| # | Exemptions | Summer | Winter |
|---|---|---|---|
| 1 | AHU1 | Extended hours, @74 degrees | Extended hours, @70 degrees |
| Unit | Service Area | Cool | Heat | System Type | Summer Hours | Winter Hours |
|---|---|---|---|---|---|---|
| AHU1 | Entire Building | Yes | Yes | HVAC System with Reheat | Run = 6am-8pm, Mon Run = 6am-8pm, Tue Run = 6am-8pm, Wed Run = 6am-8pm, Thu Run = 6am-6pm, Fri Run = 7am-6pm, Sat Run = 7am-6pm, Sun Off = Holidays |
Run=7am-8pm, Mon Run=7am-8pm, Tue Run=7am-8pm, Wed Run=7am-8pm, Thu Run=7am-6pm, Fri Run=7am-6pm, Sat Run=7am-6pm, Sun Off= Holidays |
| Rad | Yes | Radiator | Off | On | ||
| AH1 | Building | Yes | Yes | Mixed Air HVAC System |
| Unit | Service Area | Control Strategies |
|---|---|---|
| AHU1 | Entire Building | Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 74 degrees depending on outside air temperature and heat load in the area served. During "off" periods there will be an 83-degree upper limit and a 63-degree lower limit. |
| Rad | Radiator flow is started anytime outside temperatures are below 70 degrees | |
| Identify "last out lights off" person/process | ||
| Set back domestic hot water temp to 120 degrees |
| Date | Ex | Energy Conservation Action(s) Taken |
|---|---|---|
| 3/15/2006 | 1 | AHU1= extended hours = complete |
| 4/13/2006 | 1 | COMPLETED SPRING 06 BUILDING ENERGY CONSERVATION SETTINGS |
| 7/7/2006 | Completed MEA Holiday schedules and reviewed hours of operation | |
| 10/30/2006 | Reviewed for winter schedule. | |
| 5/9/2007 | Reviewed for summer schedule. | |
| 11/1/2007 | Update AHU-1 Nite Heating/Cooling set points nformation | |
| 11/1/2007 | Reviewed for winter schedule | |
| 5/15/2008 | Reviewed for summer schedule. | |
| 9/15/2008 | Reviewed for winter schedule. | |
| 5/12/2009 | Reviewed for summer schedule |