Building Energy Plans

Forker Building

Year Constructed: 1940 / 1972

138,703 Gross Square Feet

All Floors Plan - HVAC

Basement Floor Plan - HVAC

First Floor Plan - HVAC

Second Floor Plan - HVAC

Third Floor Plan - HVAC

# Exemptions Summer Winter
1 (AHU11) Rm 283 - Biochem Lab 24/7  24/7 
2 (AHU12) Gyms 24/7 for air movement   
3 (AHU13) Gym 24/7 for air movement   
4 (AHU20) Rms 178N, 178S Research Labs 24/7  24/7 
5 (AHU21) Locker Rms 187, 189 - Air Circulation and room 164 reheats 24/7  24/7 
6 (AHU23) Rm 142 Inadequate Cooling 24/7  24/7 
7 (AHU10) extended hours 4am - 6pm weekdays, 4am-noon, Sat, Sun  6am - 6pm weekdays, 6am-noon, Sat, Sun 
8 (AHU22) extended hours 4am - 6pm weekdays, 4am-noon, Sat, Sun  6am - 6pm weekdays, 6am-noon, Sat, Sun 
9 (AHU21) Extended hours Rms 164Q and 164V 24/7  24/7 
10 (AHU-22) Room 289 Extended hours   Run until 9:00 PM WED. thru Dec. 2007 


Unit Service Area Cool Heat System Type Summer Hours Winter Hours
AHU10 East Offices  Yes  Yes  Mixed Air HVAC System   Mon=4am-6pm
Tue=4am-6pm
Wed=4am-6pm
Thu=4am-6pm
Fri=4am-6pm
Sat=4am-12pm
Sun=4am-12pm
Off=Holidays
 
Mon=6am-6pm
Tue=6am-6pm
Wed=6am-6pm
Thu=6am-6pm
Fri=6am-6pm
Sat=6am-12pm
Sun=6am-12pm
Off=Holidays
 
AHU11 Rms 283, 287  Yes  Yes  Mixed Air HVAC System   24/7  24/7 
AHU12 South Gym 173    Yes  Mixed Air HVAC System   24/7  Mon=6am-6pm
Tue=6am-6pm
Wed=6am-6pm
Thu=6am-6pm
Fri=6am-6pm
Off=Sat
Off=Sun
Off=Holidays
 
AHU13 North Gym 175    Yes  Mixed Air HVAC System   24/7  Mon=6am-6pm
Tue=6am-6pm
Wed=6am-6pm
Thu=6am-6pm
Fri=6am-6pm
Off=Sat
Off=Sun
Off=Holidays 
AHU14 West Gym 184    Yes  Mixed Air HVAC System   Mon=6am-6pm
Tue=6am-6pm
Wed=6am-6pm
Thu=6am-6pm
Fri=6am-6pm
Off=Sat
Off=Sun
Off=Holidays 
Mon=6am-6pm
Tue=6am-6pm
Wed=6am-6pm
Thu=6am-6pm
Fri=6am-6pm
Off=Sat
Off=Sun
Off=Holidays 
AHU15 East Gym 184    Yes  Mixed Air HVAC System   Mon=6am-6pm
Tue=6am-6pm
Wed=6am-6pm
Thu=6am-6pm
Fri=6am-6pm
Off=Sat
Off=Sun
Off=Holidays 
Mon=6am-6pm
Tue=6am-6pm
Wed=6am-6pm
Thu=6am-6pm
Fri=6am-6pm
Off=Sat
Off=Sun
Off=Holidays 
AHU16 Gym Room 194  Yes  Yes  Mixed Air HVAC System   Run = 4am-9pm, Mon
Run = 4am-8pm, Tue
Run = 4am-8pm, Wed
Run = 4am-8pm, Thu
Run = 4am-8pm, Fri
Off = Sat
Off = Sun
Off = Holidays
 
Run = 6am-6pm, Mon
Run = 6am-6pm, Tue
Run = 6am-6pm, Wed
Run = 6am-6pm, Thu
Run = 6am-6pm, Fri
Off = Sat
Off = Sun
Off = Holidays
 
