ISU Facilities

Building Energy Plans

Curtiss Hall

Year Constructed: 1909

102,338 Gross Square Feet

# Exemptions Summer Winter
1 Rm 11, 6 - server rooms (AHU2) 24/7 @ 76 degrees  none 


Unit Service Area Cool Heat System Type Summer Hours Winter Hours
AHU1 Building Ventilation -Old Fan System      Supply Fan   Room Scheduling

OFF until further notice by Ron Cochrane. 
Room Scheduling

OFF until further notice by Ron Cochrane. 
AHU2 Brenton Center - Ground and 3rd floor North Call 4-1862 for hours  Yes  Yes  HVAC System with Reheat   Run = 24/7  Mon=7am-6pm
Tue=7am-6pm
Wed=7am-6pm
Thu=7am-9pm
Fri=7am-6pm
Off=Sat
Off=Sun
Off=Holidays  
AHU3 Auditorium 127 - North  Yes  Yes  Mixed Air HVAC System   Room Scheduling  Room Scheduling 
AHU4 Auditorium 127 - South  Yes  Yes  Mixed Air HVAC System   Room Scheduling   Room Scheduling  
AHU5 1st, 2nd, 3rd Floor - South  Yes  Yes  HVAC System with Reheat   Room Scheduling  Room Scheduling 
RAD Radiators, Outdoor air temperature and 4 zones in rooms 19, 111C, 206, 317, will open heating valves    Yes  Radiator   Run = Mon
5am = day = 55F
10pm = night = 45F

Run = Tue
5am = day = 55F
10pm = night = 45F

Run = Wed
5am = day = 55F
10pm = night = 45F

Run = Thu
5am = day = 55F
10pm = night = 45F

Run = Fri
5am = day = 55F
10pm = night = 45F

Run = Sat
5am = day = 55F
10pm = night = 45F

Run = Sun
5am = day = 55F
10pm = night = 45F

Off=Holidays 
Run = Mon
5am = day = 55F
10pm = night = 45F

Run = Tue
5am = day = 55F
10pm = night = 45F

Run = Wed
5am = day = 55F
10pm = night = 45F

Run = Thu
5am = day = 55F
10pm = night = 45F

Run = Fri
5am = day = 55F
10pm = night = 45F

Run = Sat
5am = day = 55F
10pm = night = 45F

Run = Sun
5am = day = 55F
10pm = night = 45F

Off=Holidays 


Unit Service Area Control Strategies
AHU1  Building Ventilation -Old Fan System  Ventilation air, no heating/cooling
AHU2  Brenton Center - Ground and 3rd floor North Call 4-1862 for hours  Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 83-degree upper limit and a 63-degree lower limit.
AHU3  Auditorium 127 - North  Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in an air mixing box located in each zone. During "off" periods there will be an 83-degree upper limit and a 63-degree lower limit.
AHU4  Auditorium 127 - South  Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in an air mixing box located in each zone. During "off" periods there will be an 83-degree upper limit and a 63-degree lower limit.
AHU5  1st, 2nd, 3rd Floor - South  Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 83-degree upper limit and a 63-degree lower limit.
RAD  Radiators, Outdoor air temperature and 4 zones in rooms 19, 111C, 206, 317, will open heating valves  Radiator flow is started any time outside temperatures are below 50 degrees


Date Ex Energy Conservation Action(s) Taken
3/27/2006   COMPLETED SPRING 06 BUILDING ENERGY CONSERVATION SETTINGS
7/11/2006   Completed MEA Holiday schedules and reviewed hours of operation
10/30/2006   Reviewed for winter settings
5/10/2007   Reviewed for summer settings.
11/1/2007   Reviewed for winter schedule
5/21/2008   Reviewed for summer schedule.
9/15/2008   Reviewed for winter schedule.
5/12/2009   Reviewed for summer schedule
10/1/2009   Reviewed for winter schedule.