ISU Facilities

Building Energy Plans

Howe Hall

Year Constructed: 1999

192,944 Gross Square Feet

# Exemptions Summer Winter
1 (AHU5) Auditorium Rms 1140, 1140A 6am - midnight Mon-Sat  6am - midnight Mon-Sat 
2 (FCU1, FCU2 ) Auditorium Projection Booth 1142A (AHU5) FCU1 = 24/7, FCU2 is controlled by occupants  FCU1 = 24/7, FCU2 is controlled by occupants 
3 (AHU2) Rm 1328, Media Services 24/7  24/7 
4 (AHU2) Rm 1364C, TV Control Rm 24/7  24/7 
5 (AHU2) Rms 2304, 2332, 2344 24/7  24/7 
6 (AHU4) Rm 144 6am -midnight Mon-Fri  6am -midnight Mon-Fri 
7 (AHU1) Rm 2362 6am - midnight  6am - midnight 
8 (AHU7) Rm 1620 6am - midnight Mon-Fri  6am - midnight Mon-Fri 
9 (AHU7) Rms 1638, 2624 6am - midnight Mon-Fri  6am - midnight Mon-Fri 
10 (AHU8) Basement Elec and Generator Rm 0145 24/7  24/7 
11 (AHU9) Zone D, Fan not sized right? 24/7  24/7 
12 (FCU3) ROOM 1620C computer server 24/7 @ 68F degrees  24/7 @68F degrees 
13 AH-6 Lab 2624 Run 7 am to 8 pm M-F and 8 am to 8 pm Sat, /Sun.  RUN 7 am to 8 pm M-F and 8 am to 8 pm Sat,/Sun. 


Unit Service Area Cool Heat System Type Summer Hours Winter Hours
AHU1 Basement, 1st, 2nd floor Labs  Yes  Yes  VAV with Reheat   Mon=6am-midnight
Tue=6am-midnight
Wed=6am-midnight
Thu=6am-midnight
Fri=6am-midnight
Sat=6am-midnight
Sun=6am-midnight
Hol=6am-midnight 
Mon=6am-midnight
Tue=6am-midnight
Wed=6am-midnight
Thu=6am-midnight
Fri=6am-midnight
Sat=6am-midnight
Sun=6am-midnight
Hol=6am-midnight 
AHU2 1st and 2nd floor Offices and Labs  Yes  Yes  VAV with Reheat   24/7  24/7 
AHU3 Atrium and walkway  Yes  Yes  VAV with Reheat   Run = 7am - 6pm, Mon
Run = 7am - 6pm, Tue
Run = 7am - 6pm, Wed
Run = 7am - 6pm, Thu
Run = 7am - 6pm, Fri
Off = Sat
Off = Sun
Off = Holidays
 
Run = 7am - 6pm, Mon
Run = 7am - 6pm, Tue
Run = 7am - 6pm, Wed
Run = 7am - 6pm, Thu
Run = 7am - 6pm, Fri
Off = Sat
Off = Sun
Off = Holidays
 
AHU4 Basement and 1st flooe East Lobby  Yes  Yes  VAV with Reheat   Run = 6am - midnight, Mon
Run = 6am - midnight, Tue
Run = 6am - midnight, Wed
Run = 6am - midnight, Thu
Run = 6am - midnight, Fri
Off = Sat
Off = Sun
Off = Holidays
 
Run = 6am - midnight, Mon
Run = 6am - midnight, Tue
Run = 6am - midnight, Wed
Run = 6am - midnight, Thu
Run = 6am - midnight, Fri
Off = Sat
Off = Sun
Off = Holidays
 
AHU5 East Oval Auditorium  Yes  Yes  VAV with Reheat   Run = 6am - midnight, Mon
Run = 6am - midnight, Tue
Run = 6am - midnight, Wed
Run = 6am - midnight, Thu
Run = 6am - midnight, Fri
Run = 6am - midnight, Sat
Off = Sun
Off = Holidays
 
Run = 6am - midnight, Mon
Run = 6am - midnight, Tue
Run = 6am - midnight, Wed
Run = 6am - midnight, Thu
Run = 6am - midnight, Fri
Run = 6am - midnight, Sat
Off = Sun
Off = Holidays
 
AHU6 Basement, 1st, 2nd floor Interior Zone C  Yes  Yes  VAV with Reheat   Mon=7am - 8pm
Tue=7am - 8pm
Wed=7am - 8pm
Thu=7am - 8pm
Fri=7am - 8pm
Sat=8am - 8pm
Sun=8am - 8pm
Off = Holidays
 
Mon=7am - 8pm
Tue=7am - 8pm
Wed=7am - 8pm
Thu=7am - 8pm
Fri=7am - 8pm
Sat=8am - 8pm
Sun=8am - 8pm
Off = Holidays
 
AHU7 Basement, 1st, 2nd floors Exterior - Zone C  Yes  Yes  VAV with Reheat   Run = 6am-midnight, Mon
Run = 6am-midnight, Tue
Run = 6am-midnight, Wed
Run = 6am-midnight, Thu
Run = 6am-midnight, Fri
Off = Sat
Off = Sun
Off = Holidays
 
Run = 6am-midnight, Mon
Run = 6am-midnight, Tue
Run = 6am-midnight, Wed
Run = 6am-midnight, Thu
Run = 6am-midnight, Fri
Off = Sat
Off = Sun
Off = Holidays
 
AHU8 Basement Elec and Generator Rm  Yes  Yes  VAV with Reheat   24/7  24/7 
AHU9 Zone D  Yes  Yes  VAV with Reheat   24/7  24/7 


Unit Service Area Control Strategies
AHU1  Basement, 1st, 2nd floor Labs  Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU2  1st and 2nd floor Offices and Labs  Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU3  Atrium and walkway  Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU4  Basement and 1st flooe East Lobby  Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU5  East Oval Auditorium  Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU6  Basement, 1st, 2nd floor Interior Zone C  Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU7  Basement, 1st, 2nd floors Exterior - Zone C  Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU8  Basement Elec and Generator Rm  Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU9  Zone D  Thermostat set at 70-degrees all year. Cooling controlled by a duct temperature sensor for 76-degree return air. Heating controlled by thermostat and reheat coils in VAV boxes. Room temperature will naturally fluctuate between 70 degrees and 76 degrees depending on outside air temperature and heat load in the area served. During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.


Date Ex Energy Conservation Action(s) Taken
4/5/2006 12  FCU3 = complete
4/5/2006 FCU1, FCU2 = complete
4/5/2006 AHU2 = complete
4/5/2006 AHU2 = complete
4/5/2006 AHU2 = complete
4/5/2006 AHU4 = complete
4/5/2006 AHU1 =complete
4/5/2006 AHU7 = complete
4/5/2006 AHU7 =complete
4/5/2006 AHU5 = complete
4/5/2006 11  AHU9 = complete
4/5/2006 10  AHU8 =complete
7/14/2006   Completed MEA Holiday schedules and reviewed hours of operation
10/31/2006   Rviewed for winter schedule
4/27/2007   AHU7: scheduled fan to run from 12pm to 6pm for saturday and sunday (4/27/07) = request from Don Hoffmann and Luis Garcia
8/9/2007   AH-7 scheduled to run 1200 to 2100 on Sat/Sun. Luis in response to Chris in room 2635
11/2/2007   Reviewed for winter schedule
5/22/2008   Reviewed for summer schedule.
9/16/2008   Reviewed for winter schedule.
5/12/2009   Reviewed for summer schedule
10/7/2009   Reviewed for winter schedule.