| # | Exemptions | Summer | Winter |
|---|---|---|---|
| 1 | (AHU1) Classrooms and Computer Labs | 7am-11:30pm all days | 7am-11:30pm all days |
| 2 | Weekend MBA Program (AHU3) | 7am-5pm Sat, 11am-5pm Sun | 7am-5pm Sat, 11am-5pm Sun |
| 3 | (AHU2) Rm 2148 - Large computer Lab | 72 degrees | 70 degrees |
| 4 | (AHU2) Classrooms and Computer labs | 6am -11:30pm all days | 6am -11:30pm all days |
| Unit | Service Area | Cool | Heat | System Type | Summer Hours | Winter Hours |
|---|---|---|---|---|---|---|
| AHU1 | Serves all floors - South wing | Yes | Yes | HVAC System with Reheat | 7am-11:30pm all days | 7am-11:30pm all days |
| AHU2 | Auditorium and large classrooms | Yes | Yes | HVAC System with Reheat | 7am-8pm, Mon 7am-8pm,Tue 7am-8pm, Wed 7am-8pm, Thu 7am-7:30pm, Fri 7am-6pm, Sat 12pm-6:30pm, Sun Off = Holidays Early 4am start for custodians |
7am–9:30pm, Mon 7am–9:30pm, Tue 7am–9:30pm, Wed 7am–9:30pm, Thu 7am–7:00pm, Fri 7am–6pm, Sat 12pm–6pm, Sun Off = Holidays Early 4am start for custodians |
| AHU3 | Offices and Interactive Rooms | Yes | Yes | HVAC System with Reheat | 6:30am-6pm,Mon 6:30am-6pm,Tue 6:30am-6pm,Wed 6:30am-6pm,Thu 6:30am-6pm,Fri 6:30am-6pm,Sat 11:30am-5pm,Sun OFF Holidays |
6am – 10pm, Mon 6am – 10pm, Tue 6am – 10pm, Wed 6am – 10pm, Thu 6am – 10pm, Fri 7am – 6pm, Sat 11am – 6pm, Sun Off = Holidays |
| FCUs | Entrance & Stairwells | Yes | Yes | Fan Coil Unit Without an Operable Thermostat | 7am - 8pm Mon-Thu 7am - 5:30pm Friday 7:30am - 6:30pm Sat 11:30am - 6:30pm Sun |
7am - 8pm Mon-Thu 7am - 5:30pm Friday 7:30am - 6:30pm Sat 11:30am - 6:30pm Sun |
| Unit | Service Area | Control Strategies |
|---|---|---|
| AHU1 | Serves all floors - South wing | Thermostat set at 73-degrees all year. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| AHU2 | Auditorium and large classrooms | Thermostat set at 73-degrees all year. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| AHU3 | Offices and Interactive Rooms | Thermostat set at 73-degrees all year. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| LTG | Interior lighting | Programmed On 1/2 hours before occupancy and Off 1/2 hour after occupancy. Early 4:00am On time for Custodial cleaning. Reduced hours for summer. |
| Date | Ex | Energy Conservation Action(s) Taken |
|---|---|---|
| 4/5/2006 | 1 | AHU1 = COMPLETE |
| 4/5/2006 | 2 | AHU3 = COMPLETE |
| 4/5/2006 | 4 | AHU2 = COMPLETE |
| 4/5/2006 | COMPLETED SPRING 06 BUILDING ENERGY CONSERVATION SETTINGS | |
| 4/5/2006 | 3 | (AHU2) ROOM 2148 = COMPLETE |
| 5/8/2006 | REDUCED AHU AND LIGHTING HOURS FOR SUMMER | |
| 5/8/2006 | Reduced lighting schedule for summer--note 4:00am start for custodial cleaning | |
| 7/12/2006 | Completed MEA Holiday schedules and reviewed hours of operation | |
| 8/8/2006 | WO# = W655706= Rooms (1312, 1313, 1314, 1315, 1316 (VMA box = 169ASC66), (1326 (VMA box = 169ASC68), (1328, 1330, 1332, 1334, 1336, 1338 (VMA box 169ASC72)= new motion detectors added and activated 8/07/06 | |
| 10/23/2006 | AHU's Preheating System: Interlock Glycol Heating system enable command to AHU's Operation and adjust Pre-heat enable set point to 55 F. | |
| 10/30/2006 | Reviewed for winter schedule | |
| 5/10/2007 | Reviewed for summer schedule | |
| 8/27/2007 | 5 | Run = AHU1 = 24/7 |
| 8/27/2007 | 5 | Room 2140 = Comm_spt= 1F, Occ_Cbias= +1.7F, Occ_Hbias -1.7F, Occ_CMax - 350 CFM |
| 9/1/2007 | FCU's Schedule Operation | |
| 11/1/2007 | Reviewed for winter schedule | |
| 5/22/2008 | Reviewed for summer schedule | |
| 4/23/2009 | "Exemption #5 (AHU1 to run 24/7) was removed" | |
| 5/8/2009 | Reviewed for summer schedule | |
| 5/12/2009 | Reviewed for summer schedule: AHU-2 start from 4am to 5am (Paul Haggard) | |
| 10/7/2009 | Reviewed for winter schedule. | |
| 10/7/2009 | Reviewed for winter schedule. |