Request for Services Form

View a Service Request

SR480958 has created Work Order WJ36898.

Date 4/27/2021
Requestor SHRIVER, MATTHEW LAWRENCE
Location POWER 
Description C3 - CHECK CALIBRATION OF TURBINE OIL TEMPERATURE SW AND XMTR 
Details THE TURBINE HIGH OIL TEMP TRIP (THOT) SW TRIPPED THE CHILLER ON 4/26, HOWEVER THE TRANSMITTER FOR OIL TEMPERATURE (ALBEIT IN A SLIGHTLY DIFFERENT LOCATION) NEVER REGISTERED A TEMP ABOVE 120F. THE THOT SWITCH IS NOT SUPPOSED TO TRIP UNTIL TEMPERATURE IS ABOVE 150F.
Status ACTIVE
Billing Info
Contact Matt Shriver
(515) 509-4693