Date WO # Location Description Requester Status
11/1/2023 318674 4115 BRL Eyewash ESE2 has very little water flow. Korinna Radke Materials-Awaiting
1/8/2024 335184 3129 BRL Fume Hood E038223 alarms when the sash is shut. Airflow passes certification testing, but does not adjust when sash is shut and causes the hood to alarm. Nicole Brandon Assigned
2/27/2024 344403 5100 BRL Sight glass leaking on ETK 3 Michael Bond Assigned
3/5/2024 348178 3120 BRL Attention Dustin Limoges Metasys device BRL.52A004VM.3120.Corridor is going Offline & Online, had to disabled because it is filling up the Event Viewer. Bruce Norris Assigned
3/27/2024 350823 2137 BRL From Inspection 9794 - Fume hood tested fine but it is a walk-in hood and the front sash does not go all the way down to the floor and is slightly damaged. Brandon Thompson Materials-Awaiting
6/17/2024 369614 BRL Air handler not functioning properly. Ryan Smith Open
7/23/2024 376935 0135 BRL Replace 2 cash valves FR800 series right after our condensate sensors (S100101 & S100208) Condensate system has a bypass. They are both 2" lines. If 6647.7900 is the inventory item, we have one in stock. The bottom cash valve is the higher priority to replace. Please target that one. Isaac Maffett Closed
4/8/2025
8/27/2024 385229 BRL BRL, CW2, Chilled Beam Differential Low Alarm Chilled Beam Supply Temp High alarm Donald Boyle Assigned
9/19/2024 390576 0135 BRL HWP5 - Check out for motor/VFD issues? Mark Schmitz Assigned
10/7/2024 396317 0135 BRL Low temp heating return line leaking in BRL room 0135-1 Jeremy Forristall Assigned
10/16/2024 397024 0135 BRL air compressor AC1 has red light on tried to reset but cant read screen to see what is wrong. John Moore On Hold
11/11/2024 403918 0135 BRL Delta to perform major PM $1847.80 Ryan Rieke Canceled
4/3/2025
11/11/2024 403921 0135 BRL Delta to perform major PM $4578.41 Ryan Rieke Canceled
4/3/2025
11/11/2024 403923 0135 BRL Delta to perform major PM $2496.46 Ryan Rieke Canceled
4/3/2025
12/12/2024 410700 4115 BRL Fume hood in this room keeps going into alarm. Korinna Radke Assigned
1/7/2025 414974 0150 BRL Replace pumps Donald Gregory Materials-Awaiting
1/23/2025 416547 0135 BRL Replace control wiring for HWP 6 VFD. Jeremy Forristall Assigned
2/24/2025 423012 4137 BRL I hope this email finds you and your loved ones well. I am emailing to get your assistance with putting an FP&M request in my stead. We are planning to buy a -80C freezer, but with space in the lab being limited it is difficult to find a red outlet (backup power outlet/standby?) to plug the freezer into. I have attached a picture of what the outlet looks like, but we only need 1 installed. Also attached is the information for the breaker all the red outlets appear to be attached to if this helps. 4137 S. WALL is where the freezer circuit would go, attached picture of location, which we can move the shelving once we schedule something. A similar freezer model, as we are still gathering quotes, requires NEMA 5-20 with an electrical requirement of 115V, 60Hz. There are two red outlets in this area on breaker 13 and breakers 26&28 in breaker box 4-SRP-4137-1. For now, please use PG111200 Shao - DISC - ENGR, once we have a better idea of what the work will cost we can discuss worktags again if that's ok with you. Please let me know if you have any questions or concerns. Thank you and take care, Daniel Bun Amanda Kramer Closed
4/9/2025
2/26/2025 423143 2120 BRL Slow leak has started from a heating water supply pipe right outside door to 2120. Not sure if anything can be done about it. Ty. Dwight Thompson Closed
4/3/2025
