Work Order Lookup
| Date | WO # | Location | Description | Requester | Status |
|---|---|---|---|---|---|
| 4/25/2022 | 183302 | DESIGN | Investigate and Address Grade issues on East Side of the Building. Having issues with water seeping into Restroom R0075 causing mold issues. | Christopher Saunders | Open |
| 4/18/2024 | 356196 | DESIGN | Sale of TreeCycle Wood to the College of Design. All the wood should be priced to the students at $4 per board foot. | Rhonda Martin | Open |
| 8/12/2024 | 382664 | 0038A DESIGN | The exhaust system for the kiln room is squealing on start up, this is large exhaust stack(fan) on the exterior of the building. Can we get someone out to take a look at it? | Jeremy Thurlby | Assigned |
| 9/19/2024 | 390572 | 0003A DESIGN | The pneumatic valves that open the exhaust vent and open the fresh air intake are not working. This is part of the system for the exhaust stack for the kiln room. | Jeremy Thurlby | Assigned |
| 10/24/2024 | 397716 | R0225 DESIGN | Graffiti on wall | Leo Pierce | Assigned |
| 11/1/2024 | 399226 | 0240 DESIGN | there are 2 banks of lights that are out in the room. This should be a priority as it is used to teach drawing classes. Thanks. | Michael Miller | Assigned |
| 1/31/2025 | 417915 | 0311A DESIGN | The faculty who teaches in this room is reporting low water pressure. They use a power washer to clean silkscreens and the water is not keeping up. Can we get someone out to take a look? | Jeremy Thurlby |
Closed 1/21/2026
|
| 2/28/2025 | 424058 | C0302 DESIGN | The green and red indicator lights are out on both elevators as well as the elevator call buttons. | Craig Strother | Assigned |
| 3/20/2025 | 428985 | C0003 DESIGN | Elevator 1 by CO003 is jumping and needs to be checked. Any questions call Dan at 515-686-0984. Due to the vintage of the controller, there is no fault log. Technician checked the door locks and could not replicate the issue. He checked the overall operation and returned the car to service. 1 Hour X $241.00 = $241.00 | Daniel Isaacson | Assigned |
| 3/26/2025 | 429704 | E0004 DESIGN | The northwest elevator is having issues. It has been reported multiple times that after you get in and it just doesn't do anything and then after you open the doors and close them again it works. Sounded like there was still movement with the doors on the ground floor the first time they closed then it closed properly the second time. Can we get the tech out to take a look? | Jeremy Thurlby | Open |
| 4/25/2025 | 436067 | M0068A DESIGN | Hire HM Cragg to perform 2 Hour Load Bank Tests on Emergency Generators. | Anthony Gervais | Open |
| 5/13/2025 | 441943 | 0434 DESIGN | There are lights out on the ceiling. Any questions call Dan at 515-686-0984. | Daniel Isaacson | Assigned |
| 5/20/2025 | 442615 | GENERAL DESIGN | water and smoke detector on 5th floor Southside | Dustin Limoges | On Hold |
| 6/26/2025 | 451424 | 0001AA DESIGN | Attn. Brock polar, I-vac battery light flashes after 20min. Of use and machine stops working. Eo24906 machine no. | Craig Strother | Materials-Awaiting |
| 6/30/2025 | 453347 | 0077 DESIGN | The air exchanger in room 77 is not putting out any air. The air exchanger in room 66 is hardly putting out any air. Both rooms are warm. Any questions call Dan at 515-686-0984. | Daniel Isaacson | Assigned |
| 7/23/2025 | 460411 | GENERAL DESIGN | Assistance from John Breon | Mark Huss | Open |
| 8/8/2025 | 465183 | M0017 DESIGN | College of Design mechanical room M0017, in the air filter bay is a condensate tank/pump system. RTK4 has a leak at the pump/motor flange that will need replaced to reseal. The RH pump motor appears to be leaking the greatest mount, but the LH may also need a new flange gasket as well. See attached file for details. | Dale Headrick |
Closed 1/22/2026
|
| 8/11/2025 | 465317 | DESIGN | Barron Equipment to replace gas shocks. | Anthony Gervais | Open |
| 8/14/2025 | 465951 | 0034A DESIGN | Water leak (condensation?) from overhead pipes running to overhead air handling unit. Can see water dripping overhead from insulation. Leak is directly above the woodworking planer and water damage can be see on infeed table and enclosure. Additional location information: above planer | Peter Scheidt | Assigned |
| 8/25/2025 | 466933 | 0534 DESIGN | No lights turn on with switches, they just blink, probably a power pack problem | Craig Strother |
Closed 2/9/2026
|
| 8/26/2025 | 467235 | 0307 DESIGN | Teacher standing desk does not function. It has power, essentially "clicks" but does not raise or lower. Additional location information: Front of classroom | Paul Bruski | Assigned |
