| Unit |
Service Area |
Cool |
Heat |
System Type |
Summer Hours |
Winter Hours |
| AHU1 |
1st Floor |
Yes |
Yes |
HVAC System with Reheat
|
Run = 24/7 |
Run = 24/7 |
| AHU2 |
Basement Floor Rooms 1, 5, 7, 25, 26, 27, 29 |
Yes |
Yes |
HVAC System with Reheat
|
Run = 24/7 |
Run = 24/7 |
| AHU3 |
2nd and 3rd Floor North & East Rooms 261, 263 |
Yes |
Yes |
HVAC System with Reheat
|
Run = 24/7 |
Run = 24/7 |
| AHU4 |
2nd and 3rd Floor South and West, Rooms 250, 256, 260, 264 |
Yes |
Yes |
HVAC System with Reheat
|
Run = 24/7 |
Run = 24/7 |
| AHU5 |
4th Floor except for area served by AHU6 |
Yes |
Yes |
HVAC System with Reheat
|
Run = 24/7 |
Run = 24/7 |
| AHU6 |
4th Floor Interior Rooms (rooms 475H, 432, 434) |
Yes |
Yes |
HVAC System with Reheat
|
Run = 24/7 |
Run = 24/7 |
| Unit |
Service Area |
Control Strategies |
| AHU1 |
1st Floor |
Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During "off" periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| AHU2 |
Basement Floor Rooms 1, 5, 7, 25, 26, 27, 29 |
Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During "off" periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| AHU3 |
2nd and 3rd Floor North & East Rooms 261, 263 |
Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During "off" periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| AHU4 |
2nd and 3rd Floor South and West, Rooms 250, 256, 260, 264 |
Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During "off" periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| AHU5 |
4th Floor except for area served by AHU6 |
Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During "off" periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| AHU6 |
4th Floor Interior Rooms (rooms 475H, 432, 434) |
Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During "off" periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| AHU6 |
4th Floor Interior Rooms (rooms 475H, 432, 434) |
Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During "off" periods there will be an 80-degree upper limit and a 65-degree lower limit. |