Work Order Lookup

Date WO # Location Description Requester Status
12/19/2022 246819 1414 MOL-BIO end caps on the following rows are missing either screws, spacers, or both. B north side, C both ends, H north end, G north end, F north end Janet Schneider Assigned
4/5/2023 272465 0114 MOL-BIO 0114 MBB - This lab room is over cooling. Peter Lelonek Assigned
7/24/2023 295668 MOL-BIO Replace transfer switch on generator Derick Anderson Assigned
1/23/2024 336949 3177 MOL-BIO 3177 MBB - The humidifier in this fly stock warm room started leaking water into the room. users have unplugged it and shut off the water to it until it can be repaired. Peter Lelonek Materials-Awaiting
4/3/2024 354858 R2037 MOL-BIO They urinal will not flush and go down. It's not running down the wall anymore now.It just won't flush. Brandina Gallardo Herrera Materials-Awaiting
4/8/2024 355252 2312 MOL-BIO Please check the controls for this greenhouse - The heating and cooling systems are not working properly here. Peter Lelonek Assigned
4/8/2024 355263 2328 MOL-BIO 2328 MBB - This greenhouse room is not controlling correctly and is overheating Peter Lelonek Assigned
4/10/2024 355473 M0240 MOL-BIO AHU 3 is not working. NAE 147 is in fault. Peter Lelonek Assigned
4/17/2024 356122 2306 MOL-BIO 2306 hot Pete Lelonek Assigned
6/5/2024 368850 2306 MOL-BIO 2306 MBB - greenhouse room is overheating and keeps setting of temperature alarm. No windows are opening and no cooling. Jeff Lamb was working on and needs to come back and finish. Peter Lelonek Assigned
6/17/2024 369679 MOL-BIO Hire Midwest Sprinkler to extend a sprinkler pipe attn apepper Adam Pepper Assigned
6/19/2024 369871 M0240 MOL-BIO M0240 MBB - The cooling valve on AHU-8 is not opening up when the unit is running. There appears to be a control problem in METASYS. Peter Lelonek Assigned
6/23/2024 370969 0112 MOL-BIO FY25 MOL BIO - SLA for additional custodial services in rooms 0112 and 0114. Every 2 weeks to sweep, mop and empty trash. FPM Service Desk Open
7/25/2024 377237 M0144 MOL-BIO M0144 MBB - In this main electrical room there is a trough system under sewer piping that could leak into the room. I noticed today that the drain line from the trough down to the floor had a small stream of water running out of it. This means there is a leak somewhere in the piping above the trough. Peter Lelonek Assigned
10/9/2024 396510 M0240 MOL-BIO Hire Waldinger to replace failed motor bearings on AHU6 return fan. Lyle Bishop Closed
4/22/2025
10/25/2024 397865 MOL-BIO Utility outage for transfer switch. Jeremy Forristall Assigned
10/30/2024 398863 2141 MOL-BIO Power loss in IT room 2141 between 615-645. Please determine the cause and report to Lyle at 515-294-3813 Lyle Lovig Assigned
11/1/2024 399224 M1185 MOL-BIO Outside of custodial closet 1185 right next to the door there is some vandalism. Carved in letters and a chunk carved out as well. Tigra Sims Assigned
11/18/2024 404676 MOL-BIO ahu 7 VFD not working on supply fan Mark Schmitz Assigned
11/20/2024 404989 M0240 MOL-BIO have heat exchanger process water tested for oils. Nalco Joe Joe Judge Assigned
12/19/2024 411297 GENERAL MOL-BIO Generator has original belts and needs replacement due to age and wear on belts Attention to Eric Robinson Eric Robinson Assigned
1/15/2025 415738 0124 MOL-BIO Multiple lights are burnt out. At least 5 can lights and a few more fluorescent tube/bulbs are out. Lucas Showman Closed
4/21/2025
1/16/2025 415917 3242 MOL-BIO 3242 MBB - The control valve diaphragm on the heating coil above the ceiling is leaking air so temperature control is not good. I have partially closed the manual valve next to the control valve to help with temp control until repairs can be done. Peter Lelonek Assigned
