| # | Exemptions | Summer | Winter |
|---|---|---|---|
| 1 | (AHU11) Rm 283 - Biochem Lab | 24/7 | 24/7 |
| 2 | (AHU12) Gyms | 24/7 for air movement | |
| 3 | (AHU13) Gym | 24/7 for air movement | |
| 4 | (AHU20) Rms 178N, 178S Research Labs | 24/7 | 24/7 |
| 5 | (AHU21) Locker Rms 187, 189 - Air Circulation and room 164 reheats | 24/7 | 24/7 |
| 6 | (AHU23) Rm 142 Inadequate Cooling | 24/7 | 24/7 |
| 7 | (AHU10) extended hours | 4am - 6pm weekdays, 4am-noon, Sat, Sun | 6am - 6pm weekdays, 6am-noon, Sat, Sun |
| 8 | (AHU22) extended hours | 4am - 6pm weekdays, 4am-noon, Sat, Sun | 6am - 6pm weekdays, 6am-noon, Sat, Sun |
| 9 | (AHU21) Extended hours Rms 164Q and 164V | 24/7 | 24/7 |
| 10 | (AHU-22) Room 289 Extended hours | Run until 9:00 PM WED. thru Dec. 2007 |
| Unit | Service Area | Cool | Heat | System Type | Summer Hours | Winter Hours |
|---|---|---|---|---|---|---|
| AHU10 | East Offices | Yes | Yes | Mixed Air HVAC System | Mon=4am-6pm Tue=4am-6pm Wed=4am-6pm Thu=4am-6pm Fri=4am-6pm Sat=4am-12pm Sun=4am-12pm Off=Holidays |
Mon=6am-6pm Tue=6am-6pm Wed=6am-6pm Thu=6am-6pm Fri=6am-6pm Sat=6am-12pm Sun=6am-12pm Off=Holidays |
| AHU11 | Rms 283, 287 | Yes | Yes | Mixed Air HVAC System | 24/7 | 24/7 |
| AHU12 | South Gym 173 | Yes | Mixed Air HVAC System | 24/7 | Mon=6am-6pm Tue=6am-6pm Wed=6am-6pm Thu=6am-6pm Fri=6am-6pm Off=Sat Off=Sun Off=Holidays |
|
| AHU13 | North Gym 175 | Yes | Mixed Air HVAC System | 24/7 | Mon=6am-6pm Tue=6am-6pm Wed=6am-6pm Thu=6am-6pm Fri=6am-6pm Off=Sat Off=Sun Off=Holidays |
|
| AHU14 | West Gym 184 | Yes | Mixed Air HVAC System | Mon=6am-6pm Tue=6am-6pm Wed=6am-6pm Thu=6am-6pm Fri=6am-6pm Off=Sat Off=Sun Off=Holidays |
Mon=6am-6pm Tue=6am-6pm Wed=6am-6pm Thu=6am-6pm Fri=6am-6pm Off=Sat Off=Sun Off=Holidays |
|
| AHU15 | East Gym 184 | Yes | Mixed Air HVAC System | Mon=6am-6pm Tue=6am-6pm Wed=6am-6pm Thu=6am-6pm Fri=6am-6pm Off=Sat Off=Sun Off=Holidays |
Mon=6am-6pm Tue=6am-6pm Wed=6am-6pm Thu=6am-6pm Fri=6am-6pm Off=Sat Off=Sun Off=Holidays |
|
| AHU16 | Gym Room 194 | Yes | Yes | Mixed Air HVAC System | Run = 4am-9pm, Mon Run = 4am-8pm, Tue Run = 4am-8pm, Wed Run = 4am-8pm, Thu Run = 4am-8pm, Fri Off = Sat Off = Sun Off = Holidays |
Run = 6am-6pm, Mon Run = 6am-6pm, Tue Run = 6am-6pm, Wed Run = 6am-6pm, Thu Run = 6am-6pm, Fri Off = Sat Off = Sun Off = Holidays |
| AHU17 | East Room 196 | Yes | Yes | Mixed Air HVAC System | Mon=6am-6pm Tue=6am-6pm Wed=6am-6pm Thu=6am-6pm Fri=6am-6pm Sat=6am-12pm Sun= 6am-12pm Off=Holidays |
Mon=6am-6pm Tue=6am-6pm Wed=6am-6pm Thu=6am-6pm Fri=6am-6pm Sat=6am-12pm Sun= 6am-12pm Off=Holidays |
| AHU18 | West Room 196 | Yes | Yes | Mixed Air HVAC System | Mon=6am-6pm Tue=6am-6pm Wed=6am-6pm Thu=6am-6pm Fri=6am-6pm Sat=6am-12pm Sun= 6am-12pm Off=Holidays |
Mon=6am-6pm Tue=6am-6pm Wed=6am-6pm Thu=6am-6pm Fri=6am-6pm Sat=6am-12pm Sun= 6am-12pm Off=Holidays |
| AHU19 | Room 198 | Yes | Yes | Mixed Air HVAC System | Mon=6am-6pm Tue=6am-6pm Wed=6am-6pm Thu=6am-6pm Fri=6am-6pm Sat=6am-12pm Sun= 6am-12pm Off=Holidays |
