SR480954 has created Work Order WJ36894.

Date 4/27/2021
Requestor SHRIVER, MATTHEW LAWRENCE
Location POWER 
Description C3 - CHECK CALIBRATION OF HW LEVEL & RECIRV CONTROL VALVES. 
Details SPECIFICALLY, IT APPEARS THE CONDENSATE RECIRC VALVE IS NOT OPENING. THIS IS OBSERVED WHEN ANOTHER EVENT HAPPENS, THE CONDENSATE HOTWELL LEVEL CONTROL VALVE GOES SHUT AND THE TOTAL CONDENSATE FLOW (AS SEEN BY THE RECIRC FLOW CONTROLLER, AIR EJECTORS HALF DECK) DROPS TO NEAR ZERO. IT IS PRESUMED THAT THIS HAPPENS BECAUSE THE RECIRC VALVE DOES NOT OPEN TO MAINTAIN MINIMUM FLOW. PLEASE CHECK CALIBRATION ON: 1. HOTWELL LEVEL CONTROLLER 2. CONDENSATE MINIMUM FLOW CONTROLLER 3. HOTWELL LEVEL CONTROL VALVE 4. CONDENSATE RECIRC CONTROL VALVE.
Status ACTIVE