1/16/2025 415918 4242 MOL-BIO 4242 MBB - The control valve on the heating coil above the ceiling seems to be stuck closed so there is no heat in this lab. Peter Lelonek Assigned
1/22/2025 416427 MOL-BIO diagnose transfer switch for failure to operate correctly attn: Eric Robinson Eric Robinson Assigned
1/27/2025 417510 MOL-BIO jlamb call back for AHU-4 low limit alarm DPS dispatch DPS Assigned
1/29/2025 417741 M MOL-BIO Penthouse 5100 - Exhaust fan EF6B has stopped running. It appears there is an issue in Controls/METASYS that is keeping it off. Peter Lelonek Assigned
1/29/2025 417772 MOL-BIO Cooling water system turned off for multiple cold rooms, it is back on now but needs reset. Room numbers are 2181, 2131, 2235, 4135, 4281, 4235. Peter Lelonek On Hold
1/29/2025 417788 M0240 MOL-BIO Moly Bio - Basement Mech Room 0240 AHU 5 - Fan B (Green Fan) is making noise. Please verify the fan motor bearings are in running condition. MF Michael Fields Closed
4/17/2025
2/6/2025 421202 M0240 MOL-BIO repair/replace steam pop-off valve, leaking. Drain line from it to drain is corroded and needs replaced also. SE corner of mechanical room. Janet Schneider Assigned
2/6/2025 421225 0124 MOL-BIO 0124 MBB - The DI water faucet in this lab has very low flow. This is a metal faucet and may just need a new seal. The regular water faucet next to it is also leaking from multiple locations when used and needs some repair. Peter Lelonek Closed
4/16/2025
2/12/2025 421839 R1405 MOL-BIO Light flickering rapidly over 2nd stall. Quintin Long Closed
4/29/2025
2/14/2025 422059 2377 MOL-BIO 2377 MBB - This greenhouse is not cooling consistently. Thermostat does not seem to be working correctly. Peter Lelonek Assigned
2/18/2025 422340 C2310 MOL-BIO C2310 MBB - The two exhaust fans in this greenhouse hallway are not working correctly. EF-17A is not running at all and EF-17B is running but shows as not running in METASYS. This may be a METASYS issue. Peter Lelonek Assigned
2/18/2025 422395 M0240 MOL-BIO M0240 MBB - AHU-1 tripped out on freeze Stat this morning at ~11:50AM even though the unit had been running fine prior to that. I was able to get it reset. It appears the controls for the heating valves are erratic and possibly caused the freeze stat trip when the valves went completely closed. After the unit shut down I noticed that both heating valves were completely closed also. This should not be happening when it is below freezing outside. We have had issues with fire dampers closing in this system due to overheating when the unit trips out, but something should be changed in the controls so that the heating valves don't go completely closed. Contact Pete at 294-2699 if you need more information or history Peter Lelonek Assigned
2/18/2025 422402 M0240 MOL-BIO M0240 MBB - The low steam pressure reading in METASYS has been erratic lately and sometimes even shows as a negative number. I have checked several actual gages on the system and none of them were reading negative when METASYS was. I think the sensor may need to be replaced. Peter Lelonek Assigned
2/19/2025 422494 MOL-BIO The freight elevator is not working. For the last few days you had to push the floor button inside the elevator more then once before it would move. Now it it isn't working at all. Peter Lelonek Assigned
2/28/2025 424099 3237 MOL-BIO 3237 MBB - Replace all burnt out or dim lamps in this room. Peter Lelonek Closed
5/6/2025
3/7/2025 427792 4278 MOL-BIO Lab Cleanout - 4278 Molecular Biology Building (req. by Pete Lelonek) Peter Lelonek Open
3/17/2025 428710 1428 MOL-BIO make and install capacity sign, 25 chairs in room Janet Schneider Assigned