Mon=6am-6pm Tue=6am-6pm Wed=6am-6pm Thu=6am-6pm Fri=6am-6pm Sat=6am-12pm Sun= 6am-12pm Off=Holidays |
| AHU20 | Rms 178N, 178S | Yes | Yes | Mixed Air HVAC System | 24/7 | 24/7 |
| AHU21 | Locker rms 187, 189 | Yes | Yes | Mixed Air HVAC System | 24/7 | 24/7 |
| AHU22 | West Offices, Rms 289, 291 | Yes | Yes | Mixed Air HVAC System | Mon=4am-6pm Tue=4am-6pm Wed=4am-6pm Thu=4am-6pm Fri=4am-6pm Off=Sat Off=Sun Off=Holidays |
Mon=4am-6pm Tue=4am-6pm Wed=4am-9pm Thu=4am-6pm Fri=4am-6pm Off=Sat Off=Sun Off=Holidays |
| AHU23 | Rm 142 | Yes | Yes | Mixed Air HVAC System | 24/7 | 24/7 |
| AHU-1 | Room 0227 and others | Yes | Yes | Mixed Air HVAC System | Time clock | Time Clock |
| Unit | Service Area | Control Strategies |
|---|---|---|
| AHU10 | East Offices | Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| AHU11 | Rms 283, 287 | Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| AHU12 | South Gym 173 | Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| AHU13 | North Gym 175 | Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| AHU14 | West Gym 184 | Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| AHU15 | East Gym 184 | Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| AHU16 | Gym Room 194 | Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| AHU17 | East Room 196 | Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| AHU18 | West Room 196 | Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| AHU19 | Room 198 | Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| AHU20 | Rms 178N, 178S | Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| AHU21 | Locker rms 187, 189 | Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| AHU23 | Rm 142 | Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| AHU22 | West Offices, Rms 289, 291 | Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| Date | Ex | Energy Conservation Action(s) Taken |
|---|---|---|
| 3/16/2006 | 1 | AHU11 = complete |
| 3/16/2006 | 2 | AHU12 = complete |
| 3/16/2006 | 3 | AHU13 = complete |
| 3/16/2006 | 4 | AHU20 = complete |
| 3/16/2006 | 5 | AHU21 = complete |
| 3/16/2006 | 6 | AHU23 = complete |
| 3/16/2006 | 7 | AHU10 = complete |
| 3/16/2006 | 8 | AHU22 = complete |
| 6/22/2006 | 9 | AH21 = complete, also see exemption #5 |
| 7/12/2006 | Completed MEA Holiday schedules and reviewed hours of operation | |
| 10/30/2006 | Reviewed for winter schedule | |
| 5/10/2007 | Reviewed for summer schedule | |
| 9/20/2007 | 10 | AHU-22 extended hours on wednesday until 9:pm |
| 11/1/2007 | Reviewed for winter schedule | |
| 5/22/2008 | Reviewed for summer schedule | |
| 9/15/2008 | Reviewed for winter schedule. | |
| 5/12/2009 | Reviewed for summer schedule | |
| 10/7/2009 | Reviewed for winter schedule. | |
| 5/12/2010 | Reviewed for summer schedule | |
| 6/7/2011 | Reviewed for summer schedule 2011. | |
| 6/7/2011 | Reviewed for summer schedule 2011. | |
| 2/17/2012 | Reviewed for winter schedule. | |
| 10/8/2012 | Reviewed for winter schedules |