SR473252 has created Work Order WJ14852.

Date 10/26/2020
Requestor WOODS, GORDON J
Location POWER 
Description CW - THERE APPPEARS TO BE A LEAK FROM THE COOLING TOWER 
Details WHEN THE BOLLARDS WERE REPLACED THE HOLES WERE FILLED WITH WATER. THAT WATER TESTED POSITIVE FOR TRASAR. THIS IS INDICATION THAT THERE IS A LEAK IN THE TOWER BAYS #2 OR #3 (POSSIBLEY BOTH OR MORE). WE NEED TO INSPECT ALL CONCRETE JOINTS AT THE NEXT TOWER CLEANING OUTAGE. WORK AT RESEALING THE JOINTS.
Status CLOSED
Close Date 6/23/2021 3:17:02 PM
Contact Gordon Woods
(515) 291-1742