| # | Exemptions | Summer | Winter |
|---|---|---|---|
| 1 | (AHU5) Auditorium Rms 1140, 1140A | 6am - midnight Mon-Sat | 6am - midnight Mon-Sat |
| 2 | (FCU1, FCU2 ) Auditorium Projection Booth 1142A (AHU5) | FCU1 = 24/7, FCU2 is controlled by occupants | FCU1 = 24/7, FCU2 is controlled by occupants |
| 3 | (AHU2) Rm 1328, Media Services | 24/7 | 24/7 |
| 4 | (AHU2) Rm 1364C, TV Control Rm | 24/7 | 24/7 |
| 5 | (AHU2) Rms 2304, 2332, 2344 | 24/7 | 24/7 |
| 6 | (AHU4) Rm 144 | 6am -midnight Mon-Fri | 6am -midnight Mon-Fri |
| 7 | (AHU1) Rm 2362 | 6am - midnight | 6am - midnight |
| 8 | (AHU7) Rm 1620 | 6am - midnight Mon-Fri | 6am - midnight Mon-Fri |
| 9 | (AHU7) Rms 1638, 2624 | 6am - midnight Mon-Fri | 6am - midnight Mon-Fri |
| 10 | (AHU8) Basement Elec and Generator Rm 0145 | 24/7 | 24/7 |
| 11 | (AHU9) Zone D, Fan not sized right? | 24/7 | 24/7 |
| 12 | (FCU3) ROOM 1620C computer server | 24/7 @ 68F degrees | 24/7 @68F degrees |
| 13 | AH-6 Lab 2624 | Run 7 am to 8 pm M-F and 8 am to 8 pm Sat, /Sun. | RUN 7 am to 8 pm M-F and 8 am to 8 pm Sat,/Sun. |
| Unit | Service Area | Cool | Heat | System Type | Summer Hours | Winter Hours |
|---|---|---|---|---|---|---|
| AHU1 | Basement, 1st, 2nd floor Labs | Yes | Yes | VAV with Reheat | Mon=6am-midnight Tue=6am-midnight Wed=6am-midnight Thu=6am-midnight Fri=6am-midnight Sat=6am-midnight Sun=6am-midnight Hol=6am-midnight |
Mon=6am-midnight Tue=6am-midnight Wed=6am-midnight Thu=6am-midnight Fri=6am-midnight Sat=6am-midnight Sun=6am-midnight Hol=6am-midnight |
| AHU2 | 1st and 2nd floor Offices and Labs | Yes | Yes | VAV with Reheat | 24/7 | 24/7 |
| AHU3 | Atrium and walkway | Yes | Yes | VAV with Reheat | Run = 7am - 6pm, Mon Run = 7am - 6pm, Tue Run = 7am - 6pm, Wed Run = 7am - 6pm, Thu Run = 7am - 6pm, Fri Off = Sat Off = Sun Off = Holidays |
Run = 7am - 6pm, Mon Run = 7am - 6pm, Tue Run = 7am - 6pm, Wed Run = 7am - 6pm, Thu Run = 7am - 6pm, Fri Off = Sat Off = Sun Off = Holidays |
| AHU4 | Basement and 1st flooe East Lobby | Yes | Yes | VAV with Reheat | Run = 6am - midnight, Mon Run = 6am - midnight, Tue Run = 6am - midnight, Wed Run = 6am - midnight, Thu Run = 6am - midnight, Fri Off = Sat Off = Sun Off = Holidays |
Run = 6am - midnight, Mon Run = 6am - midnight, Tue Run = 6am - midnight, Wed Run = 6am - midnight, Thu Run = 6am - midnight, Fri Off = Sat Off = Sun Off = Holidays |
| AHU5 | East Oval Auditorium | Yes | Yes | VAV with Reheat | Run = 6am - midnight, Mon Run = 6am - midnight, Tue Run = 6am - midnight, Wed Run = 6am - midnight, Thu Run = 6am - midnight, Fri Run = 6am - midnight, Sat Off = Sun Off = Holidays |
Run = 6am - midnight, Mon Run = 6am - midnight, Tue Run = 6am - midnight, Wed Run = 6am - midnight, Thu Run = 6am - midnight, Fri Run = 6am - midnight, Sat Off = Sun Off = Holidays |