| 9/23/2025 | 474609 | DESIGN | The elevators are not currently working right now they're both stuck on the bottom floor. | Michael Valline | Open |
| 9/23/2025 | 474624 | 0066 DESIGN | We have a leak in this room when it rains, not sure if its coming from the roof, window or the vent for the FCU. Can we get someone out to check it out? | Jeremy Thurlby | Assigned |
| 9/30/2025 | 475562 | 0001AA DESIGN | Vacuum cleaner E024584. The small connector hose from head to the upright part of the vacuum has crack in it and needs replacement. | Daniel Isaacson | Materials-Awaiting |
| 10/1/2025 | 475647 | R0425 DESIGN | Rooms R425, R475, R275, R225, 54A, and 54B are very warm and thermostat does not work. Any questions call Dan 515-686-0984. | Daniel Isaacson | Assigned |
| 10/9/2025 | 479443 | R0075 DESIGN | Rooms 54B and R0075 are warm. Thermostats must not be working. Any questions call Dan at 515-686-0984. | Daniel Isaacson | Assigned |
| 10/13/2025 | 479666 | E0004 DESIGN | This elevator is stuck with the doors open on ground floor. Can we get the tech out to fix it? | Jeremy Thurlby | Assigned |
| 10/14/2025 | 479717 | DESIGN | The elevator is stuck on the ground floor with the doors open and is not responding. North elevator # 1529 | Jessica Hansen-Moench | Assigned |
| 10/16/2025 | 479923 | DESIGN | North elevator # 1529 is stuck on the ground floor with the doors closed and not responding. | Jeremy Thurlby | Assigned |
| 10/27/2025 | 480978 | M0124 DESIGN | Attention Brock Polar,: vacuum sweeper 63186 needs a new hose wand ( old one broken and taped up) and the handle needs a new screw to hold it on (handle pulls loose while vacuuming) | Craig Strother | Materials-Awaiting |
| 11/5/2025 | 485533 | 0111 DESIGN | There is a broken or missing roller shade in this room. Can we get a carpenter out to take a look? | Jeremy Thurlby | Assigned |
| 11/5/2025 | 485564 | 0101 DESIGN | Bottom of auditorium above lower entrance door light out above thanks Mike | Michael Valline | Assigned |
| 11/13/2025 | 486171 | 0001AA DESIGN | Pro Team vacuum E024584 shut of today by itself and will not run. Orange light was on, but could not find anything plugged. Any questions call Dan at 515-686-0984. | Daniel Isaacson | Assigned |
| 11/19/2025 | 486579 | 0526 DESIGN | We are having very bad luck with a number of faculty classroom desks over the last 1-3 years (all same model and installation date). We have two in room 526 that are non-functional standing desks. Both do not respond to the controls, have been unplugged and replugged in to no avail. I hope they are under warranty. Please use PG102524 | Paul Bruski | Assigned |
| 11/20/2025 | 486661 | 0066 DESIGN | The heat setting is on the highest setting. The room is about 65 degrees. That is going to be a problem when it gets colder. Any questions call Dan at 515-686-0984. | Daniel Isaacson | Assigned |
| 12/1/2025 | 487196 | 0044 DESIGN | Rooms 44 and 54A are cold. Any questions call Dan 515-686-0984. | Daniel Isaacson |
Closed 2/3/2026
|
| 12/1/2025 | 487279 | 0101C DESIGN | EML8 emergency light assembly does not function/light when tested. This is a non-battery unit and is direct wired only. This unit will need to be replaced with a new unit that has a battery back-up if possible. This w/o will need to be assigned to an electrician. See attached Word file for additional details. | Dale Headrick | Assigned |
| 12/1/2025 | 487280 | 0102 DESIGN | EML4 emergency light assembly does not function/light when tested. This is a non-battery unit and is direct wired only. This unit will need to be replaced with a new unit that has a battery back-up if possible. This w/o will need to be assigned to an electrician. See attached Word file for additional details. | Dale Headrick | Assigned |
| 12/2/2025 | 490845 | C0085 DESIGN | At the end of the hallway across from room 58, dirty water is dripping down from above. Any questions call Dan at 515-686-0984. | Daniel Isaacson |
Closed 1/20/2026
|
| 12/3/2025 | 491289 | R0575 DESIGN | The women's restrooms seems to be cold, no heat from the hot water pipes in the register | Craig Strother | Assigned |
| 12/19/2025 | 493232 | 0181 DESIGN | Request to clean/mop (not wax) gallery 181/181A floors. Work completed | Rachel Royster |
Closed 1/15/2026
|
| 12/30/2025 | 493785 | 0062 DESIGN | Water had come in through the ceiling. A ceiling tile was saturated and broke off and collapsed to the floor.Other tiles in the ceiling have water stains also. This happened over by the windows. Any questions call Dan at 515-686-0984. | Daniel Isaacson |
