| # | Exemptions | Summer | Winter |
|---|---|---|---|
| 1 | AHU1, 2nd floor operate extended hours, Dean's office working evenings and weekends | Schedule 7 days a week, see hours below | Schedule 7 days a week, see hours below |
| Unit | Service Area | Cool | Heat | System Type | Summer Hours | Winter Hours |
|---|---|---|---|---|---|---|
| AHU1 | Serves entire building | Yes | HVAC System with Reheat | Run = 6am-7pm, Mon Run = 6am-7pm, Tue Run = 6am-7pm, Wed Run = 6am-7pm, Thu Run = 6am-7pm, Fri Run = 7am-7pm, Sat Run = 8am-7pm, Sun Off = Holidays |
Run = 6am-7pm, Mon Run = 6am-7pm, Tue Run = 6am-7pm, Wed Run = 6am-7pm, Thu Run = 6am-7pm, Fri Run = 7am-7pm, Sat Run = 8am-7pm, Sun Off = Holidays |
|
| HS1 | Heating Hot Water System (HS1) Radiation and Reheat | Yes | HVAC System with Reheat | Radiation and Reheat Hot Water System Out-door Air Enable Setpoint Schedule. Run = 6am-5pm, Mon-Sun Day = 65F Night = 45F Run = Holidays Night = 45F |
Radiation and Reheat Hot Water System Out-door Air Enable Setpoint Schedule. Run = 6am-5pm, Mon-Sun Day = 65F Night = 45F Run = Holidays Night = 45F |
| Unit | Service Area | Control Strategies |
|---|---|---|
| AHU1 | Serves entire building | Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. Set back domestic water temperature to 120 degrees Identify” last out, lights off” Person or process |
| Date | Ex | Energy Conservation Action(s) Taken |
|---|---|---|
| 3/13/2006 | 1 | AHU1 = extended schedule = complete |
| 7/11/2006 | Domestic Hot Water scheduled 0n/Off, day/night, 6/1700 | |
| 7/11/2006 | Heating Enable setpoint scheduled 65/45, day/night, 6/1800 | |
| 7/11/2006 | Completed MEA Holiday schedules and reviewed hours of operation | |
| 10/30/2006 | Reviewed for winter schedule | |
| 5/10/2007 | Reviewed for summer schedule | |
| 11/1/2007 | Reviewed for winter schedule | |
| 5/15/2008 | Reviewed for summer schedule | |
| 9/9/2008 | Reviewed for winter schedule. | |
| 5/12/2009 | Reviewed for summer schedule | |
| 10/1/2009 | Reviewed for winter schedule. |