| AHU6 | Basement, 1st, 2nd floor Interior Zone C | Yes | Yes | VAV with Reheat | Mon=7am - 8pm Tue=7am - 8pm Wed=7am - 8pm Thu=7am - 8pm Fri=7am - 8pm Sat=8am - 8pm Sun=8am - 8pm Off = Holidays |
Mon=7am - 8pm Tue=7am - 8pm Wed=7am - 8pm Thu=7am - 8pm Fri=7am - 8pm Sat=8am - 8pm Sun=8am - 8pm Off = Holidays |
| AHU7 | Basement, 1st, 2nd floors Exterior - Zone C | Yes | Yes | VAV with Reheat | Run = 6am-midnight, Mon Run = 6am-midnight, Tue Run = 6am-midnight, Wed Run = 6am-midnight, Thu Run = 6am-midnight, Fri Off = Sat Off = Sun Off = Holidays |
Run = 6am-midnight, Mon Run = 6am-midnight, Tue Run = 6am-midnight, Wed Run = 6am-midnight, Thu Run = 6am-midnight, Fri Off = Sat Off = Sun Off = Holidays |
| AHU8 | Basement Elec and Generator Rm | Yes | Yes | VAV with Reheat | 24/7 | 24/7 |
| AHU9 | Zone D | Yes | Yes | VAV with Reheat | 24/7 | 24/7 |
| Unit | Service Area | Control Strategies |
|---|---|---|
| AHU1 | Basement, 1st, 2nd floor Labs | Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| AHU2 | 1st and 2nd floor Offices and Labs | Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| AHU3 | Atrium and walkway | Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| AHU4 | Basement and 1st flooe East Lobby | Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| AHU5 | East Oval Auditorium | Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| AHU6 | Basement, 1st, 2nd floor Interior Zone C | Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| AHU7 | Basement, 1st, 2nd floors Exterior - Zone C | Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| AHU8 | Basement Elec and Generator Rm | Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| AHU9 | Zone D | Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| Date | Ex | Energy Conservation Action(s) Taken |
|---|---|---|
| 4/5/2006 | 12 | FCU3 = complete |
| 4/5/2006 | 2 | FCU1, FCU2 = complete |
| 4/5/2006 | 3 | AHU2 = complete |
| 4/5/2006 | 4 | AHU2 = complete |
| 4/5/2006 | 5 | AHU2 = complete |
| 4/5/2006 | 6 | AHU4 = complete |
| 4/5/2006 | 7 | AHU1 =complete |
| 4/5/2006 | 8 | AHU7 = complete |
| 4/5/2006 | 9 | AHU7 =complete |
| 4/5/2006 | 1 | AHU5 = complete |
| 4/5/2006 | 11 | AHU9 = complete |
| 4/5/2006 | 10 | AHU8 =complete |
| 7/14/2006 | Completed MEA Holiday schedules and reviewed hours of operation | |
| 10/31/2006 | Rviewed for winter schedule | |
| 4/27/2007 | AHU7: scheduled fan to run from 12pm to 6pm for saturday and sunday (4/27/07) = request from Don Hoffmann and Luis Garcia | |
| 8/9/2007 | AH-7 scheduled to run 1200 to 2100 on Sat/Sun. Luis in response to Chris in room 2635 | |
| 11/2/2007 | Reviewed for winter schedule | |
| 5/22/2008 | Reviewed for summer schedule. | |
| 9/16/2008 | Reviewed for winter schedule. | |
| 5/12/2009 | Reviewed for summer schedule | |
| 10/7/2009 | Reviewed for winter schedule. |