Work Order Lookup
Date | WO # | Location | Description | Requester | Status |
---|---|---|---|---|---|
9/29/2021 | 118570 | 2103 BLACK | Design - EE - KT - Room 2103 | Kenneth Thelen | Open |
9/29/2021 | 118571 | 1115 BLACK | Design - EE - KT - Room 1115 | Kenneth Thelen |
Closed 8/21/2024
|
2/3/2023 | 258417 | 2079 BLACK | The Air in room 2079 is not working, might be a thermostat issue. Room is very warm. Reference request 238388 for previous issues if needed. | Nate Jensen | On Hold |
5/16/2023 | 280643 | BLACK | call back sat 13 Attn- Jeff Lamb- DPS called about AHU-5 being in alarm | DPS dispatch DPS | Assigned |
8/29/2023 | 304941 | BLACK | CP002649-Utility Engineering-Black Engineering ATS Replacement | Michael Olson | Open |
1/16/2024 | 335958 | 3020 BLACK | Room 3020 Has no heat, the thermostat reads 62 and the register is ice cold. This is the same space that the heat was fixed in last month. Thank you | Shelley Anderson | Assigned |
1/16/2024 | 335964 | 3004A BLACK | Room 3004A - thermostat is reading 62 degrees and is very cold. There is no heat coming out. | Shelley Anderson | Assigned |
1/23/2024 | 336895 | 0095E BLACK | Black, Ground Floor, Room 95 D/E, FCU-2, Supply Fan OFF, | Donald Boyle | Assigned |
2/9/2024 | 342186 | M1054 BLACK | Please pick up Genie GS-2632 scissor lift E009282 from receiving area and deliver to General Services Building loading dock. Must be completed by 2/15/23. | Mark Wyant | Open |
2/19/2024 | 342955 | M1044 BLACK | Hire JCI Fire to repair Duct detectors that had no alarm when tested. Replace Duct Detector 1052-Zone 8-with new addressable version. New addressable shutdown relay, remote test and sampling tube is included. Replace Duct Detector M4052 AHU-002 -Zone 2-with new addressable version. New addressable shutdown relay, remote test and sampling tube is included. | Lyle Bishop | Open |
3/6/2024 | 348323 | BLACK | Panel alarm & UPS alarm | Hillary Anderson | Assigned |
3/20/2024 | 349311 | M0098 BLACK | Replace red lion totalizer with Rosemount remote transmitter | Isaac Maffett |
Closed 8/16/2024
|
3/20/2024 | 349355 | M0098 BLACK | Replacing red lion totalizer with Emerson equipment including: flow tube, fused disconnect, remote transmitter and integral to remote junction box. | Isaac Maffett |
Closed 9/6/2024
|
4/2/2024 | 354738 | 2014 BLACK | The door closure for this office is broken. Please replace with the same type of door closure that was just installed in office 2100 Black. | Sandy Sayer | Assigned |
4/18/2024 | 356215 | GENERAL BLACK | Floor tiles in second floor hallway have come loose and are wet due to a window leak. Please see attached photo. I think the black glue has asbestos. I have contacted EH&S to come over and test. Please find and stop the leak in the window. | Sandy Sayer | Assigned |
4/18/2024 | 356222 | C2039 BLACK | Sampling and disposal of asbestos | Charles Rodgers | Open |
5/8/2024 | 362468 | 2032 BLACK | This office is freezing and the thermostat is making a leaky air sound. Please take a look at the thermostat to see if it is functioning properly | Sandy Sayer |
Closed 9/5/2024
|
5/20/2024 | 363528 | M0105 BLACK | Please assign to Don Gregory. Pull sewage pumps and check for leaks. Check floats for proper operation. | Donald Gregory | Materials-Awaiting |
5/24/2024 | 364069 | 2043 BLACK | It is very cold in the Mechanical Engineering admin office. The thermostat reads 63 degrees in the room currently. Is there any way that we could get this temperature bumped up? Thank you. | Morgan Pierce | Assigned |
