Date WO # Location Description Requester Status
4/25/2025 436082 BERGFBC I talked to Ryan Flaherty about checking the Lead/Lag and switch over on failure for Pump 5 and 6 in the Bergstrom Football Building for the Heat Pump Loop. Ken Ely Assigned
9/30/2025 475496 BERGFBC Ground fault on SIG14 attn Duncan Wood Duncan Wood Assigned
7/23/2024 376952 2012B BERGFBC Repair Fire Alarm Deficiencies: Primary and Alternate Elevator recall - did not recall Elevator Shunt Trip - did not shunt trip Smoke Detector M1-89 1st flr corr by mech rm 1021 - no alarm when tested 4098-9714 4 duct detectors in mech rm 1021 - no alarm when tested, not wired/programmed into the system Lyle Bishop Assigned
10/20/2025 480127 2012B BERGFBC Repair Fire Panel inspection deficiencies: "M1-89 not programmed in. Device non functional. 1st FLR Hall by 1021 M1-68,67,66,65 duct detector not programmed in. 1021 4009 1021 5: Battery: Aged out. Replace with 12v 12ah Elevator Shunt Trip, Alternate and Primary Elevator Recall: Did not recall FACP Node 5: Battery: Aged out. Replace with 12v 44ah" ATTN: Duncan Wood Sailesh Gautam Assigned
6/4/2025 447371 1050 BERGFBC Automatic door 1050-1 does not open fully each time the wave to open is used. One time it will open normally and the next it will open about a foot and close. Ken Ely Closed
2/3/2026
7/17/2025 459683 BERGFBC Repair Wet Sprinkler deficiencies: SPRINKLER P.I.V. M1-103 - SPRINKLER MONITOR (Room 1058-1 Tamper Switch): PIV Tamper failed to report to the panel when the PIV was fully exercised. Tamper will need to be troubleshoot and repaired. Retest tamper after repair is completed. ATTN: Tim Kelley Sailesh Gautam Assigned