Date | WO # | Location | Description | Requester | Status |
---|---|---|---|---|---|
7/3/2023 | 293232 | 2230 SPC | got a call from Eric 30 Jun at 3:52 PM saying the CW3 was running continuously I pulled up METASYS and notice that DC-1 control was "unreliable" opened it and was able to see there was an issue with the logic for the chill water pumps, did an edit on the logic and the issue went away saved the screen the "unreliable" went away for DC-1 controls and the unit shut off followed up with Dan on Saturday. | Eric Terrazas | Assigned |
10/21/2024 | 397304 | SPC | Change oil. "Check causes of oil breakdown - overheating, wrong lube, excessive service or contaminated sample" | Anthony Gervais | Assigned |
3/21/2025 | 429324 | SPC | Generator needs a colorant flush due to a bad coolant sample Attn: Eric Robinson | Eric Robinson | Assigned |
4/10/2025 | 434882 | SPC | I need the fire panel down from 7:30 am to 4 pm. on June 27th for the kitchen hood cleaning. | Miles Pankonen | Assigned |
4/22/2025 | 435696 | SPC | I need the fore panel taken down on 4-23 from 8 a.m. to 3:30 p.m., and we will let you know if we are done earlier than 3:30. | Miles Pankonen | Assigned |
4/25/2025 | 436063 | SPC | Hire HM Cragg to perform 2 Hour Load Bank Tests on Emergency Generators. | Anthony Gervais | Open |