AHU17 East Room 196  Yes  Yes  Mixed Air HVAC System   Mon=6am-6pm
Tue=6am-6pm
Wed=6am-6pm
Thu=6am-6pm
Fri=6am-6pm
Sat=6am-12pm
Sun= 6am-12pm
Off=Holidays 
Mon=6am-6pm
Tue=6am-6pm
Wed=6am-6pm
Thu=6am-6pm
Fri=6am-6pm
Sat=6am-12pm
Sun= 6am-12pm
Off=Holidays  
AHU18 West Room 196  Yes  Yes  Mixed Air HVAC System   Mon=6am-6pm
Tue=6am-6pm
Wed=6am-6pm
Thu=6am-6pm
Fri=6am-6pm
Sat=6am-12pm
Sun= 6am-12pm
Off=Holidays  
Mon=6am-6pm
Tue=6am-6pm
Wed=6am-6pm
Thu=6am-6pm
Fri=6am-6pm
Sat=6am-12pm
Sun= 6am-12pm
Off=Holidays  
AHU19 Room 198  Yes  Yes  Mixed Air HVAC System   Mon=6am-6pm
Tue=6am-6pm
Wed=6am-6pm
Thu=6am-6pm
Fri=6am-6pm
Sat=6am-12pm
Sun= 6am-12pm
Off=Holidays  
Mon=6am-6pm
Tue=6am-6pm
Wed=6am-6pm
Thu=6am-6pm
Fri=6am-6pm
Sat=6am-12pm
Sun= 6am-12pm
Off=Holidays  
AHU20 Rms 178N, 178S  Yes  Yes  Mixed Air HVAC System   24/7  24/7 
AHU21 Locker rms 187, 189  Yes  Yes  Mixed Air HVAC System   24/7  24/7 
AHU22 West Offices, Rms 289, 291  Yes  Yes  Mixed Air HVAC System   Mon=4am-6pm
Tue=4am-6pm
Wed=4am-6pm
Thu=4am-6pm
Fri=4am-6pm
Off=Sat
Off=Sun
Off=Holidays  
Mon=4am-6pm
Tue=4am-6pm
Wed=4am-9pm
Thu=4am-6pm
Fri=4am-6pm
Off=Sat
Off=Sun
Off=Holidays  
AHU23 Rm 142  Yes  Yes  Mixed Air HVAC System   24/7  24/7 
AHU-1 Room 0227 and others  Yes  Yes  Mixed Air HVAC System   Time clock  Time Clock 


Unit Service Area Control Strategies
AHU10  East Offices  Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU11  Rms 283, 287  Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU12  South Gym 173  Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU13  North Gym 175  Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU14  West Gym 184  Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU15  East Gym 184  Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU16  Gym Room 194  Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU17  East Room 196  Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU18  West Room 196  Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU19  Room 198  Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU20  Rms 178N, 178S  Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU21  Locker rms 187, 189  Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU23  Rm 142  Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU22  West Offices, Rms 289, 291  Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.


Date Ex Energy Conservation Action(s) Taken
3/16/2006 AHU11 = complete
3/16/2006 AHU12 = complete
3/16/2006 AHU13 = complete
3/16/2006 AHU20 = complete
3/16/2006 AHU21 = complete
3/16/2006 AHU23 = complete
3/16/2006 AHU10 = complete
3/16/2006 AHU22 = complete
6/22/2006 AH21 = complete, also see exemption #5
7/12/2006   Completed MEA Holiday schedules and reviewed hours of operation
10/30/2006   Reviewed for winter schedule
5/10/2007   Reviewed for summer schedule
9/20/2007 10  AHU-22 extended hours on wednesday until 9:pm
11/1/2007   Reviewed for winter schedule
5/22/2008   Reviewed for summer schedule
9/15/2008   Reviewed for winter schedule.
5/12/2009   Reviewed for summer schedule
10/7/2009   Reviewed for winter schedule.
5/12/2010   Reviewed for summer schedule
6/7/2011   Reviewed for summer schedule 2011.
6/7/2011   Reviewed for summer schedule 2011.
2/17/2012   Reviewed for winter schedule.
10/8/2012   Reviewed for winter schedules