| # | Exemptions | Summer | Winter |
|---|---|---|---|
| 1 | Rm 1 - Department Classroom (AHU1, FCU1) | Schedule varies for academic year vs. summer | Schedule varies for academic year vs. summer |
| 2 | Rm 23, 23A - Tearoom (UV2, UV3) | 24/7 @ 72 degrees | 24/7 @ 72 degrees |
| 3 | Rm 201, 206, 207, 210 - Teaching Labs with heat load (AHU7) | 72 degrees for Academic Year | none |
| 4 | Rm 30A thru 30E, 31, 31A - extended staff occupancy times (AHU3 and locally controlled fan coil units) | Mon-Fri 7am-10pm, Sat/Sun 10am-4pm, Holidays off | Mon-Fri 7am-6pm, Sat/Sun 10am-4pm, Holidays off |
| 5 | (AHU7) Room 207 | Run 24/7 | Run 24/7 |
| Unit | Service Area | Cool | Heat | System Type | Summer Hours | Winter Hours |
|---|---|---|---|---|---|---|
| AHU1 | Ground, 1st, 2nd, 3rd Floor - West | Yes | Yes | Mixed Air HVAC System | Mon=6am-6pm Tue=6am-6pm Wed=6am-6pm Thu=6am-6pm Fri=6am-5pm Off=Sat Off=Sun Off=Holidays |
Run = 7am - 6pm, Mon Run = 7am - 6pm, Tue Run = 7am - 6pm, Wed Run = 7am - 6pm, Thu Run = 7am - 6pm, Fri Off = Sat Off = Sun Off = Holidays |
| FCU1 | Ground and 1st Floor - must run with AHU1 | Yes | Yes | Mixed Air HVAC System | Academic Year Schedule same as AH-1 |
Academic Year Schedule same as AH-1 |
| AHU2 | Auditorium | Yes | Yes | Mixed Air HVAC System | Room Scheduling | Room Scheduling |
| AHU3 | Ground and 3rd Floor, Room 30A, 30E, 31, 31A - East | Yes | Yes | Mixed Air HVAC System | Run = 7am-10pm, Mon Run = 7am-10pm, Tue Run = 7am-10pm, Wed Run = 7am-10pm, Thu Run = 7am-10pm, Fri Run = 10am -4pm, Sat Run = 10am -4pm, Sun Off = Holidays |
Run = 7am-6pm, Mon Run = 7am-6pm, Tue Run = 7am-9pm, Wed Run = 7am-6pm, Thu Run = 7am-6pm, Fri Run = 10am -4pm, Sat Run = 10am -4pm, Sun Off = Holidays |
| AHU4 | Tea Room | Yes | Yes | Mixed Air HVAC System | Run = 24/7 | Run = 24/7 |
| AHU7 | 2nd Floor - West | Yes | Yes | Mixed Air HVAC System | Run = 24/7 | Run = 24/7 |
| UV2 | Room 221 West Lab | Yes | Yes | Mixed Air HVAC System | Run = 24/7 |
Run = 24/7 |
| UV3 | Room 221 East Lab | Yes | Yes | Mixed Air HVAC System | Run = 24/7 |
Run = 24/7 |
| LIT1 | EAST CORRIDOR , GROUND FLOOR, INTERIOR LIGHTING. | Lighting Control | Run = 24/7 | Run = 24/7 |
| Unit | Service Area | Control Strategies |
|---|---|---|
| AHU1 | Ground, 1st, 2nd, 3rd Floor - West | Local thermostat set at 70 degrees in winter and 76 degrees in summer. During "off" periods there will be an 80-degree upper limt and a 65-degree lower limit. |
| FCU1 | Ground and 1st Floor - must run with AHU1 | Schedule follows schedule of AHU1. Local thermostat set at 70 degrees in winter and 76 degrees in summer. During "off" periods there will be an 80-degree upper limt and a 65-degree lower limit. |
| AHU2 | Auditorium | Local thermostat set at 70 degrees in winter and 76 degrees in summer. During "off" periods there will be an 80-degree upper limt and a 65-degree lower limit. |
| AHU3 | Ground and 3rd Floor, Room 30A, 30E, 31, 31A - East | Local thermostat set at 70 degrees in winter and 76 degrees in summer. During "off" periods there will be an 80-degree upper limt and a 65-degree lower limit. |
| AHU4 | Tea Room | Occupant Controlled |
| AHU7 | 2nd Floor - West | Local thermostat set at 70 degrees in winter and 72 degrees in summer. During "off" periods there will be an 80-degree upper limt and a 65-degree lower limit. |
| UV2 | Room 221 West Lab | Local thermostat set at 70 degrees in winter and 76 degrees in summer. During "off" periods there will be an 80-degree upper limt and a 65-degree lower limit. |
| UV3 | Room 221 East Lab | Local thermostat set at 70 degrees in winter and 76 degrees in summer. During "off" periods there will be an 80-degree upper limt and a 65-degree lower limit. |
| LIT1 | EAST CORRIDOR , GROUND FLOOR, INTERIOR LIGHTING. | Ground floor, East Corridor, interior lights |
| Date | Ex | Energy Conservation Action(s) Taken |
|---|---|---|
| 3/27/2006 | COMPLETED SPRING 06 BUILDING ENERGY CONSERVATION SETTINGS | |
| 7/14/2006 | Completed MEA Holiday schedules and reviewed hours of operation | |
| 8/24/2006 | 5 | AHU7 = Room 207 = complete |
| 10/31/2006 | Reviewed for winter settings | |
| 5/10/2007 | Reviewed for summer settings. | |
| 5/22/2008 | Reviewed for summer schedule. | |
| 9/22/2008 | Reviewed for winter schedule. | |
| 5/13/2009 | Reviewed for summer schedule. | |
| 10/9/2009 | Reviewed for winter schedule. |