Date |
WO # |
Location |
Description |
Requester |
Status |
10/7/2022 |
230635 |
0139 SCI 2 |
The lock for room 139 only opens for DAAA, and we'd like to add a student key. |
Jennifer McGill |
Open
|
4/11/2023 |
272859 |
SCI 2 |
night call burning the prairie south of the building |
Jeffrey Lamb |
Assigned
|
11/10/2023 |
323453 |
0045 SCI 2 |
Science 2 Building - Basement/NE Hallway/Room B0045 Chase in East Wall
Cast iron drain pipe has a crack in the piping and needs to be replaced. |
Michael Fields |
Assigned
|
2/28/2024 |
344558 |
0140 SCI 2 |
There are sagging celling tiles from the leak above. Please replace. |
Jennifer McGill |
Assigned
|
3/8/2024 |
348576 |
0528 SCI 2 |
Corroded pipes and starting to leak - adding to the list. Up in the ceiling near the fume hood |
Jennifer McGill |
Assigned
|
3/19/2024 |
349246 |
GENERAL SCI 2 |
A space survey was done by NREM in Science 2, trying to locate all of the leaks that currently need to be addressed or checked out before more serious leaks occur - The damaged parts of the ceiling will need to be addressed as well so that we know which areas are no longer a problem. Please note one may have already been submitted.
These rooms are for the 1st floor (I will submit for each floor):
0102 - Accumulating rust on the ceiling and water damage.
0115 - Rust and watermarks over desk
0128 - Large watermark and rust on wooden cabinet
0135 - Watermarks on ceiling and rusting ceiling supports
0141 - Small watermark and rust near the closet door. |
Jennifer McGill |
Assigned
|
3/19/2024 |
349247 |
GENERAL SCI 2 |
A space survey was done by NREM in Science 2, trying to locate all of the leaks that currently need to be addressed or checked out before more serious leaks occur - The damaged parts of the ceiling will need to be addressed as well so that we know which areas are no longer a problem. Please note one may have already been submitted.
These rooms are for the 2nd floor (I will submit for each floor):
0202 - Rusted supports in four places on the drop ceiling, especially around the fluorescent lights
0208 - Currently has a wet spot on the ceiling, likely a slow leak
0215 - Watermarks around both drop ceiling lights
0219 - Watermarks of unknown age
0232 Watermarks on ceiling
0233 - Watermark around light and rust on ceiling support |
Jennifer McGill |
Assigned
|
3/19/2024 |
349248 |
GENERAL SCI 2 |
A space survey was done by NREM in Science 2, trying to locate all of the leaks that currently need to be addressed or checked out before more serious leaks occur - The damaged parts of the ceiling will need to be addressed as well so that we know which areas are no longer a problem. Please note one may have already been submitted.
These rooms are for the 3rd floor (I will submit for each floor):
0306 - Middle of room by light, possible leak
0319 - Rust on ceiling support in back by the light
|
Jennifer McGill |
Assigned
|
3/19/2024 |
349249 |
GENERAL SCI 2 |
A space survey was done by NREM in Science 2, trying to locate all of the leaks that currently need to be addressed or checked out before more serious leaks occur - The damaged parts of the ceiling will need to be addressed as well so that we know which areas are no longer a problem. Please note one may have already been submitted.
These rooms are for the 4th floor (I will submit for each floor):
0404 - Rust on supports by fume hood
0409 - possible leak in the middle of the room
0433 - The back corner near the door - possible ceiling leak (the tile has been removed and there is a small container below that), also possible leak in the center of the room |
Jennifer McGill |
Assigned
|
3/19/2024 |
349261 |
GENERAL SCI 2 |
A space survey was done by NREM in Science 2, trying to locate all of the leaks that currently need to be addressed or checked out before more serious leaks occur - The damaged parts of the ceiling will need to be addressed as well so that we know which areas are no longer a problem. Please note one may have already been submitted.
