| # | Exemptions | Summer | Winter |
|---|---|---|---|
| 1 | (AHU2) Research Labs 003, 006, 14, 103, 139 | 24/7 | 24/7 |
| 2 | (AHU3) Research Labs 151, 156, 225, 233, 248, 256 | 24/7 | 24/7 |
| Unit | Service Area | Cool | Heat | System Type | Summer Hours | Winter Hours |
|---|---|---|---|---|---|---|
| AHU1 | Ground Floor East | Yes | Yes | Mixed Air HVAC System | Run = 7am-6pm, Mon Run = 7am-6pm, Tue Run = 7am-6pm, Wed Run = 7am-6pm, Thu Run = 7am-6pm, Fri Off = Sat Off = Sun Off = Holidays |
Run = 7am-6pm, Mon Run = 7am-6pm, Tue Run = 7am-6pm, Wed Run = 7am-6pm, Thu Run = 7am-6pm, Fri Off = Sat Off = Sun Off = Holidays |
| AHU2 | Ground Floor West & 1st Floor | Yes | Yes | Mixed Air HVAC System | 24/7 | 24/7 |
| AHU3 | 24/7 | Yes | Yes | Mixed Air HVAC System | 24/7 | 24/7 |
| AHU4 | Auditorium 118 | Yes | Yes | Mixed Air HVAC System | Room Scheduling | Room Scheduling |
| Unit | Service Area | Control Strategies |
|---|---|---|
| AHU1 | Ground Floor East | Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| AHU2 | Ground Floor West & 1st Floor | Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| AHU3 | 24/7 | Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| AHU4 | Auditorium 118 | Thermostat set at 70/76 degrees. Heating and cooling controlled by thermostat that modulates dampers in a mixing box located in each zone. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| Date | Ex | Energy Conservation Action(s) Taken |
|---|---|---|
| 3/17/2006 | 2 | AHU3 = complete |
| 3/17/2006 | 1 | AHU2 = complete |
| 7/14/2006 | Completed MEA Holiday schedules and reviewed hours of operation | |
| 10/31/2006 | Reviewed for winter schedule | |
| 5/10/2007 | Reviewed for summer schedule | |
| 11/2/2007 | Reviewed for winter schedule | |
| 9/16/2008 | Reviewed for winter schedule. | |
| 5/12/2009 | Reviewed for summer schedule | |
| 10/7/2009 | Reviewed for winter schedule. |