HVAC Equipment Associated with Rooms
| # | Exemptions | Summer | Winter |
|---|---|---|---|
| 1 | S.E. fan coils, E005, E001, E006, E012, E016 (UV26 and FC1) | 24/7 | 24/7 |
| 2 | Computer labs - Rms W205, 207, 207A W002 (AHU6, FC1- southwest GRD floor and southwest 2nd floor) | 24/7 | 24/7 |
| 3 | Extended hours Rms N221E & N231 | Mon. thru Thurs. 10:00 PM Aug. thru Dec. 2007 | Tues. Wed. 9:30 PM Jan. 08 thru May 08 |
| 4 | Room E262 Extended hours Jan to March | 68 degrees 10:00 AM to 5:00 PM Sat. and Sun. | |
| 5 | (Exemption removed 10-26-09) (AHU5) Rm W249 24/7 operation for servers. Server room has been moved. | 24/7 | 24/7 |
| 6 | AH-3, AH-4, FCU NE-2, FCU NW-2 Rooms N221-E and N243-B: Tue, Wed, Thu to 9pm; Fri to 8pm; Sat 8-5:30 | ||
| 7 | Rms W0012 & W0014 24/7 for servers | 24/7 operation 76 degrees | 24/7 operation 68 egrees |
| Unit | Service Area | Cool | Heat | System Type | Summer Hours | Winter Hours |
|---|---|---|---|---|---|---|
| UV26-SE | SOUTHEAST - BSMT AND 1ST FLOOR | Yes | Yes | Mixed Air HVAC System | Run = 24/7 | Run = 24/7 |
| FC1-SE-GRD | SOUTHEAST - GROUND FLOOR | Yes | Yes | Fan Coil Unit with Occupant Thermostat | Run = 24/7 | Run = 24/7 |
| FC1-SE-1ST | SOUTHEAST - 1ST FLOOR | Yes | Yes | Fan Coil Unit with Occupant Thermostat | Run = 7am-6pm, Mon Run = 7am-6pm, Tue Run = 7am-6pm, Wed Run = 7am-6pm, Thu Run = 7am-6pm, Fri Off = Sat Off = Sun Off= Holidays |
Run = 7am-6pm, Mon Run = 7am-6pm, Tue Run = 7am-6pm, Wed Run = 7am-6pm, Thu Run = 7am-6pm, Fri Off = Sat Off = Sun Off= Holidays |
| AHU2-CE | CENTRAL EAST 1ST AND 2ND FLOOR | Yes | Yes | Dual Duct HVAC System | Room Scheduling | Room Scheduling |
| FC1-CE-1ST | CENTRAL EAST - 1ST FLOOR | Yes | Yes | Fan Coil Unit with Occupant Thermostat | Room Scheduling | Room Scheduling |
| FC1-CE-2ND | CENTRAL EAST - 2ND FLOOR | Yes | Yes | Fan Coil Unit with Occupant Thermostat | Run = 7am-6pm, Mon Run = 7am-6pm, Tue Run = 7am-6pm, Wed Run = 7am-6pm, Thu Run = 7am-6pm, Fri Off = Sat Off = Sun Off= Holidays |
Run = 7am-6pm, Mon Run = 7am-6pm, Tue Run = 7am-6pm, Wed Run = 7am-6pm, Thu Run = 7am-6pm, Fri Off = Sat Off = Sun Off= Holidays |
| AHU3-NE | NORTHEAST 1ST AND 2ND FLOOR | Yes | Yes | Mixed Air HVAC System | Room Scheduling Run = 7am-10pm, Mon Run = 7am-10pm, Tue Run = 7am-10pm, Wed Run = 7am-10pm, Thu Run = 7am-6pm, Fri Off = Sat Off = Sun Off= Holidays |
Room Scheduling Run = 7am-10pm, Mon Run = 7am-10pm, Tue Run = 7am-10pm, Wed Run = 7am-10pm, Thu Run = 7am-8:30pm, Fri Run = 8am-5:30pm = Sat Off = Sun Off= Holidays |
| FC1-NE-1ST | NORTHEAST 1ST FLOOR | Yes | Yes | Fan Coil Unit with Occupant Thermostat | Run = 7am-6pm, Mon Run = 7am-6pm, Tue Run = 7am-6pm, Wed Run = 7am-6pm, Thu Run = 7am-6pm, Fri Off = Sat Off = Sun Off= Holidays |
Run = 7am-6pm, Mon Run = 7am-6pm, Tue Run = 7am-6pm, Wed Run = 7am-6pm, Thu Run = 7am-6pm, Fri Off = Sat Off = Sun Off= Holidays |
| FC1-NE-2ND | NORTHEAST 2ND FLOOR | Yes | Yes | Fan Coil Unit with Occupant Thermostat | Room Scheduling Run = 7am-10pm, Mon Run = 7am-10pm, Tue Run = 7am-10pm, Wed Run = 7am-10pm, Thu Run = 7am-6pm, Fri Off = Sat Off = Sun Off= Holidays |
Room Scheduling Run = 7am-10pm, Mon Run = 7am-10pm, Tue Run = 7am-10pm, Wed Run = 7am-10pm, Thu Run = 7am-8:30pm, Fri Run = 8am-5:30pm = Sat Off = Sun Off= Holidays |
| AHU4-NW | NORTHWEST BASEMENT - 1ST - 2ND FLOOR | Yes | Yes | Dual Duct HVAC System | Room Scheduling Run = 7am-10pm, Mon Run = 7am-10pm, Tue Run = 7am-10pm, Wed Run = 7am-10pm, Thu Run = 7am-8:30pm, Fri Run = 7am-5:30pm, Sat Run = 12pm-10pm, Sun Off= Holidays |