3/19/2025 428902 1190 MOL-BIO There are approximately 8 or so lights going out in lab 1190 and the research team has asked for them to be switched out. Tigra Sims Assigned
3/25/2025 429588 C2175 MOL-BIO One of the light bulbs along the corridor is not working. Candice Yee Wong Assigned
3/26/2025 429640 M1185 MOL-BIO The advance autoscrub in closet 1185 is missing a piece that holds the pad to the machine causing it to fall off and drag while using it. Tigra Sims Materials-Awaiting
3/27/2025 430458 2377 MOL-BIO 2377 MBB - This greenhouse room has no cooling and none of the windows are opening. It is over 120 degrees in there. There are plants that can't be moved. Please come and correct as soon as possible. Peter Lelonek Open
3/28/2025 430522 2245 MOL-BIO 2245 MBB - Replace any burnt out or dim lamps in this room Peter Lelonek Assigned
3/31/2025 430596 4278 MOL-BIO Lab Cleanout of 4278 MBB - Req. by P. Lelonek Brady Harfst Open
3/31/2025 430598 M0240 MOL-BIO M0240 MBB - AHU-8 is not following the occupied/unoccupied schedule setup in METASYS and appears to be running all of the time. Please correct. Peter Lelonek Assigned
4/1/2025 430761 4132 MOL-BIO 4132 MBB - Replace all burnt out, dim or yellow lamps. Also fix the light cover that has fallen down. Peter Lelonek Assigned
4/1/2025 430768 4132 MOL-BIO 4132 MBB - The first sink inside the door has a drain that drains slow and the faucet drips. Peter Lelonek Closed
4/14/2025
4/1/2025 430777 4138 MOL-BIO From Inspection 13505 ; fume hood E033013 airflow is too low and needs brought up to acceptable range of 80-125fpm. Katelyn Thompson Closed
4/21/2025
4/2/2025 434015 C4100 MOL-BIO Water is dripping from the ceiling just outside C4100 (the 4th floor hallway northeast of the atrium) Joseph Davidson Closed
5/7/2025
4/2/2025 434026 R1405 MOL-BIO In the women's second stall the light is out. Tigra Sims Closed
5/5/2025
4/2/2025 434027 R1404 MOL-BIO The light right outside of the men's restroom 1404 is out. Tigra Sims Closed
5/5/2025
4/2/2025 434102 M0240 MOL-BIO scope of work replace VFD on AHU-7 Jeremy Forristall Assigned
4/7/2025 434443 M0240 MOL-BIO Purchase replacement VFDs for air handler 7 Jeremy Forristall Assigned
4/7/2025 434471 4188 MOL-BIO 4188 MBB - one of the DI water faucets at the sinks has broken apart and was leaking. We shut the water off till it can be repaired. This lab will no longer be in use once it is cleaned out and the broken faucet is redundant. I would prefer to have it eliminated in lieu of repair and the DI lines tied together or cut above the ceiling. Peter Lelonek Assigned
4/7/2025 434474 M0240 MOL-BIO M0240 MBB - AHU3 return fan does not operate without an override. It appears that it doesn't have any return airflow signal in Metasys. Peter Lelonek Closed
4/21/2025
4/7/2025 434496 MOL-BIO PWP 8 has water all over the floor, but its running into a drain. Janet Schneider Materials-Awaiting
4/8/2025 434634 C4160 MOL-BIO Fire Code: None of the fire doors that separate the freight elevator landings from the building operate properly. Many coordinators are missing rollers. Troy Carey Materials-Awaiting
4/8/2025 434635 C3160 MOL-BIO Fire Code: None of the fire doors that separate the freight elevator landings from the building operate properly. Many coordinators are missing rollers. Troy Carey Materials-Awaiting
4/8/2025 434636 C2160 MOL-BIO Fire Code: None of the fire doors that separate the freight elevator landings from the building operate properly. Many coordinators are missing rollers. Troy Carey Materials-Awaiting
