Date | WO # | Location | Description | Requester | Status |
---|---|---|---|---|---|
10/22/2024 | 397506 | 0026 MORRILL | Attn JLAMB - Humidifier #1 is off line with message "thermo sensor" repair or replace as necessary | Jeffrey Lamb |
Closed 10/1/2025
|
10/23/2024 | 397572 | 2001 MORRILL | Safety issue- Lights out in stairway to auditorium and at the top of the landing by auditorium doors. | Valerie Hansen | Assigned |
1/9/2025 | 415205 | 0021 MORRILL | Attn Jlamb - Humidifier #2 is leaking replace the O-rings | Jeffrey Lamb |
Closed 10/1/2025
|
3/3/2025 | 427141 | 3024 MORRILL | Minor renovations and furniture needs in order to move into our new space in July 2025. | Kris Kilibarda | Open |
3/21/2025 | 429314 | 2001 MORRILL | One of the emergency lights is out in the stair entry to the auditorium. The rest of the emergency lights are on. | Valerie Hansen | Assigned |
4/15/2025 | 435148 | MORRILL | Estimate for Waddle to replace three snow stops | John Breon | On Hold |
4/16/2025 | 435232 | 2019 MORRILL | Security light is out at the back of the auditorium. Please check the lights (security and overhead) in the stairway to the auditorium. There's lots of lights out and could be a problem when it's dark outside. | Valerie Hansen | Assigned |
5/28/2025 | 443769 | MORRILL | Elevator is not working. It's not coming when called.It seems stuck somewhere. | Valerie Hansen | Assigned |
6/3/2025 | 447288 | MORRILL | Elevator would not move from Ground floor. Pressed buttons for multiple floors after it was not responsive and it would still not move. Then a high pitched sound came on and the doors opened. Elevator then delayed for several more minutes before moving. MORRILL Additional location information: Elevator | Alison Ranniger | Assigned |
6/20/2025 | 449389 | MORRILL | repair condensate valve in Morroll hall tunnel . Please ass. to Dave chenavert. | Scott Nibe | Open |
6/27/2025 | 453002 | MORRILL | Attention Josh Bremer Morrill Hall Humidity Issues in Gallary | Joshua Bremer | Assigned |
7/10/2025 | 458620 | 1019 MORRILL | There is a puddle of water in the lobby by the back door. Not sure if it is coming from the roof of the sprinklers. Have placed a caution sign temporarily to mark the spot. This is on the landing between the first floor and basement. | Valerie Hansen | Open |
7/14/2025 | 459098 | MORRILL | ATTN: jlamb Call back from DPS for 13JUL- high humidity alarm 7-1 | DPS Dispatch | Assigned |
7/14/2025 | 459099 | MORRILL | ATTN: jlamb Call back from DPS for 13JUL- high humidity alarm 8-1 | DPS Dispatch | Assigned |
7/16/2025 | 459569 | 1024 MORRILL | Temperature low- read on psychrometer as 50.7 degrees Additional location information: Loaned Object Storage | Caitlin Patton | Assigned |
7/16/2025 | 459581 | MORRILL | On Friday, July 11, approximately 12:45pm water began rushing into the basement level of Morrill Hall via the two exterior doors. The drains outside of each door, especially door 0001-1, were not draining properly and cumulated high levels of standing water. Carpets became soaked and baseboard is peeling away from the wall in room 0001 (mold is already present on baseboards due to continued issues with water coming in, and it still has not been addressed). Door 0001 is also not sealed properly on the bottom and the gasket on the door threshold needs replaced (is worn down/ falling apart and light is visible under the door). Not only for building safety, this a major concern for University Museums and the T&C Collections that are housed on this level. Room 0001 directly abuts our museum gallery (room 0003) and collections storage (room 0003-A). High levels of humidity and mold present can cause irreversible damage to objects in our collections. MORRILL floor B Additional location information: Entryway 0001, Door 0001-1 Entryway 0009, Door 0009 | Alison Ranniger | Assigned |
7/22/2025 | 460265 | MORRILL | There was an energy surge throughout the entire building and the elevator did not come back up. | Valerie Hansen | Open |
7/23/2025 | 460462 | 1026 MORRILL | Temperature is reading too cool in here - I got a Metasys alarm for 64F (Low). This is a museums collections storage, and temperature should be maintained in the range of 68-72 F. | Alison Ranniger | Assigned |
7/25/2025 | 460663 | MORRILL | Attention Josh Bremer Call Back: Morrill Hall 3rd floor rooms low temp | Joshua Bremer | Assigned |
7/29/2025 | 461280 | 0026 MORRILL | Fire Marshal Violation - Life Safety Please install a circuit breaker lock on the breaker connected to the FACP. Also provide a breaker location label on the FACP. Thank you! | Zachary Morgan | Open |
7/29/2025 | 461281 | GENERAL MORRILL | Fire Marshal Violation - Electrical Various locations have emergency lights that do not illuminate when tested. Emergency light (no EML number) near 1005 landing, and ECL6 Room 1023 near stairwell door | Zachary Morgan |
Closed 10/15/2025
|