These rooms are for the 5th floor (I will submit for each floor):
0526 - Possible leak in back of room
0528 - Already submitted - Ceiling near fume hood leaking
0539 - Way in the back where the ceiling tile is missing
|
Jennifer McGill |
Assigned
|
3/19/2024 |
349262 |
GENERAL SCI 2 |
A space survey was done by NREM in Science 2, trying to locate all of the leaks that currently need to be addressed or checked out before more serious leaks occur - The damaged parts of the ceiling will need to be addressed as well so that we know which areas are no longer a problem. Please note one may have already been submitted.
These rooms are for the 6th floor (I will submit for each floor):
0626 - Already submitted, leak in the back of the room under the drop ceiling and rust staining the floor tiles
|
Jennifer McGill |
Assigned
|
3/19/2024 |
349263 |
GENERAL SCI 2 |
A space survey was done by NREM in Science 2, trying to locate all of the leaks that currently need to be addressed or checked out before more serious leaks occur - The damaged parts of the ceiling will need to be addressed as well so that we know which areas are no longer a problem. Please note one may have already been submitted.
These rooms are for the Basement (I will submit for each floor):
039/039A - Leak in corner, dripping and mold in ceiling |
Jennifer McGill |
Assigned
|
4/19/2024 |
356283 |
0503 SCI 2 |
The radiator seems to be leaking, and there is water bubbling under the carpet near the window and near the center of the room. Please fix ASAP! |
Jennifer McGill |
Assigned
|
5/7/2024 |
362310 |
SCI 2 |
Install steam drip legs and blowdowns. |
David Chenevert |
Assigned
|
6/23/2024 |
370994 |
0537 SCI 2 |
FY25 SCI 2 - SLA Additional Cleaning Rm 537 |
FPM Service Desk |
Open
|
7/2/2024 |
375188 |
0082 SCI 2 |
Water fountain has been inoperable for quite some time - original work order 239005 looks to have been submitted on 11/11/2022 and was subsequently closed. Please fix! Thanks. |
Jennifer McGill |
Assigned
|
7/10/2024 |
375758 |
0339 SCI 2 |
Water leak from ceiling |
Jeri Kleckner |
Assigned
|
7/12/2024 |
376074 |
0780 SCI 2 |
Heater in hallway is kicking out heat - possible pneumatic thermostat issue? Unit is working but shouldn't be on this time of year. |
Jennifer McGill |
Assigned
|
7/29/2024 |
378220 |
0418 SCI 2 |
There is a broken pipe and water leaking in room 418 Science 2 |
Jennifer McGill |
Assigned
|
8/8/2024 |
382370 |
0202 SCI 2 |
Please mark attention: Aaron Moses
Room 202 Science 2 there are two lights that will not turn on
Room 220 Science 2 there are three lights that will not turn off, and two lights that are flickering |
Jennifer McGill |
Assigned
|
10/30/2024 |
398855 |
0631 SCI 2 |
VFD5, in alarm, alarm says, fan cooling, change fan and reset fan life time counter |
Janet Schneider |
Assigned
|
10/31/2024 |
398992 |
0030 SCI 2 |
Repair broken drywall hole in ceiling of room 0030 in basement. |
Lyle Bishop |
Assigned
|
11/21/2024 |
405044 |
0619 SCI 2 |
Investigate wires in conduit outside of room 0619. Make code compliant. (attention: Collin Dodge) |
Tamara Porter |
Assigned
|
2/17/2025 |
422257 |
SCI 2 |
I need 107, ADA wall signs installed at Science Hall 2. Lenses are ready for pickup at the main office (2333 Kooser Drive) of printing. Black frames were previously ordered and are in a box at Duane Strahs' old desk. Refer to install maps, attached. Please let me know if there are any questions. |
Jennifer Evans |
Assigned
|
2/25/2025 |
423043 |
GENERAL SCI 2 |
Lights starting to go out they are dimmer then rear of hall way next to room 201 |
Jeri Kleckner |
Assigned
|
3/4/2025 |
427235 |
GENERAL SCI 2 |
Hall light out next to room 312 |
Jeri Kleckner |
Assigned
|
3/6/2025 |
427656 |
0407 SCI 2 |
Light out in hallway next to room 407 |
Jeri Kleckner |
Assigned
|
3/7/2025 |
427728 |
0433 SCI 2 |
Room has 5 sets of lights out |
Jeri Kleckner |
Assigned
|
3/12/2025 |
428320 |
0592 SCI 2 |
Elevator closed on vacuum while I was cleaning it and would not open back up so it pulled off the vac attachment and now it's jammed in the door and the elevator won't move/door won't open
Technician found the door out of service timer had expired. He reset the timer, checked the operation of the door, checked overall operation and returned the elevator to service.