2/28/2025 424034 1140N BRL Call back fire alarm trouble attn Adam Pepper Adam Pepper Assigned
3/11/2025 428307 3129 BRL From Inspection 13258 ; fume hood E038221 fume hood controller alarm is sounding (reading low airflow) every time sash is opened, even when airflow test passed at a good rate. Repair the controller/monitor so it does not alarm every time sash is opened. Katelyn Thompson Assigned
3/14/2025 428652 3129 BRL An instrument is 250V, and will need transformer or other solution, as only 120 is available at the hood where this instrument is housed. Additional location information: Fume hood in SW part of 3129 lab. Work tags to attach: SG2702216 Ryan Smith Closed
4/16/2025
3/18/2025 428849 1125 BRL Fume Hood E038184 alarms when the sash is closed. monitor may need to be re-calibrated or set-points changed. Nicole Brandon Assigned
3/27/2025 430425 1151 BRL Light out in the stairwell landing between the basement and first floor. Dwight Thompson Assigned
4/1/2025 430734 3130B BRL Ceiling light is out over inside cubicle Dwight Thompson Closed
4/24/2025
4/2/2025 434118 3129 BRL Fume hood E038215 has liquid coming out of the vacuum port. Michelle Thompson Assigned
4/3/2025 434248 4104 BRL Left mirror light is out Dwight Thompson Closed
4/24/2025
4/3/2025 434291 1125 BRL From Inspection 13440 ; fume hood E038184 alarms every time the sash is closed and will not stop unless opened up again. Needs repaired so they can shut the sash properly without alarming. Katelyn Thompson Canceled
4/3/2025
4/4/2025 434401 1135 BRL SE High Bay LED light out Additional location information: SE corner Jordan Funkhouser Open
4/4/2025 434403 1135 BRL 250V 1P 30A outlet has no power. New equipment needs to go into this corner and use this outlet. Breaker up on mezzo was off but once switched still not getting power at outlet. Additional location information: NE corner Jordan Funkhouser Closed
4/24/2025
4/9/2025 434761 BRL BLR building is having shortage of compressed air. Sensitive instruments are unable to turn on/perform analysis. BRL floor 3 Additional location information: BRL 3rd floor. BLR is located opposite to Student Innovation Center Work tags to attach: PG114186 Chumki Banik Closed
4/15/2025
4/11/2025 434934 0135 BRL Hire Delta Industries to perform Major PMs on Air Compressor Unit 1. Lyle Bishop Open
4/11/2025 434936 0135 BRL Hire Delta Industries to perform Major PMs on Air Compressor Unit 2. Lyle Bishop Open
4/11/2025 434974 0135 BRL Hire Delta Industries to perform Major PMs on Desiccant Air Dryer 1. Lyle Bishop Open
4/11/2025 434975 0135 BRL Hire Delta Industries to perform Major PMs on Vacuum Pump 1 & 2. Lyle Bishop Open
4/16/2025 435243 1100 BRL Some wainscoting panels have come loose under the fire alarm switch and a piece to the left of the elevator. Dwight Thompson Closed
4/17/2025
4/18/2025 435494 1100 BRL Thank you for fixing one section of wainscoting that was loose, but the original request has another section that needs attention. It's just left of the door to the stairs, below the fire alarm. Dwight Thompson Closed
4/30/2025
4/21/2025 435603 3115 BRL Low Air Pressure in lab Chumki Banik Closed
4/30/2025
4/21/2025 435662 BRL Two individuals were stuck on 3rd floor in elevator 2. Dispatch called Schumacher elevator tech. Tammy Barker Assigned
4/23/2025 435832 BRL Restart AHUs. Christine Crockett Assigned
4/23/2025 435851 0135 BRL DIU1- tank second from Left has a red light Michael Bond Assigned
4/29/2025 436952 4104 BRL Urinal is draining too slow. Overflows onto the floor. Can't keep up with flushing more than once. Dwight Thompson Assigned