7/29/2025 | 461282 | 1016 MORRILL | Fire Marshal Violation - Life Safety Missing fire sprinkler escutcheon, room 1016. | Zachary Morgan |
Closed 9/23/2025
|
7/30/2025 | 461395 | 0026 MORRILL | Repair Backflow Sprinkler deficiencies: Mechanical - Riser Room SPRINKLER BOTTOM BACKFLOW TAMPER M1-8 and M1-10 City Connection Control Valve: FAILURE REASON: NFPA 25 13.3.2.2* The valve inspection shall verify that the valves are in the following condition: (6) Provided with applicable identification ATTN: Kevin Vols | Sailesh Gautam |
Closed 9/24/2025
|
7/30/2025 | 461453 | MORRILL | Call back fire panel trouble outdoor strobe short circuit Attention Dustin Limoges The fire crew will need a follow up request order to resolve this issue | Dustin Limoges |
Closed 9/30/2025
|
7/30/2025 | 461484 | MORRILL | Call back fire panel trouble outdoor strobe short circuit | Dustin Limoges |
Closed 10/17/2025
|
8/4/2025 | 464443 | GENERAL MORRILL | Cover found on floor 2, which looks like for a cover for a sprinkler head. | Valerie Hansen |
Closed 10/17/2025
|
8/12/2025 | 465585 | 0026 MORRILL | Repair Drypipe sprinkler system deficiencies: Both pre-action Waterflow M1-162 and Dry System Waterflow M1-105 Report as a Zone and should be changed in programming as a Waterflow alarm in the panel.. ATTN: Duncan Wood | Sailesh Gautam | Assigned |
8/19/2025 | 466302 | 1017 MORRILL | This is an "after the fact" maintenance request - Barb Steiner and others worked at Morrill Hall yesterday for one hour (4 ppl total). This work needs to be charged to the worktag below. Work tags to attach: PG113015 DD19801 | Edith Hunter |
Closed 10/16/2025
|
9/4/2025 | 471607 | 1026 MORRILL | Excessive cold air in room 1026 - temperature is around 60F daily with high rH. Submitted a work order back in July and still not fixed - see Service Request 460462 | Alison Ranniger |
Closed 9/30/2025
|
9/15/2025 | 473637 | 0017 MORRILL | Temperature alarm listed as 76 degrees, doesn't feel that high in the gallery Additional location information: 1017A (Christian Petersen Art Museum gallery) | Caitlin Patton | Assigned |
9/17/2025 | 473884 | 1017 MORRILL | Receiving Metasys alerts for 76+ degree F in 1017 Morrill. Our hygrometer is reading 73-74 degree F. Metasys reading says it is for sensor "1017S" - please review this sensor for faulty readings. We have to take action for the safety of the museum collections in the case of out-of-range temp/rH readings so they need to be accurate and these high range readings alert us at all hours of the day, so please have this looked at ASAP. Additional location information: Christian Petersen Art Museum | Alison Ranniger | Assigned |
9/18/2025 | 474342 | MORRILL | High humidity (55%rH - 60rH+) Metasys alerts for museum spaces. We have dehumidifiers going in each room but we are still struggling to lower the humidity. For the safety of the museum collections, we need to keep the humidity between 45-50%rH. Please see what can be done to lower humidity in the building. MORRILL Additional location information: Christian Petersen Art Museum spaces, rooms 1017, 1026, 0003, 0003A | Alison Ranniger | Assigned |
9/19/2025 | 474428 | GENERAL MORRILL | The temperature is really cold on 2nd floor hallway and room 2026 and 2030. The rest of the building seems to be at the right temperature. | Valerie Hansen | Assigned |
9/22/2025 | 474545 | MORRILL | Someone pressed the button with the fire helmet symbol, so the elevator door is staying open and the elevator is unusable. I am not sure if there is FPM service happening on the elevator (I don't see anyone present). MORRILL floor 1 Additional location information: 1st floor elevator | Alison Ranniger | Assigned |
9/26/2025 | 474911 | 2030 MORRILL | There are 2 lights out in the room. | Valerie Hansen | Materials-Awaiting |
9/29/2025 | 475445 | 1017 MORRILL | Need Gary Puls and Brandon Bartleson to assist in removing large glass panels they installed for art exhibition. Must be on February 16, 2026. Additional location information: Christian Petersen Art Museum Work tags to attach: PG113015 DD19801 | Adrienne Gennett | Assigned |
10/1/2025 | 475695 | 0026 MORRILL | attn: Mike Solberg Steam leak in 2" line | James Bohl | Assigned |
10/10/2025 | 479509 | 1030 MORRILL | Light out in room. The best time to check it out is Monday, Wednesday, and Friday before 9:30. | Valerie Hansen |
Closed 10/16/2025
|
10/12/2025 | 479584 | MORRILL | Elevator is making alarm sounds and doors are only half opening, then finally closing. MORRILL Additional location information: Elevator | Alison Ranniger | Assigned |
10/14/2025 | 479725 | 2010 MORRILL | Light out in stairway next to the bathrooms. | Valerie Hansen | Assigned |
10/14/2025 | 479733 | 1018 MORRILL | Toilet seat cracked all the way through. Probably needs replacing. | Valerie Hansen |
Closed 10/17/2025
|
10/14/2025 | 479774 | 2015 MORRILL | Door 2015 is not working. They are saying that it's not responding to people's cards or codes. | Steven Ristvedt |
Closed 10/15/2025
|