4/8/2025 434637 C1158 MOL-BIO Fire Code: None of the fire doors that separate the freight elevator landings from the building operate properly. Many coordinators are missing rollers. Troy Carey Materials-Awaiting
4/8/2025 434638 C0150 MOL-BIO Fire Code: None of the fire doors that separate the freight elevator landings from the building operate properly. Many coordinators are missing rollers. Troy Carey Materials-Awaiting
4/8/2025 434639 S0118 MOL-BIO Fire Code: Stairway fire door fails to latch. NE Stair basement. Troy Carey Materials-Awaiting
4/8/2025 434641 C0050 MOL-BIO Exit sign without number in C0050 near restrooms does not operate. Troy Carey Closed
5/2/2025
4/8/2025 434643 MOL-BIO The state of repair of other fire doors in the building raises concern that the automatic doors serving the atrium will not operate properly when the smoke evacuation system is activated. Arrange a functional test of the smoke evacuation atrium door sequence with EH&S with an emphasis on testing automatic door closing and verification of positive latching of all doors. Troy Carey Closed
4/18/2025
4/8/2025 434645 0112 MOL-BIO Block off the back of EXL110 so it can't be seen on the corridor side. Troy Carey Assigned
4/10/2025 434824 1320C MOL-BIO The light in front of room 1320c is going out. Tigra Sims Assigned
4/11/2025 434950 3192 MOL-BIO 3192 MBB - The DI water faucet just inside the door to this lab has a leak in the body of the faucet. The DI water to the lab has been shut off till the faucet can be repaired. Peter Lelonek Closed
5/2/2025
4/15/2025 435170 MOL-BIO The freight elevator has stopped working. A person had to pry themselves out in the basement when the doors didn't open completely. They said the doors do not look level and this may be why they only opened part way and tripped the elevator out. Peter Lelonek Assigned
4/15/2025 435171 1106A MOL-BIO 1104 and 1106A MBB - Replace any dim or burnt out lamps in these 2 rooms. Peter Lelonek Assigned
4/15/2025 435172 MOL-BIO The freight elevator in Molecular Biology isn't working. It's stuck on the basement level. The door won't open and it can't be summoned to another floor. Joseph Davidson Canceled
4/15/2025
4/15/2025 435198 3034 MOL-BIO 3034 MBB - replace all dim or burnt out lamps in this room. Peter Lelonek Assigned
4/16/2025 435228 R1404 MOL-BIO The water fountain located in front of men's restroom 1404 is not draining Tigra Sims Closed
4/28/2025
4/17/2025 435371 4193 MOL-BIO 4193 MBB - This cold room has stopped working. It has been switched off till it can be repaired. Peter Lelonek Assigned
4/17/2025 435439 3282 MOL-BIO Rooms 3282, 3278- Please have the floors cleaned and waxed in these labs over the summer months. Work and timing can be coordinated with Olga Zabotina in office 3212. Peter Lelonek Assigned
4/17/2025 435442 0124 MOL-BIO 0124 MBB - We believe the damper on fume exhaust fan FE-8 serving a hood exhaust in this lab is not open because they are not getting any flow. That hood fan and the other one in the room show the value on METASYS as not being able to be read. When I looked at the fan in the penthouse it was running but it appeared that the damper may have been closed. Peter Lelonek Assigned
4/22/2025 435714 2231 MOL-BIO a fan motor is not working and the guard needs reattached Michael Mosch Assigned
4/23/2025 435916 2306 MOL-BIO 2306 MBB - The west floor drain in this room is clogged. Peter Lelonek Assigned
4/24/2025 436003 M5100 MOL-BIO Electric motor on HEF 226 is not working Michael Mosch Assigned
