Date | WO # | Location | Description | Requester | Status |
---|---|---|---|---|---|
8/16/2022 | 216177 | 3241 HACH | The gas regulator in hood #39122 connecting the nitrogen tanks is leaking. | Shengkai Wei | Materials-Awaiting |
3/13/2023 | 266163 | 0215A HACH | while working on another room I notice a low temp alarm for 215A in metasys the room was showing a temp in the upper 50's but the room was 73 | Jeffrey Lamb | On Hold |
4/13/2023 | 273163 | HACH | W side of building is extremely hot. | David Appy | Open |
4/24/2023 | 274032 | 2206 HACH | Fume Hood in Lab is Increasing in Speed on it's own. Contact: Iqtidar Hussain in Office 2306 | Iqtidar Hussain | Open |
6/19/2023 | 287556 | 2211 HACH | Fume hoods in rooms 2211 and 2161 are not working. | M Dissanayake | Assigned |
8/23/2023 | 303492 | 0231A HACH | 0231A too cold. | David Appy | Assigned |
1/23/2024 | 336820 | GENERAL HACH | Attention Jeremy F EF-2 STROBIC fan is tripping the breaker investigate this issue | Dustin Limoges | On Hold |
2/9/2024 | 342156 | HACH | Please pick up JLG lift E049817 located in penthouse, and deliver to General Services Building loading dock. Must be done by Thursday 2/15/23 | Mark Wyant | Open |
3/5/2024 | 348227 | 0250 HACH | Fume hoods in this room alarm when the sashes are fully closed. Please adjust setpoint so that hoods will not alarm when sashes are fully closed. | Nicole Brandon | Assigned |
4/11/2024 | 355522 | GENERAL HACH | EF-12 VFD REPLACE OR REPAIR | Dustin Limoges | Materials-Awaiting |
4/24/2024 | 356751 | 2306 HACH | Fume hood needs service from a couple issues - Please see Iqtidar for details. | Iqtidar Hussain | Assigned |
5/3/2024 | 362158 | 3161 HACH | From Inspection 10303 - Fume Hood E039089 alarms when at 18 inch sash height. | Brandon Thompson | Assigned |
5/3/2024 | 362159 | 3161 HACH | From Inspection 10308 - Fume Hood E039091 alarms when at 18 inch sash height. | Brandon Thompson | Assigned |
5/3/2024 | 362161 | 3181 HACH | From Inspection 10313 - Fume Hood E039104 alarms when at 18 inch sash height. | Brandon Thompson | Assigned |
5/3/2024 | 362162 | 3191 HACH | From Inspection 10316 - Fume Hood E039114 alarms when at 18 inch sash height. | Brandon Thompson | Assigned |
5/3/2024 | 362163 | 3181 HACH | From Inspection 10314 - Fume Hood E039105 has a low face velocity of 48. Please service to an acceptable range (70-150). | Brandon Thompson | Assigned |
5/6/2024 | 362225 | 3252 HACH | From Inspection 10355 - Fume Hood E039145 has a low face velocity of 37. Please service to an acceptable range (70-150). | Brandon Thompson | Assigned |
5/10/2024 | 362643 | 3128 HACH | The window cannot be opened. Please fix. | Junqi Li | Materials-Awaiting |
5/20/2024 | 363554 | HACH | call back for 18 May -DPS called south side air handlers in alarm | DPS dispatch DPS | Assigned |
7/20/2024 | 376780 | 3101B HACH | Please paint walls for new incoming assistant Organic Professor. | Angela Harms | Assigned |
7/20/2024 | 376781 | 3101C HACH | Please paint walls- a few spots are rough. Needs a touch Up- | Angela Harms | Assigned |
7/23/2024 | 376934 | 0103 HACH | sheetrock repair has been completed and needs to be painted just outside the men's bathroom. | Michael Mosch | Assigned |
