| Date | WO # | Location | Description | Requester | Status |
|---|---|---|---|---|---|
| 7/22/2021 | 98365 | 1598 FOOD SC | ReplaceVFD for Exhaust fan 10 ( North West corner of room) | Michael Hanson | Materials-Awaiting |
| 6/19/2023 | 287573 | 1598 FOOD SC | South wall center of the room has much of the wall space with peeling paint/calcium build up. This is a food grade laboratory and needs to be scraped clean and re painted. Coordination of work to be done is important as to not overlap with lab work which can be delayed as needed. Thanks! | Jordan Funkhouser | On Hold |
| 7/12/2023 | 293946 | M2043 FOOD SC | Return fan for Air Handler 6 - AHU6 - VFD not working | Joe Flaherty | Assigned |
| 8/16/2023 | 302459 | GENERAL FOOD SC | Food Science Courtyard windows need painted. These are located above the upper terrace on the north side. It was pointed out to me that these windows are in need of paint. | Justin Abbott | Assigned |
| 3/25/2024 | 349901 | 2384 FOOD SC | In Food Sci 2384 (Kemin teaching Lab) there is a spot on the ceiling in what is (I believe) the SW corner above the fume hoods where the paint is bubbling and peeling. We don''t know when the spot appears but has been there at least a couple of weeks. It doesn''t appear wet; we don''t know if it is from previous leaking or the paint is peeling because of fume hood use. Pictures attached. Medium urgency | Deanna Powell | Assigned |
| 4/8/2024 | 355272 | FOOD SC | The railing to the ramp that leads from the loading dock to the Main Doors facing Wallace is chipped and there are several rust spots. Low priority | Deanna Powell | Assigned |
| 5/23/2024 | 363934 | 1626 FOOD SC | Please install the new latch (located in 2 boxes on the counter) on the hallway door so it can be locked and safe to get out. | Sarah Canova | Assigned |
| 5/29/2024 | 365017 | M0043 FOOD SC | Steam leak above water softener. | Ralph Nerem | Open |
| 12/27/2024 | 412104 | FOOD SC | Wet Sprinkler Inspection deficiencies: Control Valve-Room 1566 - 2.5” Osy Valve is severely corroded and leaking. Needs to be replaced. Take out measurement is 7.75 inches - Hiring Midwest Automatic fire sprinkler | Sailesh Gautam | On Hold |
| 3/6/2025 | 427705 | S2300 FOOD SC | FCU22 The heating valve is leaking. Pleas fix, thanks Bob. I shut the ball valve off so it's not leaking now, but no heat also. | Bob Betts | Assigned |
| 3/21/2025 | 429333 | FOOD SC | Generator needs a colorant flush due to a bad coolant sample Attn: Eric Robinson | Eric Robinson | Assigned |
| 5/20/2025 | 442654 | 1598 FOOD SC | The ISU Brew Lab is ready to get a cost estimate on installing trough floor drains between the existing floor drains in the lab. We currently have temporary sink/wash down stations in the lab and desire to procure and install a permanent sink station on one of the exterior walls. We are upgrading vessels in the brew lab that will require more chilling capacity, and so we will also be sourcing and purchasing a stand-alone chiller system that we would like to install remotely if possible. The desired location will either be in an adjoining utility closet next to the lab or, potentially in the second-floor maintenance utility room next to the lab. This would require utility lines to be run through the wall. Considerations for the chiller would be either liquid cooled or air cooled, depending on the existing chilled water supply and locations. The last portion of our project includes either relocating or installing a new engineered work platform above current vessels as well as installing several of our existing vessels in an elevated configuration to take advantage of vertical work space in the lab. Once the project begins, we can provide the exact dimensions and layout of the work platform being considered. This platform is either already existing and would be relocated from the BCRF or internally designed and sent out for fabrication to be installed. This project request is to get location and design approval from FP&M and not the actual design, purchasing or installation. The sink and trough will need to be purchased and installed/managed by FP&M. | Jordan Funkhouser | Open |