4/24/2025 436012 0112 MOL-BIO 0112 MBB - This room contains a very expensive research instrument and the room is over heating. Keeping the room temperature consistent is critical for the instrument operation. There is a separate air handler for just this room is located above the ceiling in the adjacent room 0114. We have had recent issues with the cooling water system being dirty and clogging up other equipment in this area. The cooling water system has been cleaned but maybe it has also clogged this air handler before it was cleaned. Please have this looked at as soon as possible to prevent potential issues with the instrument. Peter Lelonek Assigned
4/28/2025 436904 MOL-BIO DPS called and asked for help resetting fire alarm panel. IO91 attn Duncan Wood Duncan Wood Assigned
4/29/2025 436928 M5200 MOL-BIO Moly Bio - West Penthouse M5200 On the South end of the penthouse is a plastic tank - glycol reservoir with a AXIOM pump on top of the tank. This pump assembly is leaking and needs to be replaced. (It doesn't look like the pump is the problem, it is the other parts the pump is connected to...) MF Michael Fields Assigned
4/30/2025 437026 1137 MOL-BIO Outside door 1137 multiple ceiling tiles need replaced. Attention Justin Rummans Justin Rummans Assigned
4/30/2025 437028 C1175 MOL-BIO Multiple ceiling tiles need replaced. Attention Justin Rummans Justin Rummans Assigned
4/30/2025 437029 C1265 MOL-BIO Multiple ceiling tiles need replaced. Attention Justin Rummans Justin Rummans Assigned
4/30/2025 437031 1210 MOL-BIO Outside room 1210 by elevator multiple ceiling tiles need replaced. Attention Justin Rummans Justin Rummans Assigned
4/30/2025 437032 R2013 MOL-BIO Ceiling tiles need replaced. Attention Justin Rummans Justin Rummans Assigned
4/30/2025 437033 2011 MOL-BIO Kitchenette outside room 2011 has a cabinet pull missing and a couple doors that need adjusted. Attention Craig Stevens. Craig Stevens Closed
5/7/2025
4/30/2025 437034 C2175 MOL-BIO Multiple ceiling tiles need replaced. Attention Justin Rummans Justin Rummans Assigned
4/30/2025 437035 C2200 MOL-BIO By elevator multiple ceiling tiles need replaced. Attention Justin Rummans Justin Rummans Assigned
4/30/2025 437036 C2200 MOL-BIO Door CC2200-1 has a loose door handle and also needs a new bump stop. Attention Craig Stevens. Craig Stevens Closed
5/5/2025
4/30/2025 437037 R3013 MOL-BIO Outside room 3013 multiple ceiling tiles need replaced. Attention Justin Rummans Justin Rummans Assigned
4/30/2025 437038 C3200 MOL-BIO Multiple ceiling tiles need replaced attention Justin Rummans Justin Rummans Assigned
4/30/2025 437040 C3225 MOL-BIO Carpet tile is peeling up and needs replaced. Trip hazard. Attention Craig Stevens. Craig Stevens Assigned
4/30/2025 437042 C3175 MOL-BIO Multiple ceiling tiles need replaced. Attention Justin Rummans Justin Rummans Assigned
4/30/2025 437043 4014 MOL-BIO Kitchenette outside room 4014 has some cabinet doors that need adjusted. Attention Craig Stevens. Craig Stevens Closed
5/5/2025
4/30/2025 437044 C4100 MOL-BIO Multiple ceiling tiles need replaced. Attention Justin Rummans Justin Rummans Assigned
4/30/2025 437051 C0120 MOL-BIO Both doors need new bump stops. attention Craig Stevens. Craig Stevens Closed
5/5/2025
4/30/2025 437138 3181 MOL-BIO 3181, 3178 and 3142 - please replace all lamps that are dim or out in these 3 rooms. Peter Lelonek Assigned
5/1/2025 437218 M0240 MOL-BIO Deionized water system in the basement needs new check valves ordered and replaced. Joe Judge Joe Judge Assigned
5/2/2025 441119 2372 MOL-BIO 2372 MBB - Two panels of glass on the west outside wall of this greenhouse room have slid down allowing insects to get into the room. We can deal with the insects but someone needs to fix the glass. Peter Lelonek Closed
5/5/2025
5/5/2025 441260 1160 MOL-BIO There is some flooding in this room. Please send over custodial with supper suckers to clean up. Benjamin Adams Assigned