| # | Exemptions | Summer | Winter |
|---|---|---|---|
| 1 | Rm 11, 6 - server rooms (AHU2) | 24/7 @ 76 degrees | none |
| Unit | Service Area | Cool | Heat | System Type | Summer Hours | Winter Hours |
|---|---|---|---|---|---|---|
| AHU1 | Building Ventilation -Old Fan System | Supply Fan | Room Scheduling OFF until further notice by Ron Cochrane. |
Room Scheduling OFF until further notice by Ron Cochrane. |
||
| AHU2 | Brenton Center - Ground and 3rd floor North Call 4-1862 for hours | Yes | Yes | HVAC System with Reheat | Run = 24/7 | Mon=7am-6pm Tue=7am-6pm Wed=7am-6pm Thu=7am-9pm Fri=7am-6pm Off=Sat Off=Sun Off=Holidays |
| AHU3 | Auditorium 127 - North | Yes | Yes | Mixed Air HVAC System | Room Scheduling | Room Scheduling |
| AHU4 | Auditorium 127 - South | Yes | Yes | Mixed Air HVAC System | Room Scheduling | Room Scheduling |
| AHU5 | 1st, 2nd, 3rd Floor - South | Yes | Yes | HVAC System with Reheat | Room Scheduling | Room Scheduling |
| RAD | Radiators, Outdoor air temperature and 4 zones in rooms 19, 111C, 206, 317, will open heating valves | Yes | Radiator | Run = Mon 5am = day = 55F 10pm = night = 45F Run = Tue 5am = day = 55F 10pm = night = 45F Run = Wed 5am = day = 55F 10pm = night = 45F Run = Thu 5am = day = 55F 10pm = night = 45F Run = Fri 5am = day = 55F 10pm = night = 45F Run = Sat 5am = day = 55F 10pm = night = 45F Run = Sun 5am = day = 55F 10pm = night = 45F Off=Holidays |
Run = Mon 5am = day = 55F 10pm = night = 45F Run = Tue 5am = day = 55F 10pm = night = 45F Run = Wed 5am = day = 55F 10pm = night = 45F Run = Thu 5am = day = 55F 10pm = night = 45F Run = Fri 5am = day = 55F 10pm = night = 45F Run = Sat 5am = day = 55F 10pm = night = 45F Run = Sun 5am = day = 55F 10pm = night = 45F Off=Holidays |
| Unit | Service Area | Control Strategies |
|---|---|---|
| AHU1 | Building Ventilation -Old Fan System | Ventilation air, no heating/cooling |
| AHU2 | Brenton Center - Ground and 3rd floor North Call 4-1862 for hours | Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 83-degree upper limit and a 63-degree lower limit. |
| AHU3 | Auditorium 127 - North | Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in an air mixing box located in each zone. During "off" periods there will be an 83-degree upper limit and a 63-degree lower limit. |
| AHU4 | Auditorium 127 - South | Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in an air mixing box located in each zone. During "off" periods there will be an 83-degree upper limit and a 63-degree lower limit. |
| AHU5 | 1st, 2nd, 3rd Floor - South | Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 83-degree upper limit and a 63-degree lower limit. |
| RAD | Radiators, Outdoor air temperature and 4 zones in rooms 19, 111C, 206, 317, will open heating valves | Radiator flow is started any time outside temperatures are below 50 degrees |
| Date | Ex | Energy Conservation Action(s) Taken |
|---|---|---|
| 3/27/2006 | COMPLETED SPRING 06 BUILDING ENERGY CONSERVATION SETTINGS | |
| 7/11/2006 | Completed MEA Holiday schedules and reviewed hours of operation | |
| 10/30/2006 | Reviewed for winter settings | |
| 5/10/2007 | Reviewed for summer settings. | |
| 11/1/2007 | Reviewed for winter schedule | |
| 5/21/2008 | Reviewed for summer schedule. | |
| 9/15/2008 | Reviewed for winter schedule. | |
| 5/12/2009 | Reviewed for summer schedule | |
| 10/1/2009 | Reviewed for winter schedule. |