| # | Exemptions | Summer | Winter |
|---|---|---|---|
| 1 | (AHU1) Rm 3332, 3334 - Labs with volatile materials | 24/7 @ 76 degrees | none |
| 2 | (AHU16) Rm 1597, 1578 - Leased to private firm | 24/7 @ 76 degrees | 24/7 @ 70 degrees |
| 3 | (AHU11) Rm 1833 - Solvents Lab | 24/7 @ 76 degrees | 24/7 @ 70 degrees |
| 4 | (AHU1) Rm 3333 - Lab having trouble with excessive heat | 24/7 @ 76 degrees | none |
| 5 | (AHU1) Rm 3364, 3397 Labs having trouble with heat | 24/7 @ 76 degrees | none |
| 6 | AHU12, 13, 14 = rm 2623 is hot for laboratory equipment | Run = 24/7 | Run = 24/7 |
| Unit | Service Area | Cool | Heat | System Type | Summer Hours | Winter Hours |
|---|---|---|---|---|---|---|
| AHU1 | West Basement | Yes | Yes | Mixed Air HVAC System | 24/7 | Run = 7am – 6pm, Mon Run = 7am – 6pm, Tue Run = 7am – 6pm, Wed Run = 7am – 6pm, Thu Run = 7am – 6pm, Fri Off =Sat Off = Sun Off = Holidays |
| AHU2 | West Auditorium - Rm 2432 | Yes | Yes | Mixed Air HVAC System | Room Scheduling | Room Scheduling |
| AHU3 | Laboratory 2379 | Yes | Yes | Mixed Air HVAC System | Occupant Controlled | Occupant Controlled |
| AHU4 | Laboratory 2384 | Yes | Yes | Mixed Air HVAC System | Occupant Controlled | Occupant Controlled |
| AHU5 | South wing - Labs | Yes | Yes | Mixed Air HVAC System | Run = 7am – 6pm, Mon Run = 7am – 6pm, Tue Run = 7am – 6pm, Wed Run = 7am – 6pm, Thu Run = 7am – 6pm, Fri Off =Sat Off = Sun Off = Holidays |
Run = 7am – 6pm, Mon Run = 7am – 6pm, Tue Run = 7am – 6pm, Wed Run = 7am – 6pm, Thu Run = 7am – 6pm, Fri Off =Sat Off = Sun Off = Holidays |
| AHU6 | East offices, Kitchen, Auditorium | Yes | Yes | Mixed Air HVAC System | Run = 7am – 6pm, Mon Run = 7am – 6pm, Tue Run = 7am – 6pm, Wed Run = 7am – 6pm, Thu Run = 7am – 6pm, Fri Off =Sat Off = Sun Off = Holidays |
Run = 7am – 6pm, Mon Run = 7am – 6pm, Tue Run = 7am – 6pm, Wed Run = 7am – 6pm, Thu Run = 7am – 6pm, Fri Off =Sat Off = Sun Off = Holidays |
| AHU7 | South Pilot Lab | Yes | Yes | Mixed Air HVAC System | Run = 7am – 6pm, Mon Run = 7am – 6pm, Tue Run = 7am – 6pm, Wed Run = 7am – 6pm, Thu Run = 7am – 6pm, Fri Off =Sat Off = Sun Off = Holidays |
Run = 7am – 6pm, Mon Run = 7am – 6pm, Tue Run = 7am – 6pm, Wed Run = 7am – 6pm, Thu Run = 7am – 6pm, Fri Off =Sat Off = Sun Off = Holidays |
| AHU8 | North Pilot Lab | Yes | Yes | Mixed Air HVAC System | Run = 7am – 6pm, Mon Run = 7am – 6pm, Tue Run = 7am – 6pm, Wed Run = 7am – 6pm, Thu Run = 7am – 6pm, Fri Off =Sat Off = Sun Off = Holidays |
Run = 7am – 6pm, Mon Run = 7am – 6pm, Tue Run = 7am – 6pm, Wed Run = 7am – 6pm, Thu Run = 7am – 6pm, Fri Off =Sat Off = Sun Off = Holidays |
| AHU9 | Storage/Shop | Yes | Yes | Mixed Air HVAC System | Run = 7am – 6pm, Mon Run = 7am – 6pm, Tue Run = 7am – 6pm, Wed Run = 7am – 6pm, Thu Run = 7am – 6pm, Fri Off =Sat Off = Sun Off = Holidays |
Run = 7am – 6pm, Mon Run = 7am – 6pm, Tue Run = 7am – 6pm, Wed Run = 7am – 6pm, Thu Run = 7am – 6pm, Fri Off =Sat Off = Sun Off = Holidays |
| AHU10 | East Pilot Lab | Yes | Yes | Mixed Air HVAC System | Run = 7am – 6pm, Mon Run = 7am – 6pm, Tue Run = 7am – 6pm, Wed Run = 7am – 6pm, Thu Run = 7am – 6pm, Fri Off =Sat Off = Sun Off = Holidays |
Run = 7am – 6pm, Mon Run = 7am – 6pm, Tue Run = 7am – 6pm, Wed Run = 7am – 6pm, Thu Run = 7am – 6pm, Fri Off =Sat Off = Sun Off = Holidays |
| AHU11 | Laboratory 1833 - Chemical Storage | Yes | Yes | Mixed Air HVAC System | 24/7 | 24/7 |
| AHU12 | Old East Addition | Yes | Yes | Mixed Air HVAC System | Occupant Controlled Run = 24/7 |
Occupant Controlled Run = 24/7 |
| AHU13 | Old East Addition | Yes | Yes | Mixed Air HVAC System | Occupant Controlled | Occupant Controlled |
| AHU14 | Old East Addition | Yes | Yes | Mixed Air HVAC System | Occupant Controlled | Occupant Controlled |
| AHU15 | North Wing - Offices | Yes | Yes | Mixed Air HVAC System | Run = 7am – 6pm, Mon Run = 7am – 6pm, Tue Run = 7am – 6pm, Wed Run = 7am – 6pm, Thu Run = 7am – 6pm, Fri Off =Sat Off = Sun Off = Holidays |
Run = 7am – 6pm, Mon Run = 7am – 6pm, Tue Run = 7am – 6pm, Wed Run = 7am – 6pm, Thu Run = 7am – 6pm, Fri Off =Sat Off = Sun Off = Holidays |