5/29/2024 | 364949 | 1117A BLACK | INSTALL 2 480 V DISSCONNECTS ON WALL IN ROOM 1117A | Aaron Jordan | Assigned |
6/3/2024 | 368506 | M0098 BLACK | Replace Valve M098 Hx1 | Eric Zierke |
Closed 8/22/2024
|
6/3/2024 | 368538 | 0083 BLACK | Leak ceiling outside room 0083 in hall way with black exposed mold in ceiling. trash can in hallway | John Howell | Assigned |
6/7/2024 | 368983 | 1116 BLACK | The professor and grad students say it is too cold to work in this lab. Please see if there is anything you can do to make it more comfortable. | Sandy Sayer | Assigned |
6/10/2024 | 369129 | 1059 BLACK | two drop cords towards the center of the room with two sockets each 110V/30A for all. | Sandy Sayer | Assigned |
6/24/2024 | 371448 | 2029 BLACK | Room is very hot. AC does not work. | Baskar Ganapathysubramanian | Open |
6/24/2024 | 371455 | BLACK | Call back fire alarm trouble attn Adam Pepper | Adam Pepper | Assigned |
6/25/2024 | 371546 | M0098 BLACK | Repair steam relief valves. ATTN: Lyle Bishop | Lyle Bishop |
Closed 8/22/2024
|
6/25/2024 | 371594 | BLACK | Black, AHU-2, not making setpoint. SPT = 55 TMP = 68 VLV = 100% Open DIF = 8 degrees, should be 20 degrees | Donald Boyle | Assigned |
6/28/2024 | 372667 | 1072 BLACK | Asbestos sampling of floor tile and mastic in 1072 | Charles Rodgers |
Closed 8/20/2024
|
7/3/2024 | 375350 | 1116 BLACK | The room is 65.5 degrees and the thermostat is set at 78. I think hat spring on the hot water line is stuck again. We tried looking at it but couldn't figure out how to open it up. Can you please just replace that part since it seems to not work at all anymore? | Sandy Sayer |
Closed 8/15/2024
|
7/10/2024 | 375843 | 1117B BLACK | INSTALL 3 PHASE 208V DISSCONNET ANEL ON WALL IN RESEARCH LAB. | Aaron Jordan |
Closed 8/21/2024
|
7/10/2024 | 375852 | 0066 BLACK | Room 66 thermostat is not working. Room is too cold. | Aaron Jordan |
Closed 8/28/2024
|
7/11/2024 | 375961 | 1117 BLACK | install new sign with lab name outside of 1117 Black engineering. we currently have 3 signs on the wall outside the room and would like add 1 new sign with the name of the labs that occupy that space. I have 3 unused signs that can be used | Aaron Jordan | Assigned |
7/12/2024 | 376081 | M0098 BLACK | Insulate Steam pipes near steam tunnel. See Michael Moore for additional details. | Lyle Bishop | Assigned |
7/15/2024 | 376208 | M0098 BLACK | Both main steam valves not functioning. Needs to be replaced. ATTN: Michael Moore. | Lyle Bishop |
Closed 8/27/2024
|
7/17/2024 | 376563 | 2043 BLACK | ME Dept main office is too cold. The occupants are running heaters under there desks and wearing blankets. The Chair of our department has to wear her winter coat when in her office. It is way too cold. Please warm the office up to a more comfortable temperature | Sandy Sayer |
Closed 8/15/2024
|
7/25/2024 | 377188 | 1117 BLACK | We are looking to have a industrial sink moved. We are trying to redesign a layout and need to know if it is possible. We would like to figure out if the sink can be moved in the next week or two to determine a room layout. | Aaron Jordan | Assigned |
7/26/2024 | 377302 | BLACK | Install hour meter and counter on sprinkler air compressor ATTN Nick Smith | Nicholas Smith | Assigned |
8/1/2024 | 378533 | GENERAL BLACK | Pump in basement is leaking a lot of water. | Steven Nelson |
Closed 8/27/2024
|
8/5/2024 | 381317 | 1117 BLACK | move electrical disconnect for cnc machine and check old disconnect for use/compatibility with new machine. | Aaron Jordan | Assigned |