7/23/2024 | 376996 | 0101A HACH | Repair Fire Alarm Panel System deficiencies: Smoke detector M1-156 2nd flr west elevator lobby - missing cap 4098-9714 Elevator shunt trip passenger elevator - did not shunt trip with top of shaft heat or machine room heat detectors | Lyle Bishop | Assigned |
8/8/2024 | 382469 | 3271 HACH | Hach - Lab door 3271-1 Room air pressure regulator is leaking air through the body of the valve and needs to be replaced. | Michael Fields | Assigned |
8/16/2024 | 383331 | 0211 HACH | Location: Hach 0211 & 0231 A Problem: The thermostat doesn't work in the room. The room is getting colder and colder. The current temperature is about 62F. Please take the necessary actions asap. Thanks. Best, Sujeewa | Sujeewa Lamahewage | Assigned |
8/16/2024 | 383334 | 0211 HACH | Location: Hach 0211 & 0231 A Problem: The thermostat doesn''t work in the room. The room is getting colder and colder. The current temperature is about 62F. Please take the necessary actions asap. Thanks. Best, Sujeewa | Sujeewa Lamahewage | Assigned |
9/16/2024 | 390187 | 0119 HACH | Installing a Flexim ultrasonic meter in place of a failed Rosemount mag tube. | Isaac Maffett | Open |
9/19/2024 | 390558 | 1207 HACH | 1207 and 1225 hoods do not work. | Halyna Mudryk | Assigned |
9/20/2024 | 390776 | 1225 HACH | Fume hood alarms going off. | Teresa Fernando | Open |
9/24/2024 | 391052 | 1225 HACH | Fume hoods are down | Halyna Mudryk | Assigned |
9/25/2024 | 391242 | 1208 HACH | Room temp is too high, it is 77.7 F and I think it is still rising. | Halyna Mudryk | Assigned |
9/25/2024 | 391321 | 2242 HACH | There is some sort of brown liquid dripping down from within the acid hood in this room. Can the location from where it comes from be found? | Gabriela Keeney | Assigned |
10/7/2024 | 396277 | 1225 HACH | Fume hoods alarming in 1225. | Halyna Mudryk | Assigned |
10/14/2024 | 396781 | 1225 HACH | Room 1225, student hood with a broken vacuum valve. Hood number E038990. The valve is held in place by a pin, I found the pin in the drawer below, but it was broken, so I was not able to repair the valve. | Halyna Mudryk | Assigned |
10/22/2024 | 397540 | 1208 HACH | air handler down - Fume hoods beeping | Halyna Mudryk | Assigned |
10/24/2024 | 397769 | 0204 HACH | Special Hazardous Waste Disposal - Chemistry Dept. | Brady Harfst | Open |
10/24/2024 | 397771 | 2162 HACH | Special Hazardous Waste Disposal - Chemistry Dept. (Vela-Becerra, Koeritz) | Brady Harfst | Open |
10/24/2024 | 397773 | 2211 HACH | Special Hazardous Waste Disposal - Chemistry Dept. (Winter/Koeritz) | Brady Harfst | Open |
10/24/2024 | 397774 | 3252 HACH | Special Hazardous Waste Disposal - Chemistry Dept (Stanley/Koeritz 3252) | Brady Harfst | Open |
10/24/2024 | 397776 | 3191 HACH | Special Hazardous Waste Disposal - Chemistry Dept. (Stanley/Koeritz 3191) | Brady Harfst | Open |
11/11/2024 | 403930 | 1210 HACH | Delta to perform major PM $6627.50 | Ryan Rieke |
Canceled 4/3/2025
|
11/11/2024 | 403932 | 1210 HACH | Delta to perform major PM $6627.50 | Ryan Rieke |
Canceled 4/3/2025
|
11/18/2024 | 404711 | 0204 HACH | One of the Hood in Hach 0204 (first one in the second row counting from right to left of the room once enter the 0204 door. I put a label on the door of the hood. The flow doesn't meet the requirement, so the hood makes an alarm constantly. Phone number: 5152947084 | Wenyu Huang | Assigned |