| AHU16 | North Wing - Labs | Yes | Yes | Mixed Air HVAC System | 24/7 | 24/7 |
| RAD | Outiside Walls | Yes | Radiator | Off | System Energized 24/7 | |
| EXH-8 | Exhaust Fan | Mon=7am-6pm Tue=7am-6pm Wed=7am-6pm Thu=7am-6pm Fri=7am-6pm Off=Sat Off=Sun Off=Holiday |
Mon=7am-6pm Tue=7am-6pm Wed=7am-6pm Thu=7am-6pm Fri=7am-6pm Off=Sat Off=Sun Off=Holiday |
|||
| EXH-26 | Exhaust Fan | Mon=7am-10pm Tue=7am-10pm Wed=7am-10pm Thu=7am-10pm Fri=7am-10pm Off=Sat Off=Sun Off=Holiday |
Mon=7am-10pm Tue=7am-10pm Wed=7am-10pm Thu=7am-10pm Fri=7am-10pm Off=Sat Off=Sun Off=Holiday |
| Unit | Service Area | Control Strategies |
|---|---|---|
| AHU3 | Laboratory 2379 | Occupant Controlled - not on Metasys |
| AHU4 | Laboratory 2384 | Occupant Controlled - not on Metasys |
| AHU12 | Old East Addition | Occupant Controlled - not on Metasys |
| AHU13 | Old East Addition | Occupant Controlled - not on Metasys |
| AHU14 | Old East Addition | Occupant Controlled - not on Metasys |
| AHU2 | West Auditorium - Rm 2432 | Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in an air mixing box located in each zone. During "off" periods there will be an 80-degree upper limt and a 65-degree lower limit. |
| AHU5 | South wing - Labs | Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in an air mixing box located in each zone. During "off" periods there will be an 80-degree upper limt and a 65-degree lower limit. |
| AHU6 | East offices, Kitchen, Auditorium | Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in an air mixing box located in each zone. During "off" periods there will be an 80-degree upper limt and a 65-degree lower limit. |
| AHU7 | South Pilot Lab | Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in an air mixing box located in each zone. During "off" periods there will be an 80-degree upper limt and a 65-degree lower limit. |
| AHU8 | North Pilot Lab | Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in an air mixing box located in each zone. During "off" periods there will be an 80-degree upper limt and a 65-degree lower limit. |
| AHU9 | Storage/Shop | Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in an air mixing box located in each zone. During "off" periods there will be an 80-degree upper limt and a 65-degree lower limit. |
| AHU10 | East Pilot Lab | Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in an air mixing box located in each zone. During "off" periods there will be an 80-degree upper limt and a 65-degree lower limit. |
| AHU11 | Laboratory 1833 - Chemical Storage | Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in an air mixing box located in each zone. During "off" periods there will be an 80-degree upper limt and a 65-degree lower limit. |
| AHU15 | North Wing - Offices | Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in an air mixing box located in each zone. During "off" periods there will be an 80-degree upper limt and a 65-degree lower limit. |
| AHU16 | North Wing - Labs | Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in an air mixing box located in each zone. During "off" periods there will be an 80-degree upper limt and a 65-degree lower limit. |
| RAD | Outiside Walls | Radiator flow is started any time outside temperatures are below 50 degrees |
| Date | Ex | Energy Conservation Action(s) Taken |
|---|---|---|
| 3/20/2006 | 5 | AHU1 = complete |
| 3/20/2006 | 4 | AHU1 = complete |
| 3/20/2006 | 3 | AHU11 = complete |
| 3/20/2006 | 2 | AHU16 = complete |
| 3/20/2006 | 1 | AHU1 = complete |
| 7/12/2006 | Completed MEA Holiday schedules and reviewed hours of operation | |
| 7/27/2006 | 6 | AHU12,13,14 are not controlled by Metasys (Pneumatic controls) = Fans run = 24/7 |
| 10/30/2006 | Reviewed for winter schedule | |
| 5/10/2007 | Reviewed for summer schedule | |
| 11/1/2007 | Reviewed for winter schedule | |
| 6/6/2008 | Changed return air reset schedule from 57F/68F to 57F/62F for AHU16 (Stan, per Ron Cochran +OK) | |
| 9/15/2008 | Reviewed for winter schedule. | |
| 5/12/2009 | Reviewed for summer schedule | |
| 10/7/2009 | Reviewed for winter schedule. |