ISU Facilities

Building Energy Plans

College of Design

Year Constructed: 1978 / 1999 /

163,028 Gross Square Feet

# Exemptions Summer Winter
1 Operational Areas 24/7  24/7 


Unit Service Area Cool Heat System Type Summer Hours Winter Hours
AHU1 North and East side of Building  Yes  Yes  Dual Duct HVAC System   24/7  24/7 
AHU2 South and West side of Building  Yes  Yes  Dual Duct HVAC System   24/7  24/7 
AHU3 Auditorium 101  Yes  Yes  HVAC System with Reheat   Room Scheduling  Room Scheduling 
AHU4 Conference Room 130  Yes  Yes  HVAC System with Reheat   Mon=7am-6pm
Tue=7am-6pm
Wed=7am-6pm
Thu=7am-6pm
Fri=7am-6pm
Off=Sat
Off=Sun
Off=Holidays  
Mon=7am-6pm
Tue=7am-6pm
Wed=7am-6pm
Thu=7am-6pm
Fri=7am-6pm
Off=Sat
Off=Sun
Off=Holidays  
AHU5 Darkroom 003A  Yes  Yes  Mixed Air HVAC System   24/7  24/7 
UV16 Room 54  Yes  Yes  Unit Ventilator System Without Reheat   24/7  24/7 
UV17 Room 62  Yes  Yes  Unit Ventilator System Without Reheat   24/7  24/7 
UV18 Room 66CA  Yes  Yes  Unit Ventilator System Without Reheat   24/7  24/7 
RAD Exterior Walls    Yes  Radiator   Off  Available 24/7 
EXH FAN 21 restroom exhaust fans for north side of buidling.      Exhaust Fan   Run = 5am-12am, Mon
Run = 5am-12am, Tue
Run = 5am-12am, Wed
Run = 5am-12am, Thu
Run = 5am-12am, Fri
Run = 8am-8pm, Sat
Run = 12pm-8pm, Sun
Off = Holidays
 
Run = 5am-12am, Mon
Run = 5am-12am, Tue
Run = 5am-12am, Wed
Run = 5am-12am, Thu
Run = 5am-12am, Fri
Run = 8am-8pm, Sat
Run = 12pm-8pm, Sun
Off = Holidays
 
EXH FAN 22 restroom exhaust fan for south side of building.      Exhaust Fan   Run = 5am-12am, Mon
Run = 5am-12am, Tue
Run = 5am-12am, Wed
Run = 5am-12am, Thu
Run = 5am-12am, Fri
Run = 8am-8pm, Sat
Run = 12pm-8pm, Sun
Off = Holidays
 
Run = 5am-12am, Mon
Run = 5am-12am, Tue
Run = 5am-12am, Wed
Run = 5am-12am, Thu
Run = 5am-12am, Fri
Run = 8am-8pm, Sat
Run = 12pm-8pm, Sun
Off = Holidays
 


Unit Service Area Control Strategies
AHU1  North and East side of Building  Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU2  South and West side of Building  Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU3  Auditorium 101  Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU4  Conference Room 130  Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU5  Darkroom 003A  Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
UV16  Room 54  Local thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
UV17  Room 62  Local thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
UV18  Room 66CA  Local thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
RAD  Exterior Walls  Radiator flow is started anytime outside temperatures are below 50 degrees


Date Ex Energy Conservation Action(s) Taken
3/17/2006 1 = complete
7/12/2006   Completed MEA Holiday schedules and reviewed hours of operation
10/30/2006   Reviewed for winter schedule
5/10/2007   Reviewed for summer schedule
11/1/2007   Reviewed for winter schedule
5/21/2008   Reviewed for summer schedule.
9/15/2008   Reviewed for winter schedule.
5/12/2009   Reviewed for summer schedule
10/1/2009   Reviewed for winter schedule.