11/19/2024 | 404800 | HACH | Attn: Temperature Control Hach, AHU-3, Dirty Filter Alarm rattling see trend New filter have been installed. Sensor need calibration or High/ Low checked out | Donald Boyle | Assigned |
12/16/2024 | 410964 | 0101 HACH | Beacon Madeus to service and repair air compressor 1 - AC1 - E038011 in room 0101 Hach Hall | Brady Streit | Open |
1/21/2025 | 416353 | 4200 HACH | Replace VFD on AHU-5 return fan. | Jeremy Forristall | Assigned |
1/22/2025 | 416397 | 4200 HACH | Scope of work Replace VFD for AHU-5 supply fan | Jeremy Forristall | Assigned |
1/24/2025 | 416784 | 0204 HACH | Fume Hood in 0204 Hach show ACT Bad sign. The hood number is EF7, E049537. Phone number: 5152947084 | Wenyu Huang | Assigned |
1/28/2025 | 417572 | 4156 HACH | jlamb call back DPS called about AHU-1 low static alarm | DPS dispatch DPS | Assigned |
1/28/2025 | 417638 | 1225 HACH | Fume hood not working. | Ihor Hlova | Open |
1/28/2025 | 417665 | HACH | Elevator, passenger west, is not opening the doors on the first floor. | Joseph Saunders | Assigned |
1/30/2025 | 417832 | 1300 HACH | Interior vestibule door on north side is dragging substantially and scratching the tile | Sarah Cady | Assigned |
2/3/2025 | 420664 | 1207 HACH | Hood in 1207 is constantly beeping | Halyna Mudryk | Assigned |
2/4/2025 | 420764 | 4200 HACH | Hach Penthouse Mech Room - AHU 4 Steam Coil Leak Bottom steam coil on AHU 4 has multiple steam leaks in the south header tubes. Unit needs repaired as soon as possible. MF | Michael Fields |
Closed 4/22/2025
|
2/5/2025 | 421131 | 0320 HACH | Autoscrubber pad keeps picking up as I am autoscubbing EO24902 Hach tunnel closet 0320-1 | Jessica Archer | Materials-Awaiting |
2/11/2025 | 421775 | HACH | Replace supply fan on AHU-5 building is Hach hall. | Jeremy Forristall | Assigned |
2/11/2025 | 421776 | HACH | Replace VFD on exhaust fan 12 | Jeremy Forristall | Assigned |
2/13/2025 | 422011 | 0231 HACH | Light bulbs need to be replaced | Vincenzo Venditti | Assigned |
2/13/2025 | 422019 | HACH | Fire panel trouble | Hillary Anderson | Open |
2/20/2025 | 422588 | 1207 HACH | 1207 and 1225 both have hoods constantly in a alarm. | Halyna Mudryk | Assigned |
2/25/2025 | 423041 | 4200 HACH | AHU 3 VFD overheating. | Dana Wills | Assigned |
2/25/2025 | 423090 | 4200 HACH | Clean VFD'S on AHU'S 1,2 and 4. Please sent out a building notifier ahead of work. Attn. Dana | Michael Hanson | Assigned |
2/26/2025 | 423144 | 2225 HACH | I am in a lab in Hach Hall and we would like to to have the signs on our office updated to show the names of current group members. Here are the names and the rooms. If possible please use Arial bold. I have attached a photo of what we currently have if that helps. (Hach 2225) (Header) Zaikina Research Office Md Rubel Hossen Mahmudul Islam Rain Nisaga Wanigasekara (Hach 2235) (Header) Zaikina Research Office Sashini Bandara William Josul Paul Oftedahl Thomas Seymour-Cozzini | Paul Oftedahn |
Closed 4/25/2025
|
2/26/2025 | 423215 | 1225 HACH | Hoods in 1225 are intermittently beeping. Please silence them. | Halyna Mudryk | Assigned |
3/4/2025 | 427579 | 1232 HACH | Light bulb needs replacing in NMR lab. Note to FPM staff: ceiling is very high, and superconducting magnets require extra care to work around - please make sure no magnetic objects are placed in the vicinity of the magnet. | Sarah Cady |
Closed 4/17/2025
|
