Request for Services Form

View a Service Request

SR466444 has created Work Order WH45160.

Date 6/9/2020
Requestor SHRIVER, MATTHEW LAWRENCE
Location POWER 
Description TG3 - AT NEXT OVERHAUL NEED TO DO SOME OIL MITIGATION EFFORTS 
Details 1. IN THE BOX WHERE THE ARRESTORS AND GENERATOR LEADS ARE THE BARRIER BOARDS NEED TO BE REMOVED AND CLEANED IN SOLVENT TANKS. 2. WHEN THE BARRIER BOARDS ARE INSTALLED, GORTEX AT LEAST 1/2" WIDE ON BARRIERS, THEN THEY NEED TO BE SILICONED AROUND THERE THE BUSS PENETRATES AND THERE THE MEET IN THE MIDDLE. ALSO NEED TO SILICONE THE UNDERSIDE OF THE WASHERS ON BOLTS AND AROUND THE ENDGE OF THE BARRIER BOARDS.
Status ACTIVE
Contact Matt Shriver
(515) 509-4693