Closed 1/16/2026
|
| 12/31/2025 | 493837 | DESIGN | When elevator starts up it jumps then goes, then slows way down Reported by Dan Erickson 686-0984 | Barbara Schumacher | Open |
| 1/5/2026 | 496523 | 0054 DESIGN | The lock mechanism on the door is seized up. The door cannot be opened from the inside or outside from the hallway. Any questions call Dan at 515-686-0984. | Daniel Isaacson |
Closed 1/15/2026
|
| 1/5/2026 | 496696 | 0346 DESIGN | Not all lights are working in area thanks Mike | Michael Valline | Assigned |
| 1/8/2026 | 496936 | 0562 DESIGN | 2 banks of lights out in room 562 | Craig Strother |
Closed 1/15/2026
|
| 1/8/2026 | 496937 | 0507 DESIGN | 1 bank of lights out in 507 and 1 bank of lights out in room 511 | Craig Strother |
Closed 1/15/2026
|
| 1/8/2026 | 496964 | 0530 DESIGN | Window shade will not go up or down | Craig Strother |
Closed 2/3/2026
|
| 1/9/2026 | 497054 | DESIGN | Design test header needs attion.Leaking inside the building and needs new valves outside. please get quote and PO. ATT. Tim Kelley | Timothy Kelley | Assigned |
| 1/9/2026 | 497062 | 0116 DESIGN | The carpet transition strip in the doorway has come loose and is catching on the door when it closes. Can we get a carpenter out to take a look? | Jeremy Thurlby | Assigned |
| 1/9/2026 | 497063 | 0111 DESIGN | There is a window blind that is not staying up and it appears to be a broken clutch. Can we get a carpenter out to take a look? | Jeremy Thurlby |
Closed 1/14/2026
|
| 1/9/2026 | 497106 | 0134 DESIGN | Two people have reported that their keys do not work in the lock. | Michael Miller |
Closed 1/15/2026
|
| 1/13/2026 | 497280 | 0440 DESIGN | The curtain on the far right window will not stay up. Any questions call Dan at 515-686-0984. | Daniel Isaacson |
Closed 2/4/2026
|
| 1/13/2026 | 497281 | 0452 DESIGN | There are lights out in the ceiling. Any questions call Dan at 515-686-0984. | Daniel Isaacson |
Closed 1/15/2026
|
| 1/16/2026 | 497722 | 0352 DESIGN | 3 blinds won't stay up marked with blue tape | Michael Valline |
Closed 2/4/2026
|
| 1/16/2026 | 497723 | 0387 DESIGN | Thermostat is hissing | Michael Valline |
Closed 2/3/2026
|
| 1/20/2026 | 497843 | 0291 DESIGN | This office door is having issues it seems with the closer or hinges. It is hard to close right before it latches. Can we get someone out to take a look? | Jeremy Thurlby |
Closed 1/28/2026
|
| 1/23/2026 | 498202 | 0054AA DESIGN | The FCU (UVU16) in this room is not operating. The room is cold and sounds like the motor is stuck or trying to start(low hum coming from the unit). Can we get a tech out to take a look? | Jeremy Thurlby | Assigned |
| 1/23/2026 | 498209 | 0044 DESIGN | This studio is cold, we have opened the back room to 44B to provide some heat. Can we get a tech out to take a look? | Jeremy Thurlby | Assigned |
| 1/23/2026 | 498274 | R0075 DESIGN | The soap dispenser on the mirror has one side of the cover that is broke and needs replacing. Any questions call Dan at 515-686-0984. | Daniel Isaacson |
Closed 2/2/2026
|
| 1/26/2026 | 498522 | 0116 DESIGN | The faucet in this room is dripping, can we get someone out to take a look at it? | Jeremy Thurlby |
Closed 2/2/2026
|
| 1/27/2026 | 498780 | 0592 DESIGN | Thermostat doesn't work, room is at 66 degrees | Craig Strother | Assigned |
| 1/28/2026 | 498990 | 0578 DESIGN | It has been very cold in our office (578). I have tried to adjust the thermostat, but it doesn't seem to work. Can we get a tech out to take a look? | Jeremy Thurlby | Assigned |
| 1/29/2026 | 499065 | 0054A DESIGN | The temp is this studio is cold, it appears the thermostat is broken/out of adjustment. Can we get a tech out to take a look? | Jeremy Thurlby | Assigned |
| 2/2/2026 | 502245 | 0034 DESIGN | Air handler in room 0034 makes loud noise when fan starts. | Peter Scheidt | Assigned |
| 2/3/2026 | 502379 | R0575 DESIGN | One of the stalls in the women’s bathroom on the 5th floor has a broken lock. Can we get a carpenter out to take a look? | Jeremy Thurlby |
Closed 2/5/2026
|
| 2/3/2026 | 502423 | 0011 DESIGN | There is a large sink to the left of the room. The hot water side f the faucet has a small leak when shut off. Can we get someone out to take? | Jeremy Thurlby | Assigned |
| 2/4/2026 | 502605 | 0160 DESIGN | Carpet cleaned in this office Work tags to attach: PG101717 | Melissa Barnes | Assigned |
| 2/9/2026 | 502867 | 0386 DESIGN | Michael Smith | Open |
Loading data, please wait...