3/11/2025 | 428151 | HACH | Hello, I work on the second floor of Hach, but the heat is running, and the office temperature is between 78â?"80°F. Could you please look into this issue? Thank you so much. | Amanda Kramer | Assigned |
3/17/2025 | 428707 | 0250 HACH | The fume hood error we are receiving is “ACT bad” | Nicholas Tryon-Tasson | Assigned |
3/19/2025 | 428930 | 1211 HACH | Autoclave stopped working in the middle of a cycle. | Abdel Harrata | Assigned |
3/20/2025 | 429018 | GENERAL HACH | The vestibule door still scrapes slightly. The one next to it, I remember they shaved off some aluminum because they could not get it to stop sagging. Video, let me know if you can't see it (it's more important to hear it I guess). https://photos.app.goo.gl/gD9bZgCcGzjsf3U87 | Sarah Cady | Assigned |
3/20/2025 | 429239 | GENERAL HACH | Order new pad driver for Motor Scrub Stair scrubber. Attn Brock Palar | Brock Palar |
Closed 4/2/2025
|
3/25/2025 | 429560 | 0119 HACH | Backflow preventer, BFP5, dumping water on floor, not constant, but has flooded the room | Janet Schneider | Assigned |
3/28/2025 | 430533 | HACH | Hot in the building in general, but Hach 0203 and 3272 were where we got specific complaints that it was too hot. HACH Additional location information: 0203 and 3272 were named as very warm | Deanna Powell | Assigned |
4/2/2025 | 434114 | 3266 HACH | There are 3 bulbs out in this office. | Joseph Race |
Closed 4/15/2025
|
4/3/2025 | 434203 | 2140 HACH | The shades in the second floor conference room are not working. | Sarah Cady |
Closed 4/15/2025
|
4/3/2025 | 434222 | 2225 HACH | Intramural to Printing | Aaron Goebel |
Closed 4/25/2025
|
4/3/2025 | 434251 | 2242 HACH | Faucet dripping | Iqtidar Hussain |
Closed 4/7/2025
|
4/3/2025 | 434288 | 0204 HACH | From Inspection 13548 ; fume hood E049537 airflow is too low and needs brought up to acceptable range of 80-125 fpm. | Katelyn Thompson |
Closed 4/10/2025
|
4/4/2025 | 434316 | HACH | Hach hall needs sprayed for ants by the atrium. | Jessica Archer |
Closed 4/8/2025
|
4/8/2025 | 434567 | 1225 HACH | Fume hood not working properly, unsure if issue. | Halyna Mudryk | Materials-Awaiting |
4/8/2025 | 434608 | 1315 HACH | There is a code-required gate at the 1st floor landing to prevent people exiting from upper floors from continuing into the basement. This gate seems to have a custom fabricated gas-strut closer that is supposed to keep it shut. It seems that it can be held open by over-extending the gate, which defeats the purpose of the gate. We need to make it so that gate can't be held open, or it can be dropped by a magnetic holder, see Durham stairs for example. | Troy Carey |
Closed 4/28/2025
|
4/8/2025 | 434655 | 2166 HACH | The main water tap in the sink of the student kitchenette, located in 2166 Hach has stopped working. Little or no water comes out: see attached video for more details. Additional location information: The sink in the student kitchenette of this room. | Caleb Thompson |
Canceled 4/8/2025
|
4/8/2025 | 434656 | 2166 HACH | The main water tap in the sink of the student kitchenette, located in 2166 Hach has stopped working. Little or no water comes out: see attached video for more details. Additional location information: The sink in the student kitchenette of this room. | Caleb Thompson |
Closed 4/9/2025
|