Room Scheduling Run = 7am-10pm, Mon Run = 7am-10pm, Tue Run = 7am-10pm, Wed Run = 7am-10pm, Thu Run = 7am-8:30pm, Fri Run = 7am-5:30pm, Sat Run = 12pm-10pm, Sun Off= Holidays |
| FC1-NW-GRD | NORTHWEST- GROUND FLOOR | Yes | Yes | Fan Coil Unit with Occupant Thermostat | Run = 7am-6pm, Mon Run = 7am-6pm, Tue Run = 7am-6pm, Wed Run = 7am-6pm, Thu Run = 7am-6pm, Fri Off = Sat Off = Sun Off= Holidays |
Run = 7am-6pm, Mon Run = 7am-6pm, Tue Run = 7am-6pm, Wed Run = 7am-6pm, Thu Run = 7am-6pm, Fri Off = Sat Off = Sun Off= Holidays |
| FC1-NW-1ST | NORTHWEST - 1ST FLOOR | Yes | Yes | Fan Coil Unit with Occupant Thermostat | Room Scheduling | Room Scheduling |
| FC1-NW-2ND | NORTHWEST - 2ND FLOOR | Yes | Yes | Fan Coil Unit with Occupant Thermostat | Room Scheduling Run = 7am-10pm, Mon Run = 7am-10pm, Tue Run = 7am-10pm, Wed Run = 7am-10pm, Thu Run = 7am-9pm, Fri Off = Sat Off = Sun Off = Holidays |
Room Scheduling Run = 7am-10pm, Mon Run = 7am-10pm, Tue Run = 7am-10pm, Wed Run = 7am-10pm, Thu Run = 7am-9pm, Fri Run = 8am-5:30pm, Sat Off = Sun Off = Holidays |
| AHU5-CW | CENTRAL WEST - 1ST AND 2ND FLOOR | Yes | Yes | Fan Coil Unit with Occupant Thermostat | Room Scheduling | Room Scheduling |
| FC1-CW-1ST | CENTRAL WEST - 1ST FLOOR | Yes | Yes | Fan Coil Unit with Occupant Thermostat | Room Scheduling | Room Scheduling |
| FC1-CW-2ND | CENTRAL WEST - 2ND FLOOR | Yes | Yes | Fan Coil Unit with Occupant Thermostat | Room Scheduling | Room Scheduling |
| AHU6-SW | SOUTHWEST - GROUND - 1ST - 2ND FLOOR | Yes | Yes | Mixed Air HVAC System | Run = 24/7 | RUN = 24/7 |
| FC1-SW-GRD | SOUTHWEST - GROUND FLOOR | Yes | Yes | Fan Coil Unit with Occupant Thermostat | Run = 24/7 | Run = 24/7 |
| FC1-SW-1ST | SOUTHWEST - 1ST FLOOR | Yes | Yes | Fan Coil Unit with Occupant Thermostat | Run = 7am-6pm, Mon Run = 7am-6pm, Tue Run = 7am-6pm, Wed Run = 7am-6pm, Thu Run = 7am-6pm, Fri Off = Sat Off = Sun Off= Holidays |
Run = 7am-6pm, Mon Run = 7am-6pm, Tue Run = 7am-6pm, Wed Run = 7am-6pm, Thu Run = 7am-6pm, Fri Off = Sat Off = Sun Off= Holidays |
| FC1-SW-2ND | SOUTHWEST - 2ND FLOOR | Yes | Yes | Fan Coil Unit with Occupant Thermostat | Run = 7am-6pm, Mon Run = 7am-6pm, Tue Run = 7am-6pm, Wed Run = 7am-6pm, Thu Run = 7am-6pm, Fri Off = Sat Off = Sun Off= Holidays |
Run = 7am-6pm, Mon Run = 7am-6pm, Tue Run = 7am-6pm, Wed Run = 7am-6pm, Thu Run = 7am-6pm, Fri Off = Sat Off = Sun Off= Holidays |
| Date | Ex | Energy Conservation Action(s) Taken |
|---|---|---|
| 4/20/2006 | 2 | AHU6 and FC1 = complete |
| 4/20/2006 | 1 | UV26 and FC1 = complete |
| 7/14/2006 | Completed MEA Holiday schedules and reviewed hours of operation | |
| 8/23/2006 | 3 | FC1 = northeast 2nd floor = mon-thru = 10pm |
| 10/31/2006 | Reviewed for winter settings | |
| 5/10/2007 | 5 | AHU5 complete |
| 5/10/2007 | Reviewed for summer schedule | |
| 8/17/2007 | 3 | Extended hours of operation for AHU4 and FC1-NW-2nd floor (Fan Coil Unit) = Room N221-E |
| 8/17/2007 | 3 | Extended hours of operations for AHU3 and FC1-NE-2nd floor (Fan Coil Unit) = N-231 |
| 11/2/2007 | Reviewed for winter schedule | |
| 5/22/2008 | Reviewed for summer schedule. | |
| 1/8/2009 | 6 | Added new schedules for room N221-E and N243B |
| 5/13/2009 | Reviewed for summer schedule. | |
| 10/26/2009 | 5 | Exemption # 5 has been removed by department request. AHU5 will start to follow room schedule. |