.5 Hour X $241.00 = $120.50 |
Victorea Banks |
Assigned
|
3/12/2025 |
428367 |
0043 SCI 2 |
Light in back corner is not working. |
Jennifer McGill |
Assigned
|
3/13/2025 |
428522 |
0306 SCI 2 |
There are quite a few lights that are not working in 306 |
Jennifer McGill |
Assigned
|
4/14/2025 |
435076 |
0220 SCI 2 |
There is a large coffee (?) stain in the front of the room by the podium that needs to be removed from the carpet. Can we please schedule a carpet cleaning for after May 5th? Thanks |
Jennifer McGill |
Assigned
|
4/23/2025 |
435914 |
0220 SCI 2 |
One of the light covers fell off the ceiling (during an exam). Up near the front, put back on loosely and not secured. Please fix! |
Jennifer McGill |
Assigned
|
4/24/2025 |
435959 |
0636 SCI 2 |
Light fixture out. Room 636 Science Hall II. The fixture above the desk. Thanks.
Phone number: 5154600542
|
Donald Lewis |
Assigned
|
4/30/2025 |
437117 |
0532 SCI 2 |
Light bulb out in office |
Victorea Banks |
Assigned
|
4/30/2025 |
437132 |
0123 SCI 2 |
one fan on RSF#1 is not working |
Michael Mosch |
Assigned
|
5/7/2025 |
441431 |
0003 SCI 2 |
Please hang the large whiteboard that was in 0106 Science 2 (currently leaning in the hallway outside room 0109) into room 0003 Science 2, the graduate student lounge. Please install on the East (green) wall. Thanks |
Jennifer McGill |
Assigned
|
5/7/2025 |
441433 |
0332 SCI 2 |
Please hang a corkboard (provided, on floor) on the wall outside office 0332 Science 2, to the right of the ADA signage and at the same height as the others in the hallway. Thanks. |
Jennifer McGill |
Assigned
|
5/14/2025 |
442101 |
0039A SCI 2 |
There is an active leak in the southwest corner of the room coming from the ceiling (you can see the existing rust) through the tiles.
This is an old problem that has not been fixed and is actively leaking currently. A cracked cast found leaking in pipe chase of Room 0135.
|
Jennifer McGill |
Assigned
|
5/15/2025 |
442163 |
0020 SCI 2 |
Replace buildings main chilled water valves. Vendor supported. |
Morgan Linley |
Open
|
5/19/2025 |
442500 |
0115 SCI 2 |
Science Hall #2 - Classroom 0115
Various stained ceiling tile to be replaced. Some tile will need to be cut to fit ceiling grid layout. |
Michael Fields |
Assigned
|
5/20/2025 |
442588 |
0321 SCI 2 |
Lock opens for change key but not easily for sub-master key; I couldn''t relock it when I was finished. Thanks! |
Jennifer McGill |
Assigned
|
5/20/2025 |
442706 |
SCI 2 |
Elevator entrapment at 8:24 pm. 4 individual stuck between 3rd and 4th floor. The riders were able to open a level and get out of the elevator. Schumacher was notified. |
Stephanie Gorden |
Open
|