008 |
|
Reviewed for summer schedule |
| 9/8/2008 |
|
Reviewed for winter schedule. |
| 5/11/2009 |
|
Reviewed for summer schedule |
| 9/30/2009 |
|
Reviewed for winter schedule. |