8/7/2024 | 381942 | BLACK | black AHU-4 not making set point DIF = 13, should be 23 degrees | Donald Boyle | Assigned |
8/9/2024 | 382535 | GENERAL BLACK | Please relocate the thermostats in rooms 2019A and 2019B. I'm not sure if the one in 2019A is a thermostat or not but can we have it moved next to the door? Please move the thermostat in 2019B farther behind the door or between the doorway and pillar. I will be available to show you what we would like done if you wat to call my office number 294-2656 | Sandy Sayer | Assigned |
8/12/2024 | 382762 | 1091 BLACK | Condensate leaking onto ballast in room. | Alex Sobotka |
Closed 8/27/2024
|
8/14/2024 | 383045 | 1091 BLACK | Please install 3 compressed air drops in 1091 Black. one on west wall, one on east wall and one on north wall. There is a compressed air line running east/west in the center of the room we would like you to tap off of. There are already three capped drops on that line you could possibly use. | Sandy Sayer | Assigned |
8/19/2024 | 383469 | M0098 BLACK | CDP4 LEAKING at motor | Michael Bond |
Closed 9/4/2024
|
8/20/2024 | 383750 | 2073A BLACK | Room is too hot. | Derek Dickson | Open |
8/22/2024 | 383964 | C1040 BLACK | We keep getting forced entry alarms for this door even though the door is closed. The alarm comes in around 20 times. | William Brown |
Closed 9/1/2024
|
8/26/2024 | 384267 | R1111 BLACK | The stall against the wall leaks alot of water when flushed | John Holt lll |
Closed 8/27/2024
|
8/26/2024 | 384483 | 1104A BLACK | Abate small 2'x2' section of floor.. We removed a base cabinet to make room for a piece of equipment and there were floor tiles with mastic in the glue underneath. | Sandy Sayer | Assigned |
8/26/2024 | 384529 | 2045A BLACK | The heat is on in my office and it is uncomfortably warm. Please turn off the heat. Work tags to attach: PG103402 | Brianna Enearl | Assigned |
8/27/2024 | 385201 | R1111 BLACK | The urinal on the far left when you walk in isn't working. It doesn't flush at all, might be the sensor or motor | John Holt lll |
Closed 8/27/2024
|
8/27/2024 | 385302 | 1116 BLACK | Black, Lab 1116, Reheat leaking by SPT = 68 TMP = 92 VLV = Closed | Donald Boyle |
Closed 9/5/2024
|
8/27/2024 | 385374 | BLACK | Unlock Doors on 9/02/2024 from 7:00am-12:00 Midnight | Aaron Jordan |
Canceled 9/2/2024
|
8/29/2024 | 385638 | 1104A BLACK | Item 1 needs: 2 - 480 V, 30 A, 3 phase outlets & fused disconnect 1 - 208 V, 20 A, 1 phase outlet ( 6-20R ) Item 2 needs: 1 - 208 V, 50 A, 1 phase outlet ( 10-50R ) Estimate cost before proceeding. Work tags to attach: GR-028404-00001 | James Dautremont | Assigned |
8/29/2024 | 385664 | 1104A BLACK | Please change the ballasts in the light fixtures to support LED bulbs. We need this research lab to be well lit. | Sandy Sayer | Assigned |
8/30/2024 | 385800 | 1026 BLACK | light out in the room | Jonathan Smith | Assigned |
9/4/2024 | 389154 | 1091 BLACK | We removed a blue gas cylinder cabinet from this room and there is a small 2' x 2' section of floor tile that needs removed. EH&S found no asbestos in the mastic in this room. | Sandy Sayer | Assigned |
9/5/2024 | 389220 | R1044 BLACK | Both lights above the urinals are out completely | John Holt lll | Assigned |
9/5/2024 | 389272 | R1044 BLACK | There is a light out in R1044. | Aaron Jordan | Assigned |
9/6/2024 | 389425 | M0098 BLACK | Replace pre action sprinkler valve | Justin Abbott | Assigned |