Building Energy Plans

Atanasoff Hall

Year Constructed: 1969

39,451 Gross Square Feet

# Exemptions Summer Winter
1 (AHU1) Rms B10, B26, B26E Computer Labs 24/7  24/7 
2 (AHU3) Rms 106, 108, 116B, 125, 126 Computer Labs 24/7  24/7 
3 (AHU5) Rm 215 Computer Lab 24/7  24/7 
4 (AHU3) Rms 115, 116, 116A until Fall 2006 24/7 @ 74 degrees  24/7 


Unit Service Area Cool Heat System Type Summer Hours Winter Hours
AHU1 Basement  Yes  Yes  HVAC System with Reheat   24/7  24/7 
AHU3 1st Floor  Yes    Constant Volume   24/7  24/7 
AHU5 2nd Floor  Yes  Yes  HVAC System with Reheat   24/7  24/7 
AHU6 Rm 116B Computer Lab  Yes  Yes  Constant Volume   24/7  24/7 
RAD Radiators    Yes  Radiator   ODA Enable
Setpoint=scheduled

Run = All days
6am = Day = 45F
12am = Night = 35F

No Holiday scheduled 
ODA Enable
Setpoint=scheduled

Run = All days
6am = Day = 45F
12am = Night = 35F

No Holiday scheduled 


Unit Service Area Control Strategies
AHU1  Basement  Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU3  1st Floor  Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU5  2nd Floor  Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU6  Rm 116B Computer Lab  Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
RAD  Radiators  Radiator flow is started anytime outside temperatures are below 50 degrees


Date Ex Energy Conservation Action(s) Taken
3/16/2006 AHU3 = complete
3/16/2006 AHU5 = complete
3/16/2006 AHU3 = complete
3/16/2006 AHU1 = complete
7/7/2006   Completed MEA Holiday schedules and reviewed hours of operation
10/30/2006   Reviewed for winter settings = found a schedule for radiation added to data file (Stan)
5/9/2007   Reviewed for summer settings.
11/1/2007   Reviewed for winter schedule
5/15/2008   Reviewed for summer schedule.
9/8/2008   Reviewed for winter schedule.
5/11/2009   Reviewed for summer schedule. Noted radiating is 7am-6pm M-F
9/30/2009   Reviewed for winter schedule.