Extension 4-H Building

Year Constructed: 2003

23,356 Gross Square Feet

# Exemptions Summer Winter
1 Video/TV Studios Rms 1145, 1147, 1147A, 1147B, 1151 (AHU2) 74 degrees  72 degrees 
2 Room 1104   70 degrees 7:30 am to 5:00pm 


Unit Service Area Cool Heat System Type Summer Hours Winter Hours
AHU1 Offices 1112-1118, 1185-1189; Conf Rms 1114, 1110, 1183, 1181; Library; 1159; Also 1159, 1104, 1142  Yes  Yes  VAV with Reheat   Run = 7am - 6pm, Mon
Run = 7am - 6pm, Tue
Run = 7am - 6pm, Wed
Run = 7am - 6pm, Thu
Run = 7am - 6pm, Fri
Off = Sat
Off = Sun
Off = Holidays
 
Run = 7am - 6pm, Mon
Run = 7am - 6pm, Tue
Run = 7am - 6pm, Wed
Run = 7am - 6pm, Thu
Run = 7am - 6pm, Fri
Off = Sat
Off = Sun
Off = Holidays
 
AHU2 Conf Rm 1020, 1141, Wow Center, Radio/TV Studios 1145-1151  Yes  Yes  VAV with Reheat   Run = 7am - 6pm, Mon
Run = 7am - 6pm, Tue
Run = 7am - 6pm, Wed
Run = 7am - 6pm, Thu
Run = 7am - 6pm, Fri
Off = Sat
Off = Sun
Off = Holidays
 
Run = 7am - 6pm, Mon
Run = 7am - 6pm, Tue
Run = 7am - 6pm, Wed
Run = 7am - 6pm, Thu
Run = 7am - 6pm, Fri
Off = Sat
Off = Sun
Off = Holidays
 


Unit Service Area Control Strategies
AHU1  Offices 1112-1118, 1185-1189; Conf Rms 1114, 1110, 1183, 1181; Library; 1159; Also 1159, 1104, 1142  Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU2  Conf Rm 1020, 1141, Wow Center, Radio/TV Studios 1145-1151  Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.


Date Ex Energy Conservation Action(s) Taken
3/20/2006 (AHU2) Video Studios Rms 1145, 1147, 1147A, 1147B, 1151= complete
7/12/2006   Completed MEA Holiday schedules and reviewed hours of operation
10/30/2006   Reviewed for winter schedule
12/19/2006 Update completed. See information under Building Energy System Notes Dated 12/19/06
5/10/2007   Reviewed for summer schedule
11/1/2007   Reviewed for winter schedule
5/21/2008   Reviewed for summer schedule.
9/15/2008   Reviewed for winter schedule.
5/5/2009   Reviewed for summer schedule
10/7/2009   Reviewed for winter schedule.