Coover Hall Basement Floor Plan - HVAC
Coover Hall First Floor Plan - HVAC
Coover Hall Second Floor Plan - HVAC
Coover Hall Third Floor Paln - HVAC
Coover Hall Fourth Floor Plan - HVAC
| # | Exemptions | Summer | Winter |
|---|---|---|---|
| 1 | Rm 2424, 2421 - server rooms (AHU2) | 24/7 @ 72 degrees | 24/7 @ 72 degrees |
| 2 | Rm 1212, 1125, 1208, 1301, 1316, 1318, 1331, 1331C, 1341 - Open Lab hours (AHU8, AHU9) | Hours vary for academic year vs summer | Hours vary for academic year vs summer |
| 3 | (AHU8) Room 1331 dept. Sever room | 72 Deg 24/7 | 72 Deg 24/7 |
| 4 | (AHU12) Rms 2011,2014,2018,2042,2046,2048,2050,2061,2041 | 24/7 operation thru June 09 | 24/7 operation thru June 09 |
| 5 | Room 1060 71.5 deg 8AM to 8PM | April 2012 thru Dec 2015 |
| Unit | Service Area | Cool | Heat | System Type | Summer Hours | Winter Hours |
|---|---|---|---|---|---|---|
| AHU6 | Auditorium 2245 | Yes | Yes | Mixed Air HVAC System | Run = 24/7 | Room Scheduling |
| AHU8 | Grahics/Computer Rooms 1331, 1331C, 1341, Server Room | Yes | Yes | HVAC System with Reheat | ON 24/7 | ON 24/7 |
| AHU9 | Learning Center - Room 1313 | Yes | Yes | HVAC System with Reheat | Mon=6am-5pm Tue=6am-5pm Wed=6am-5pm Thu=6am-5pm Fri=6am-5pm Sat=6am-5pm Off=Sun Off=Holidays |
Mon=6am-2am Tue=6am-2am Wed=6am-2am Thu=6am-2am Fri=7am-8pm Sat=10am-8pm Sun=10am-2am Holidays=OFF Winter = OFF 24/7 |
| FCU1212 | Computer Lab 1212 | Yes | Fan Coil Unit with Occupant Thermostat | Occupant Controlled | Occupant Controlled | |
| FCU1301 | Computer Lab 1301 | Yes | Fan Coil Unit with Occupant Thermostat | Occupant Controlled | Occupant Controlled | |
| FCU1318 | Computer Lab 1318 | Yes | Fan Coil Unit with Occupant Thermostat | Occupant Controlled | Occupant Controlled | |
| AH11 | 1st Floor | Yes | Yes | Mixed Air HVAC System | Run = 24/7 | Run = 24/7 |
| AH12 | 2nd and 3rd Floor | Yes | Yes | Mixed Air HVAC System | Run = 24/7 | Run = 24/7 |
| LTG1 | Stand alone Lighting Panel in Room #: Serves: ? | Lighting Control | ? | ? | ||
| EXH-RR | Rest rooms | Exhaust Fan | All days 6am-10pm | All days 6am-10pm |
| Unit | Service Area | Control Strategies |
|---|---|---|
| Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. | ||
| Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. | ||
| AHU6 | Auditorium 2245 | Zone thermostat set at 71-degrees all year. Cooling/Heating controlled by a supply air temperature sensor for for a range of 55F-95F degrees reset schedule base on zone set point. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| AHU8 | Grahics/Computer Rooms 1331, 1331C, 1341, Server Room | Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| AHU9 | Learning Center - Room 1313 | Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| LTG1 | Stand alone Lighting Panel in Room #: Serves: ? | ? |
| Date | Ex | Energy Conservation Action(s) Taken |
|---|---|---|
| 7/11/2006 | Completed MEA Holiday schedules and reviewed hours of operation | |
| 7/11/2006 | Domestic Hot Water pump scheduled On/Off, Day/Night, 7/1600 | |
| 10/30/2006 | Reviewed for winter schedule | |
| 5/10/2007 | Reviewed for summer schedule | |
| 11/1/2007 | Reviewed for winter schedule | |
| 4/25/2008 | 3 | AHU8 = Run =24/7 = lowered supply air setpoint from 60F to 55F degrees (Stan) |
| 5/20/2008 | Reviewed for summer schedule | |
| 8/28/2008 | 4 | AHU12 = Run =24/7 |
| 5/12/2009 | Reviewed for summer schedule | |
| 10/1/2009 | Reviewed for winter schedule. | |
| 5/12/2010 | Reviewed for summer schedule | |
| 5/12/2010 | Reviewed for summer schedule | |
| 8/27/2012 | Run AHU6, 24/7 for summer months. See Building Energy System Notes below. (Stan, Ron and Wendy) | |
| 9/24/2012 | AHU-6: Returned to normal schedule. |