4/10/2025 | 434921 | 2311 HACH | From Inspection 13642 ; fume hood E039062 airflow is too low and needs brought up to acceptable range of 80-125fpm. | Katelyn Thompson | On Hold |
4/14/2025 | 435089 | HACH | CW36 South side of Hach Hall old style LED only half the array is lighting. | John Rice | Open |
4/15/2025 | 435207 | 1214 HACH | Occupant of 1214 Hach is reporting a chemical smell building up in the room any time the door is closed for a period of an hour or more, most noticeable in the morning. She is wondering if the ventilation of the space can be investigated and air flow increased if possible. The space is a former instrumentation lab converted into an office, so the ventilation may have been previously configured for the lab and not an office occupant. | Halyna Mudryk | Assigned |
4/16/2025 | 435236 | 0251C HACH | Location: Hach 0251 basement, Anand Lab. Sanitary waste pipe is leaking on top of laboratory lab benches in 0251C. | Beatrise Berzina | Assigned |
4/17/2025 | 435383 | HACH | Penthouse compressor #3 has a large air leak. | Michael Fields | Materials-Awaiting |
4/17/2025 | 435457 | 2212 HACH | From Inspection 13724 ; fume hood E039032 airflow is too low and needs brought up to acceptable range of 80-125 fpm. | Katelyn Thompson | Assigned |
4/18/2025 | 435560 | 1207 HACH | From Inspection 13744 ; fume hood E038929 airflow is too low and needs brought up to acceptable range of 80-125 fpm | Katelyn Thompson | Assigned |
4/18/2025 | 435562 | 1207 HACH | From Inspection 13746 ; fume hood E038931 airflow is too low and needs brought up to acceptable range of 80-125fpm. | Katelyn Thompson | Assigned |
4/21/2025 | 435611 | 1214 HACH | The room is uncomfortably cold - 66F. Would it be possible to raise the temperature to 72-73F? Work tags to attach: PG101329 DD15350 | Halyna Mudryk | Assigned |
4/22/2025 | 435737 | 1208 HACH | The room temp is currently 62.8 F. Would it be possible to raise the temp to closer to 70 F? Work tags to attach: PG101329 DD15350 | Halyna Mudryk | Assigned |
4/22/2025 | 435752 | 1101 HACH | Door for the Thiel Atrium is broken - please fix | Angela Harms |
Closed 4/23/2025
|
4/22/2025 | 435782 | 1208 HACH | Fume hood down | Yaroslav Mudryk | Open |
4/23/2025 | 435899 | 2162 HACH | The door to Hach 2162 isnâ?Tt closing properly. It can only be fully closed from the inside, and even then, we have to lift the door slightly to get it to shut. Could you please take a look at this issue? Thank you for your help. Phone number: 515-715-3750 | Lee Woolin |
Closed 4/28/2025
|
4/25/2025 | 436049 | D HACH | Hire HM Cragg to perform 2 Hour Load Bank Tests on Emergency Generators. | Anthony Gervais | Open |
4/28/2025 | 436814 | 3151 HACH | Light was flickering in mens restroom so tried to change it and it continues to flicker called Clint to look at and he replaced valance | Jessica Archer | Assigned |
4/30/2025 | 437150 | 3241 HACH | From Inspection 13927 ; fume hood E039124 airflow is too low and needs brought up to acceptable range of 80-125 fpm. | Katelyn Thompson | Assigned |
5/1/2025 | 437186 | HACH | Light out in stairwell 2155 and stairwell 3315 | Jessica Archer | Assigned |
5/1/2025 | 437250 | 0211 HACH | Sink in 0211 Hach Hall drains slowly. | Benjamin Atterberry | Assigned |
5/1/2025 | 437254 | 3242 HACH | From Inspection 13951 ; fume hood E039128 airflow is too low and needs brought up to acceptable range between 80-125 fpm. | Katelyn Thompson | Open |