ISU Facilities

Building Energy Plans

LeBaron Hall

Year Constructed: 1958 / 1992 / 2005

61,547 Gross Square Feet

# Exemptions Summer Winter
1 Room 059 - Textiles Collection (fan coil unit) Valid until Fall 2007 24/7 @ 68 degrees - occupant controlled  24/7 @ 68 degrees - occupant controlled 
2 Room 2078 - Textiles Collection (fan coil unit) 24/7 @ 68 degrees - occupant controlled  24/7 @ 68 degrees - Occupant controlled 


Unit Service Area Cool Heat System Type Summer Hours Winter Hours
AHU1 Auditorium 1210  Yes  Yes  HVAC System with Reheat   Room Scheduling  Room Scheduling 
AHU2 100% ODA Unit Ground level  Yes  Yes  Mixed Air HVAC System   24/7  24/7 
AHU3 100% ODA Unit 1st/2nd floor  Yes  Yes  Mixed Air HVAC System   24/7  24/7
 
FCU1 Ground Floor  Yes  Yes  Fan Coil Unit with Occupant Thermostat   1] Room scheduling

2] Outdoor air temperature enable set point

3] Local pneumatic thermostat setting. 
1] Room scheduling

2] Outdoor air temperature enable set point

3] Local pneumatic thermostat setting. 
FCU2 1st Floor  Yes  Yes  Fan Coil Unit with Occupant Thermostat   1] Room scheduling

2] Outdoor air temperature enable set point

3] Local pneumatic thermostat setting. 
1] Room scheduling

2] Outdoor air temperature enable set point

3] Local pneumatic thermostat setting. 
FCU3 2nd Floor  Yes  Yes  Fan Coil Unit with Occupant Thermostat   1] Room scheduling

2] Outdoor air temperature enable set point

3] Local pneumatic thermostat setting. 
1] Room scheduling

2] Outdoor air temperature enable set point

3] Local pneumatic thermostat setting. 
LIT1 Interior / Lobby Area      Lighting Control   Run = 6am-22pm, Mon
Run = 6am-22pm, Tue
Run = 6am-22pm, Wed
Run = 6am-22pm, Thu
Run = 6am-6pm, Fri
Run = 12pm-9pm, Sat
Run = 12pm-9pm, Sun
Off = Holiday's 
Run = 6am-22pm, Mon
Run = 6am-22pm, Tue
Run = 6am-22pm, Wed
Run = 6am-22pm, Thu
Run = 6am-6pm, Fri
Run = 12pm-9pm, Sat
Run = 12pm-9pm, Sun
Off = Holiday's 


Unit Service Area Control Strategies
AHU1  Auditorium 1210  During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit.
AHU2  100% ODA Unit Ground level  During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. ON 24/7 because of museum clothes storage requirement.
AHU3  100% ODA Unit 1st/2nd floor  During “off” periods there will be an 80-degree upper limit and a 65-degree lower limit. ON 24/7 because of museum clothes storage requirement.


Date Ex Energy Conservation Action(s) Taken
3/27/2006   COMPLETED SPRING 06 BUILDING ENERGY CONSERVATION SETTINGS
7/14/2006   Completed MEA Holiday schedules and reviewed hours of operation
10/31/2006   Reviewed for winter schedule
5/10/2007   Reviewed for summer schedule
11/2/2007   Reviewed for winter schedule
5/22/2008   Reviewed for summer schedule.
9/22/2008   Reviewed for winter schedule.
5/13/2009   Reviewed for summer schedule.