| # | Exemptions | Summer | Winter |
|---|---|---|---|
| 1 | Room 059 - Textiles Collection (fan coil unit) Valid until Fall 2007 | 24/7 @ 68 degrees - occupant controlled | 24/7 @ 68 degrees - occupant controlled |
| 2 | Room 2078 - Textiles Collection (fan coil unit) | 24/7 @ 68 degrees - occupant controlled | 24/7 @ 68 degrees - Occupant controlled |
| Unit | Service Area | Cool | Heat | System Type | Summer Hours | Winter Hours |
|---|---|---|---|---|---|---|
| AHU1 | Auditorium 1210 | Yes | Yes | HVAC System with Reheat | Room Scheduling | Room Scheduling |
| AHU2 | 100% ODA Unit Ground level | Yes | Yes | Mixed Air HVAC System | 24/7 | 24/7 |
| AHU3 | 100% ODA Unit 1st/2nd floor | Yes | Yes | Mixed Air HVAC System | 24/7 | 24/7 |
| FCU1 | Ground Floor | Yes | Yes | Fan Coil Unit with Occupant Thermostat | 1] Room scheduling 2] Outdoor air temperature enable set point 3] Local pneumatic thermostat setting. |
1] Room scheduling 2] Outdoor air temperature enable set point 3] Local pneumatic thermostat setting. |
| FCU2 | 1st Floor | Yes | Yes | Fan Coil Unit with Occupant Thermostat | 1] Room scheduling 2] Outdoor air temperature enable set point 3] Local pneumatic thermostat setting. |
1] Room scheduling 2] Outdoor air temperature enable set point 3] Local pneumatic thermostat setting. |
| FCU3 | 2nd Floor | Yes | Yes | Fan Coil Unit with Occupant Thermostat | 1] Room scheduling 2] Outdoor air temperature enable set point 3] Local pneumatic thermostat setting. |
1] Room scheduling 2] Outdoor air temperature enable set point 3] Local pneumatic thermostat setting. |
| LIT1 | Interior / Lobby Area | Lighting Control | Run = 6am-22pm, Mon Run = 6am-22pm, Tue Run = 6am-22pm, Wed Run = 6am-22pm, Thu Run = 6am-6pm, Fri Run = 12pm-9pm, Sat Run = 12pm-9pm, Sun Off = Holiday's |
Run = 6am-22pm, Mon Run = 6am-22pm, Tue Run = 6am-22pm, Wed Run = 6am-22pm, Thu Run = 6am-6pm, Fri Run = 12pm-9pm, Sat Run = 12pm-9pm, Sun Off = Holiday's |
| Unit | Service Area | Control Strategies |
|---|---|---|
| AHU1 | Auditorium 1210 | During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. |
| AHU2 | 100% ODA Unit Ground level | During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. ON 24/7 because of museum clothes storage requirement. |
| AHU3 | 100% ODA Unit 1st/2nd floor | During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. ON 24/7 because of museum clothes storage requirement. |
| Date | Ex | Energy Conservation Action(s) Taken |
|---|---|---|
| 3/27/2006 | COMPLETED SPRING 06 BUILDING ENERGY CONSERVATION SETTINGS | |
| 7/14/2006 | Completed MEA Holiday schedules and reviewed hours of operation | |
| 10/31/2006 | Reviewed for winter schedule | |
| 5/10/2007 | Reviewed for summer schedule | |
| 11/2/2007 | Reviewed for winter schedule | |
| 5/22/2008 | Reviewed for summer schedule. | |
| 9/22/2008 | Reviewed for winter schedule. | |
| 5/13/2009 | Reviewed for summer schedule. |