| 5/28/2025 | 443854 | FOOD SC | Flow switch and tamper switch did not report to panel. | Maintenance Support Admin | Open |
| 6/21/2025 | 449713 | 2379 FOOD SC | FY26 Fire Extinguishing Inspection and Repair Fees FES1 - FOOD SC | FPM Service Desk | Open |
| 6/21/2025 | 449718 | 2951 FOOD SC | FY26 Fire Extinguishing Inspection and Repair Fees FES2 - FOOD SC | FPM Service Desk | Open |
| 6/23/2025 | 450794 | GENERAL FOOD SC | Adding pad driver holder onto buffer. Does not have an E0 on machine. Attn Brock Palar | Brock Palar | Materials-Awaiting |
| 6/27/2025 | 453141 | 1091 FOOD SC | Steam supply ball valve handle has rusted off and will need replacement but will require steam shutdown to room. Located in south east corner of lab | Mitchel Michel | Assigned |
| 7/2/2025 | 457248 | 1854 FOOD SC | Att. Brock Vacuum roller is not turning to pick stuff up | Heather Williams | Materials-Awaiting |
| 7/2/2025 | 457546 | M0621 FOOD SC | Replace and align belts and sheaves. Please assign to me. | Donald Gregory |
Closed 1/22/2026
|
| 7/17/2025 | 459685 | FOOD SC | Repair Wet Sprinkler deficiencies: See Report ATTN: Tim Kelley | Sailesh Gautam | Assigned |
| 7/21/2025 | 459955 | 1854 FOOD SC | Att. Brock | Heather Williams | Materials-Awaiting |
| 7/25/2025 | 460652 | FOOD SC | Elevator is not working - outside the pilot plant FOOD SC floor 1 Additional location information: Elevator on the west side of first floor is not working | Ruth MacDonald | Assigned |
| 7/28/2025 | 461165 | 1578 FOOD SC | The cover of the floor drain in front of the sink in this room is loose and can easily be removed by stepping on it wrong/ or picking it up with your hand. I would like the cover to be properly screwed back onto the floor drain. Additional location information: Floor drain in front of the sink in this room. Work tags to attach: PG107300, DD00233 | Allison Little | Assigned |
| 8/22/2025 | 466740 | GENERAL FOOD SC | Floor scrubber isnt working as should , not suckin up water very well , especially on turns , leaves it lay ? Please Help | Chris Kraft | Materials-Awaiting |
| 8/25/2025 | 466909 | GENERAL FOOD SC | T350 Auto scrubber eo# 63062 has a ripped suction hose , needs repaired or replaced ... Please & Thank You | Chris Kraft | Materials-Awaiting |
| 9/23/2025 | 474597 | E1051 FOOD SC | Elevator is not working next to the creamery stairs. On first floor | Heather Williams | Assigned |
| 9/23/2025 | 474680 | X1010 FOOD SC | FCU 10 has a bad motor on the right side of the unit. This unit is in the entryway and on the ground. Please replace the motor. Assign to Scott Nibbe or Don G. | Nick Delahoussaye |
Closed 1/22/2026
|
| 9/29/2025 | 475396 | FOOD SC | Metasys Engine offline need to replace | Joe Flaherty | Assigned |
| 10/2/2025 | 478798 | 2591 FOOD SC | We have several refrigerators/freezers that need service: In 2591 Freezer not working FOOD SC Work tags to attach: PG102549 | Ruth MacDonald | Assigned |
| 10/2/2025 | 478802 | FOOD SC | We have several refrigerators/freezers that need service: In the Brew lab: Single Door Fridge- Temp read out doesn’t work but will cool - SN:1-2976197 Work tags to attach: PG102549 | Ruth MacDonald | Assigned |
| 10/2/2025 | 478806 | FOOD SC | We have several refrigerators/freezers that need service: In the Brew lab: Double Door Freezer – Doesn’t cool at all or power cycle properly – SN:1-2834941 Work tags to attach: PG102549 | Ruth MacDonald | Open |
| 10/2/2025 | 478808 | 2544 FOOD SC | We have several refrigerators/freezers that need service: In room 2544: Single Door Fridge – Temp read out doesn’t work but will cool– SN:1-2976184 Work tags to attach: PG102549 | Ruth MacDonald | Assigned |
| 10/10/2025 | 479529 | 2592 FOOD SC | URGENT REQUEST! There are several lights burnt out in 2592 FSB. This is a sensory booth room. We have a research project starting Monday, 10/13, and need the light bulbs replaced before 11:00 a.m. on Monday. The door should be unlocked, but if not, please come to 2312 FSB for a key. Thank you for your assistance. | Brenda Emery | Assigned |
