| # | Exemptions | Summer | Winter |
|---|---|---|---|
| 1 | (AHU3) Court Areas - 24/7 in summer only | 24/7 | 7am-8pm |
| 2 | (AHU3) Rm 201 & 211 7am to 10 pm Weekdays (no exemption form from department??) | 72 Deg | 72 Deg |
| Unit | Service Area | Cool | Heat | System Type | Summer Hours | Winter Hours |
|---|---|---|---|---|---|---|
| AHU1 | Old Bldg - West | Yes | Yes | Mixed Air HVAC System | Room Scheduling | Room Scheduling |
| AHU2 | Old Bldg - East | Yes | Yes | Mixed Air HVAC System | Room Scheduling | Room Scheduling |
| AHU3 | Court Areas, Computer Room | Yes | Yes | Mixed Air HVAC System | 24/7 | Run = 7am-8pm, Mon Run = 7am-8pm, Tue Run = 7am-8pm, Wed Run = 7am-8pm, Thu Run = 7am-8pm, Fri Off = Sat Off = Sun Off = Holidays |
| AHU4 | Planetarium | Yes | DX Unit | Occupant Controlled | Occupant Controlled | |
| AHU7 | Addition West | Supply Fan | 24/7 | 24/7 | ||
| AHU8 | Addition East | Supply Fan | 24/7 | 24/7 | ||
| AHU11 | Lecture Hall 5 | Yes | Yes | Mixed Air HVAC System | Room Scheduling | Room Scheduling |
| AHU12 | Lecture Hall 3 | Yes | Yes | Mixed Air HVAC System | Room Scheduling | Room Scheduling |
| Unit | Service Area | Control Strategies |
|---|---|---|
| AHU1 | Old Bldg - West | local thermostats @ 70 degrees in winter, 76 degrees in summer. 83 degrees upper limit summer, 63 degrees lower limit winter |
| AHU2 | Old Bldg - East | local thermostats @ 70 degrees in winter, 76 degrees in summer. 83 degrees upper limit summer, 63 degrees lower limit winter |
| AHU3 | Court Areas, Computer Room | local thermostats @ 70 degrees in winter, 76 degrees in summer. 83 degrees upper limit summer, 63 degrees lower limit winter |
| AHU4 | Planetarium | local thermostats @ 70 degrees in winter, 76 degrees in summer. |
| AHU11 | Lecture Hall 5 | local thermostats @ 70 degrees in winter, 76 degrees in summer. 83degrees upper limit summer, 63 degrees lower limit winter |
| AHU12 | Lecture Hall 3 | local thermostats @ 70 degrees in winter, 76 degrees in summer. 83degrees upper limit summer, 63 degrees lower limit winter |
| Date | Ex | Energy Conservation Action(s) Taken |
|---|---|---|
| 4/13/2006 | COMPLETED SPRING 06 BUILDING ENERGY CONSERVATION SETTINGS | |
| 4/21/2006 | 1 | AHU3 = complete |
| 7/17/2006 | Completed MEA Holiday schedules and reviewed hours of operation | |
| 10/31/2006 | Reviewed for winter schedule | |
| 5/11/2007 | Reviewed for summer schedule | |
| 11/2/2007 | Reviewed for winter schedule | |
| 11/2/2007 | 2 | AHU3 = complete |
| 5/22/2008 | Reviewed for summer schedule. | |
| 9/22/2008 | Reviewed for winter schedule. | |
| 5/14/2009 | Reviewed for summer schedule. | |
| 10/9/2009 | Reviewed for winter schedule |