Building Energy Plans

Forker Building

Year Constructed: 1940 / 1972

138,703 Gross Square Feet

All Floors Plan - HVAC

Basement Floor Plan - HVAC

First Floor Plan - HVAC

Second Floor Plan - HVAC

Third Floor Plan - HVAC

# Exemptions Summer Winter
1 (AHU11) Rm 283 - Biochem Lab 24/7  24/7 
2 (AHU12) Gyms 24/7 for air movement   
3 (AHU13) Gym 24/7 for air movement   
4 (AHU20) Rms 178N, 178S Research Labs 24/7  24/7 
5 (AHU21) Locker Rms 187, 189 - Air Circulation and room 164 reheats 24/7  24/7 
6 (AHU23) Rm 142 Inadequate Cooling 24/7  24/7 
7 (AHU10) extended hours 4am - 6pm weekdays, 4am-noon, Sat, Sun  6am - 6pm weekdays, 6am-noon, Sat, Sun 
8 (AHU22) extended hours 4am - 6pm weekdays, 4am-noon, Sat, Sun  6am - 6pm weekdays, 6am-noon, Sat, Sun 
9 (AHU21) Extended hours Rms 164Q and 164V 24/7  24/7 
10 (AHU-22) Room 289 Extended hours   Run until 9:00 PM WED. thru Dec. 2007 


Unit Service Area Cool Heat System Type Summer Hours Winter Hours
AHU10 East Offices  Yes  Yes  Mixed Air HVAC System   ON M-F, 4am -6pm
ON Sat, Sun, 4am-12pm
OFF Holidays  
ON M-F, 6am -6pm
ON Sat, Sun, 6am-12pm
OFF Holidays  
AHU11 Rms 283, 287  Yes  Yes  Mixed Air HVAC System   ON 24/7
ON Holidays 
ON 24/7
ON Holidays 
AHU12 South Gym 173    Yes  Mixed Air HVAC System   ON 24/7
ON Holidays 
ON M-F 6am -6pm
OFF Sat, Sun, Holidays  
AHU13 North Gym 175    Yes  Mixed Air HVAC System   ON 24/7
ON Holidays 
ON M-F 6am -6pm
OFF Sat, Sun, Holidays 
AHU14 West Gym 184    Yes  Mixed Air HVAC System   ON M-FM 6am -6pm
OFF Sat, Sun, Holidays 
ON M-F 6am -6pm
OFF Sat, Sun, Holidays 
AHU15 East Gym 184    Yes  Mixed Air HVAC System   ON M-FM 6am -6pm
OFF Sat, Sun, Holidays 
ON M-F 6am -6pm
OFF Sat, Sun, Holidays 
AHU16 Gym Room 194  Yes  Yes  Mixed Air HVAC System   ON Mon, 4am -9pm
ON Tue-F, 4am -8pm
OFF Sat, Sun, Holidays 
ON M-F, 6am -6pm
OFF Sat, Sun, Holidays 
AHU17 East Room 196  Yes  Yes  Mixed Air HVAC System   ON M-F, 6am -6pm
ON Sat, Sun, 6am-12pm
OFF Holidays 
ON M-F, 6am -6pm
ON Sat, Sun, 6am-12pm
OFF Holidays 
AHU18 West Room 196  Yes  Yes  Mixed Air HVAC System   ON M-F, 6am -6pm
ON Sat, Sun, 6am-12pm
OFF Holidays 
ON M-F, 6am -6pm
ON Sat, Sun, 6am-12pm
OFF Holidays 
AHU19 Room 198  Yes  Yes  Mixed Air HVAC System   ON M-F, 6am -6pm
ON Sat, Sun, 6am-12pm
OFF Holidays 
ON M-F, 6am -6pm
ON Sat, Sun, 6am-12pm
OFF Holidays 
AHU20 Rms 178N, 178S  Yes  Yes  Mixed Air HVAC System   ON 24/7
ON Holidays 
ON 24/7
ON Holidays 
AHU21 Locker rms 187, 189  Yes  Yes  Mixed Air HVAC System   ON 24/7
ON Holidays 
ON 24/7
ON Holidays 
AHU22 West Offices, Rms 289, 291  Yes  Yes  Mixed Air HVAC System   ON M-F, 4am -6pm
OFF Sat, Sun, Holidays  
ON M-F, 4am -6pm
OFF Sat, Sun, Holidays  
AHU23 Rm 142  Yes  Yes  Mixed Air HVAC System   ON 24/7
ON Holidays  
ON 24/7
ON Holidays  
AHU-1 Room 0227 and others  Yes  Yes  Mixed Air HVAC System   Time clock  Time Clock 


Unit Service Area Control Strategies
AHU10  East Offices  Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU11  Rms 283, 287  Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU12  South Gym 173  Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU13  North Gym 175  Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU14  West Gym 184  Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU15  East Gym 184  Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU16  Gym Room 194  Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU17  East Room 196  Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU18  West Room 196  Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU19  Room 198  Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU20  Rms 178N, 178S  Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU21  Locker rms 187, 189  Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU23  Rm 142  Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU22  West Offices, Rms 289, 291  Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.


Date Ex Energy Conservation Action(s) Taken
3/16/2006 AHU11 = complete
3/16/2006 AHU12 = complete
3/16/2006 AHU13 = complete
3/16/2006 AHU20 = complete
3/16/2006 AHU21 = complete
3/16/2006 AHU23 = complete
3/16/2006 AHU10 = complete
3/16/2006 AHU22 = complete
6/22/2006 AH21 = complete, also see exemption #5
7/12/2006   Completed MEA Holiday schedules and reviewed hours of operation
10/30/2006   Reviewed for winter schedule
5/10/2007   Reviewed for summer schedule
9/20/2007 10  AHU-22 extended hours on wednesday until 9:pm
11/1/2007   Reviewed for winter schedule
5/22/2008   Reviewed for summer schedule
9/15/2008   Reviewed for winter schedule.
5/12/2009   Reviewed for summer schedule
10/7/2009   Reviewed for winter schedule.
5/12/2010   Reviewed for summer schedule
6/7/2011   Reviewed for summer schedule 2011.
6/7/2011   Reviewed for summer schedule 2011.
2/17/2012   Reviewed for winter schedule.
10/8/2012   Reviewed for winter schedules
5/20/2015   Reviewed for Summer 2015
11/11/2015   Reviewed for Fall 2015