| 10/13/2025 | 479646 | R1278 FOOD SC | The toilets have been getting clogged and has over flowed recently. Was wondering if could put a snake down the drain or something. The supervisors suggested this. | Heather Williams | Assigned |
| 10/17/2025 | 480014 | FOOD SC | Remove grates and clean out sump. Caulk around window sill outside of room 1333 and 1337 on exterior of building. | Morgan Linley | Open |
| 10/20/2025 | 480095 | 1581 FOOD SC | Light bulb is out in room the first set the middle one | Heather Williams |
Closed 1/12/2026
|
| 10/20/2025 | 480096 | 1577 FOOD SC | Light bulbs are out in this room on the right side of the room | Heather Williams |
Closed 1/12/2026
|
| 10/20/2025 | 480097 | 1575 FOOD SC | Light bulbs are out in this room when you first walk in | Heather Williams |
Closed 1/12/2026
|
| 10/20/2025 | 480098 | 1543 FOOD SC | Light bulb is out in this room back by the wall | Heather Williams |
Closed 1/15/2026
|
| 10/20/2025 | 480099 | 1545 FOOD SC | Light bulb is out in this room by the back wall next to window | Heather Williams |
Closed 1/13/2026
|
| 10/20/2025 | 480100 | 1551 FOOD SC | Light bulbs are out in the middle set on the right hand side | Heather Williams |
Closed 1/13/2026
|
| 10/20/2025 | 480101 | 1555 FOOD SC | Light bulbs are out next to window | Heather Williams |
Closed 1/12/2026
|
| 10/24/2025 | 480723 | 1751A FOOD SC | Loading dock hydraulic lift making noise at top of hydraulic cylinder stroke, potential low reservoir? | Mitchel Michel |
Closed 1/22/2026
|
| 10/27/2025 | 481028 | 2319 FOOD SC | Jen Kalinoy @ 4-3011 called and report the radiator is leaking hot steam and water. | Gina Holtzbauer | Assigned |
| 10/31/2025 | 481454 | 2591 FOOD SC | Replace door gasket | Sarah Canova |
Closed 12/31/2025
|
| 10/31/2025 | 481460 | FOOD SC | Call Back Sewage sump pit high alarm. | Richard Lyon | Materials-Awaiting |
| 11/6/2025 | 485641 | FOOD SC | Technician received a call that the elevator was not running after KONE safety test. Found doors out of track and leveling unit hitting hoistway flags. Repositioned doors, adjusted and plumbed leveling unit. Returned car to service. Schumacher Invoice 90663884 2 Hours x $248.23 = $496.46 | Ryan Rieke | Open |
| 11/10/2025 | 485895 | 2591 FOOD SC | Refrigerator/display case for the Creamery is not holding temperature. We submitted a work order for this previously but it does not seem to have been repaired. Work tags to attach: PG102324 | Ruth MacDonald | Assigned |
| 11/11/2025 | 485978 | 2953 FOOD SC | Please wax the floor of retail store. I'll have everything emptied by December 23rd and I need to move freezers back into the room on January 12th. | Sarah Canova |
Closed 1/9/2026
|
| 12/1/2025 | 487266 | 1553 FOOD SC | Amy Vorst Office reads 60 degrees not sure of the room # | Amy Vorst | Open |
| 12/1/2025 | 487305 | FOOD SC | Attn: Don Boyle Food Science. AHU2, 7, 8. and 16 OFF | Donald Boyle | Assigned |
| 12/2/2025 | 490776 | GENERAL FOOD SC | C2377 north west elevator is not working in FoodScience | Chris Kraft | Assigned |
| 12/2/2025 | 490783 | FOOD SC | Mixed air temp law alarm on AHU 15 - in and out of trouble. | Rachel Chunn | Assigned |
| 12/2/2025 | 490837 | C1950 FOOD SC | Several light bulbs are out in the hallway between c1090 and 1950-3 on the right hand side | Heather Williams |
Closed 12/29/2025
|
| 12/2/2025 | 490840 | C1090 FOOD SC | 6 light bulbs are out in the hallway between c1090 and cc1130 door ways. | Heather Williams |
Closed 12/29/2025
|
| 12/2/2025 | 490852 | R2349A FOOD SC | Very hot! | Allison Anderson | Assigned |
| 12/3/2025 | 491021 | 2578 FOOD SC | Roof leaking in the lab on room 2578 onto some research equipment | Andrew Makowski | Assigned |
| 12/8/2025 | 491663 | 2379 FOOD SC | Jan Kalinay, 4-3011, called in stating room was cold. | Gina Holtzbauer | Assigned |
| 12/9/2025 | 491758 | 1544 FOOD SC | Incorrectly located outlet for 240V 30A (L6-30R) service outlet. It is currently incorrectly located on a wall rather than on the central island for availability for instrumentation hookup. | Mark Early |
Closed 1/12/2026
|
| 12/9/2025 | 491779 | FOOD SC | Burned out lights in hallway outside of room 1951 need replacement FOOD SC floor 1 Additional location information: Burned out lights need replacing in the hallway outside of room 1951 | Ruth MacDonald |
Closed 12/29/2025
|
| 12/11/2025 | 492146 | 1091 FOOD SC | water leak dripping onto overhead door way in northeast corner of room 1091 space. Specifically the overhead door leading into room 1857. Uncertain of water leak source. | Mitchel Michel | Assigned |
| 12/16/2025 | 492876 | FOOD SC | The hallway is very cold - only one register seems to be warm FOOD SC floor 1 Additional location information: North side of the courtyard hallway Replaced on t-stat Bledair heatin valves were stuch 10+) | Ruth MacDonald | Assigned |
| 12/17/2025 | 492949 | M0621 FOOD SC | Sump pump DWP4 has a rusted out drain pipe that leaks when pump runs. Please fix. Thanks, Bob | Bob Betts |
Closed 1/9/2026
|
| 12/23/2025 | 493422 | 1598 FOOD SC | Occupants of the space are complaining that the domestic cold water has a "stinky" smell to it. Please investigate this. | Michael McCoy |
Closed 1/21/2026
|
| 1/7/2026 | 496886 | R1274 FOOD SC | First lightbulb in women's restroom is out | Katlynd Vsetecka |
Closed 1/9/2026
|
| 1/7/2026 | 496887 | R1278 FOOD SC | First lightbulb is out in mens restroom | Katlynd Vsetecka |
Closed 1/9/2026
|
| 1/7/2026 | 496888 | M2959AA FOOD SC | Air exchanger is squeeling so bad you can hear it down the halls (belts) | Chris Kraft | Assigned |
| 1/8/2026 | 496956 | 1598 FOOD SC | plumb a new cold water spigot for student work station to support lab. Forward to Morgan Linley | Jordan Funkhouser | Assigned |
| 1/9/2026 | 497167 | 1598 FOOD SC | relocate 2 outlets for student work stations. Relocate brewhouse power cable to another panel. All outlets are existing, it is only relocating in the lab. Contact Jordan for further specific locations. (515)520-3685 | Jordan Funkhouser | Assigned |
| 1/14/2026 | 497395 | C2310 FOOD SC | paint and touch up wall next to door way to stairwell. | Morgan Linley | Assigned |
| 1/14/2026 | 497397 | 1383 FOOD SC | 1383-1 sink location May need to have door unlocked, call me at 319-499-8145 Additional location information: 1383-1 sink location May need to have door unlocked, call me at 319-499-8145 | Sara Bazyn |
Closed 1/21/2026
|
| 1/14/2026 | 497398 | FOOD SC | brick has lost grout under the windows in several places FOOD SC floor 1 Additional location information: west hallway - courtyard side of the wall | Ruth MacDonald | Assigned |
| 1/15/2026 | 497536 | 1383 FOOD SC | Called to clean up a leak, swept to drain and it's plugged. Please clear this drain just inside the door. | Chris Kraft |
Closed 1/21/2026
|
| 1/16/2026 | 497696 | FOOD SC | the handicapped accessible door - external - is not working FOOD SC floor 2 Additional location information: the handicapped accessible door is not working - north side of building | Ruth MacDonald |
Closed 1/21/2026
|
| 1/20/2026 | 497854 | M1345 FOOD SC | Reinsulate 6 inch chill water piping after new valve installation. Please give to Insulator Larry Whitehill. Thanks | Larry Whitehill | Assigned |
| 1/20/2026 | 497899 | 3383 FOOD SC | replace non working lights | Ruth MacDonald |
Closed 1/22/2026
|
| 1/20/2026 | 497900 | FOOD SC | replace non working lights in the hallway FOOD SC floor 3 | Ruth MacDonald |
Closed 1/22/2026
|
| 1/21/2026 | 497955 | 1091 FOOD SC | Our smaller pasteurizer needs a heating element replaced. We have the replacement and the instructions. Please email and coordinate a time to do this since we will be running production starting next week. | Danielle Christofferson | Assigned |
| 1/23/2026 | 498188 | GENERAL FOOD SC | Heater inside FoodScience entrance cx1600 (between Hamilton & FS) sure makes alot of noise but NO HEAT ? Please Help ... | Chris Kraft | Assigned |